Summary
B0603487
Building Permit - Commercial
Certificate of Occupancy
LEES SUMMIT SCHOOL DIST R 7
ADDITION COMMERCIAL
RENOVATION AND BUILDING ADDITION
11/21/2006
01/24/2007
03/31/2008
10/05/2007
Locations
Contacts
FIVE STAR PLUMBING INC, Address:26810 E ARGO RD  
TEAGUE ELECTRIC CONSTRUCTION, INC., Address:11325 STRANG LINE RD.  
MEYER BROTHERS, Address:200 NE MISSOURI RD  
F & G MECHANICAL SERVICES INC., Address:17219 BEL-RAY PL  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/23/2007 10/29/2010
Correction

CA - ANSI A117.1-1998 606.5 - Bowl depth. Sinks shall be 6.5 inches deep maximum. Multiple compartment sinks shall have at least one compartment complying with this requirement.
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1007.1 - Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1014.1 or 1018.1 from any accessible space, each accessible portoin of the space shall be served by not less than two accessible means of egress.
Correction

Codes Administration - 2003 IBC 1012.2 - Height. Guards shall form a protective barrier not less than 42 inches (1067 mm) high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard.
Correction

Codes Administration - 2003 IBC 1012.3 - Opening limitations. Open guards shall have balusters or ornamental patterns such that a 4-inch-diameter (102 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm). From a height of 34 inches (864 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, a sphere 8 inches (203 mm) in diameter shall not pass.
Correction

Codes Administration - 2003 IBC 1014.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds the value in Table 1014.1. 2. The common path of egress travel exceeds the limitations of Section 1013.3. 3. Where required by Sections 1014.3, 1014.4 and 1014.5.
Correction

Codes Administration - 2003 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - The Buiding Code Review on Sheet A2.3 indicates an occupancy type of S-2 which does not allow for the storage of any combustibles and only one layer of combustible packaging. If this warehouse is to be an S-2 occupancy than no paper goods or files can be stored in the warehouse and no boxed and cased products would be allowed in the building. I am not sure what the archives are on the second floor but this space is open to the warehouse. The occupancy type of the warehouse could be catagorized as an S-1 which does allow for the storage of these item. The base allowable area is 9,000 square feet and one store. As the building is actually sprinkled per NFPA 13 and is open on all sides by 60 feet, section 507.3 allows the building to be of unlimited area.
Correction

Codes Administration - The Building Code Review does not indicate that this building is sprinkled.
Correction

Fire Department-Unable to locate information on the type and height of the racks being used, or type of products being stored. The conditions of IFC, Chapter 23 "High-Piled Combustible Storage" .
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IMC 507.2.3 - Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes in accordance with Sections 507.2, 507.2.1 and 507.2.2.
Correction

Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and an smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

Codes Administration - 2003 IMC 606.2.2 - Common supply and return air systems. Where multiple air-handling systems share common supply or return air ducts or plenums with a combined design capacilty greater than 2,000 cfm, the return air system shall be provided with smoke detectors in accordance with Section 606.2.1.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $6,704.18 $6,704.18 Paid 01/24/2007
89 Sewer Tap Fees $60.00 $60.00 Paid 01/24/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 02/02/2007
Correction
Partial Correction
02/02/2007
WALL FRAMING + IN-WALL SYSTEMS 203; 205 E WALL; 206-208; 210-211; 215; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 02/07/2007
Correction
Partial Correction
02/07/2007
WALL FRAMING + IN-WALL SYSTEMS 103; 212; 203; 205 E WALL; 206-208; 210-211; 215; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 02/09/2007
Correction
Partial Correction
02/09/2007
WALL FRAMING + IN-WALL SYSTEMS 103; 202; 203; 205 E WALL; 206-208; 210-212; 215; NOTE: 204 COVERED PRIOR TO APPROVAL OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rough Electrical Inspection - Commercial Passed 02/12/2007
Correction
Resolved
02/12/2007
None BSMT BATH 102. 1ST FL RM 201, 216 - WALL ROUGH APPROVED
All Rough Inspection - Commercial Partial 02/20/2007
Correction
Partial Correction
02/20/2007
WALL FRAMING + IN-WALL SYSTEMS 103; 202 INCLUDING S WALL; 203; 205 COMPLETE; 206-208; 210-212; 213; 215; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Failed 02/21/2007
Correction
Partial Correction
02/21/2007
WALL FRAMING + IN-WALL SYSTEMS 103; 202 INCLUDING S WALL; 203; 205 COMPLETE; 206-208; 210-212; 213; 215; RR 102 NOT APPROVED -- PVC PIPE NOT SHIELD-PLATED OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Passed 02/22/2007
Correction
Resolved
02/22/2007
WALL FRAMING + IN-WALL SYSTEMS 103; 202 INCLUDING S WALL; 203; 205 COMPLETE; 206-208; 210-212; 213; 215; RR 102 NOT APPROVED -- PVC PIPE NOT SHIELD-PLATED OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
02/22/2007
Water/DWV Preotection Against Physical Damage (IRC) ROOM # 102 BATHROOM, BASEMENT OK TO COVER
Underground Plumbing Inspection - Commercial Partial 03/16/2007
Correction
Partial Correction
03/16/2007
STORM DRAIN LINES 10" TO 8" & 6" INTO SW TRUCK WELL; 6" INTO N TRUCK WELL; FROM JUNCTION BOX TO TRUCK WELLS
Underslab Electrical Inspection - Commercial Passed 03/19/2007
Correction
Resolved
03/19/2007
UNDER-FLOOR ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Underground Plumbing Inspection - Commercial Not Ready 03/20/2007
Correction
Corrective Action Required
03/20/2007
STORM DRAIN LINES 10" TO 8" & 6" INTO SW TRUCK WELL; 6" INTO N TRUCK WELL; REMAINDER OF STRORM PIPING AT N TRUCK WELL NOT READY FOR INSPECTION -- ALREADY COVERED FROM JUNCTION BOX TO TRUCK WELLS
Underground Plumbing Inspection - Commercial Partial 03/21/2007
Correction
Partial Correction
03/21/2007
STORM DRAIN LINES FROM JUNCTION BOX TO TRUCK WELLS; 10" TO 8" & 6" INTO SW TRUCK WELL; 6" INTO N TRUCK WELL FOR BUILDING ROOF DRAIN; 8" INTO N TRUCK WELL FOR TRENCH DRAIN OK TO COVER WHEN READY PORTIONS DESCRIBED BELOW:
Underground Plumbing Inspection - Commercial Passed 03/28/2007
Correction
Resolved
03/28/2007
STORM DRAIN LINES FROM JUNCTION BOX TO TRUCK WELLS; 10" TO 8" & 6" INTO SW TRUCK WELL; 6" INTO N TRUCK WELL FOR BUILDING ROOF DRAIN; 8" INTO N TRUCK WELL FOR TRENCH DRAIN; COMPLETION OF PIPING AT SW TRUCK WELL OK TO COVER WHEN READY PORTIONS DESCRIBED BELOW:
Above Ceiling Inspection Partial 04/06/2007
Correction
Partial Correction
04/06/2007
None ROOM 103 ABOVE CEILING APPROVED
Occupancy Inspection - Codes Commercial Failed 04/09/2007
Correction
Corrective Action Required
04/09/2007
USE/OCCUPANCY APPROVAL STATUS 1) CLEAR EGRESS PASSAGE WAY. 2) INSTALL EXIT SIGN NOW; EMERGENCY LIGHTS ASAP ROOM 103 ONLY RESOLVE FIRE DEPT ISSUES:
Occupancy Inspection - Codes Commercial Not Ready 04/10/2007
Correction
Partial Correction
04/10/2007
USE/OCCUPANCY APPROVAL STATUS ROOM 103 ONLY OK FOR USE
Underground Electrical Inspection - Commercial Partial 04/10/2007
Correction
Resolved
04/10/2007
PREP TO POUR LIGHT POLE BASES OK TO POUR WHNE READY 5 AT 24" DIAM VERIFY DEPTH W/ ENGINEER
Correction
Corrective Action Required
04/10/2007
UNDERGROUND CONDUIT FOR LIGHT POLE FEEDERS NOT READY FOR INSPECTION
Correction
Corrective Action Required
04/10/2007
GROUNDING ELECTRODE CONNECTIONS TO GROUND RODS @ L.P.'S NOT READY FOR INSPECTION
Underground Electrical Inspection - Commercial Request Complete 4/9/2007 4/10/2007 04/10/2007
Underground Electrical Inspection - Commercial Partial 04/12/2007
Correction
Resolved
04/12/2007
PREP TO POUR LIGHT POLE BASES 5 AT 24" DIAM VERIFY DEPTH W/ ENGINEER
Correction
Resolved
04/12/2007
SECONDARY SERVICE CONDUIT OK TO COVER WHEN READY FROM TRANSFORMER LOCATION TO SWEEP AT BUILDING
Underground Electrical Inspection - Commercial Request Complete 4/12/2007 4/12/2007 04/12/2007
Above Ceiling Inspection Failed 04/13/2007
Correction
Resolved
04/13/2007
None
Correction
Partial Correction
04/13/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 103; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Corrective Action Required
04/13/2007
RETURN-AIR ABOVE-CEILING PLENUM SPACE 1) PROVIDE CERTIFICATION ALL L.V. CABLE IS PLENUM RATED 2) REMOVE ALL COMBUSTIBLE MATERIALS 3) PVC PIPING NOT ALLOWED IN R.A. PLENUM NO COMBUSTIBLES ALLOWED
Underground Electrical Inspection - Commercial Partial 04/20/2007
Correction
Resolved
04/20/2007
UNDERGROUND ELECTRICAL TO 5 LIGHT POLES CONDUITS MIN 24" BELOW PAVEMENT, ALL CONNECTIONS TO L.P. GROUNDING RODS ARE MADE. OK TO BACKFILL FROM BUILDING NORTH TO SW
Underground Electrical Inspection - Commercial Request Complete 4/20/2007 4/20/2007 04/20/2007
Erosion Control Inspection Residential Passed 05/16/2007
Gas Service Inspection - Commercial Passed 05/16/2007
Correction
Resolved
05/16/2007
None GAS APPROVED TEST PRESSURE 20 PSI - RELEASE GAS
Gas Piping Inspection - Commercial Passed 05/16/2007
Correction
Resolved
05/16/2007
None 4 UNIT HEATERS AND 4 FURNACES
Electrical Service Inspection Passed 05/22/2007
Correction
Resolved
05/22/2007
ELECTRICAL SERVICE INSTALLATION 1200 AMPS RELEASE SERVICE
Above Ceiling Inspection Partial 05/25/2007
Correction
Partial Correction
05/25/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS CONTINGENT ON CERTIFICATION OF PLENUM-RATED LOW-VOLTAGE CABLE, ALL OK TO COVER EXCEPT AREAS COVERED PRIOR TO INSPECTION AT STAIRWELL AND CORR 215 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
05/25/2007
RETURN-AIR ABOVE-CEILING PLENUM SPACE ARE PLENUM-RATED L.V. CABLE IN PLENUM SPAC PROVIDE CERTIFICATION ALL
Above Ceiling Inspection Partial 06/01/2007
Above Ceiling Inspection Partial 06/04/2007
Correction
Partial Correction
06/04/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS CONTINGENT ON CERTIFICATION OF PLENUM-RATED LOW-VOLTAGE CABLE, ALL UPPER LEVEL SPACES EXCEPT STAIRWELL CEILING, WHICH WAS COVERED PRIOR TO INSPECTION OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
06/04/2007
RETURN-AIR ABOVE-CEILING PLENUM SPACE ARE PLENUM-RATED L.V. CABLE IN PLENUM SPAC PROVIDE CERTIFICATION ALL
Occupancy Inspection - Codes Commercial Not Ready 06/07/2007
Correction
Corrective Action Required
06/07/2007
TOILET ROOM 102 SUBJECT TO APPROVAL AT FINAL INSPECTION
Correction
Corrective Action Required
06/07/2007
UNDERGROUND ELECTRICAL NO RECORD OF INSPECTION OF BASES, BURIED CONDUIT AND GROUNDING AT SITE LIGHT POLES. NOT FULLY APPROVED SEE INSPECTION ITEM
Correction
Corrective Action Required
06/07/2007
ABOVE CEILING INSPECTION COVERED PRIOR TO INSPECTION NOT COMPLETED ABOVE STAIRWELL
Correction
Corrective Action Required
06/07/2007
WINDOWWALL GLAZING AT SPACE 205 EAST AND SOUTH TEMPERED GLASS ETCHING NOT FOUND
Correction
Corrective Action Required
06/07/2007
ELECT RECEPTACLE AT COUNTERTOP @ SPACE 202 WITHIN 6' OF SINK 2ND LEFT OF SINK NOT GFCI PROTECTED
Correction
Corrective Action Required
06/07/2007
INSTALLATION OF DISHWASHERS AT 202 & 204 IRC P2717.2: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO PROVIDE HIGH POINT IN DISCHARGE LINE.) ROUTE DISCHARGE LINE FOR BACKFLOW PROTECTION
Correction
Corrective Action Required
06/07/2007
INSTALLATION OF RANGE AT 204 MUST PROVIDE ANTI-TIP HARDWARE WITH APPLIANCE
Correction
Corrective Action Required
06/07/2007
ELECT RECEPTACLE BELOW PANEL LP1 UNUSED OPENING NOT PLUGGED
Correction
Corrective Action Required
06/07/2007
LABELING OF CUIRCUITS IN PANEL LP1 UPDATE / CONSOLIDATE ENSURE ALL ACCURATE
Correction
Corrective Action Required
06/07/2007
LABELING OF SWITCHES AT MDP IDENTIFY ALL
Correction
Corrective Action Required
06/07/2007
DESIGNATION OF ELECT PANEL RIGHT OF MDP LABEL WITH IDENTIFIER
Occupancy Inspection - Codes Commercial Failed 06/26/2007
Correction
Partial Correction
06/26/2007
USE/OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
06/26/2007
TOILET ROOM 102
Correction
Resolved
06/26/2007
UNDERGROUND ELECTRICAL
Correction
Corrective Action Required
06/26/2007
WINDOWWALL GLAZING AT SPACE 205 EAST AND SOUTH FOUR BOTTOM UNITS TEMPERED GLASS ETCHING NOT FOUND
Correction
Corrective Action Required
06/26/2007
ELECT RECEPTACLE AT COUNTERTOP @ SPACE 202 WITHIN 6' OF SINK. IF DEDICATED, USE SINGLE RECEPT. 2ND LEFT OF SINK NOT GFCI PROTECTED
Correction
Corrective Action Required
06/26/2007
INSTALLATION OF DISHWASHERS AT 202 & 204 IRC P2717.2: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO PROVIDE HIGH POINT IN DISCHARGE LINE.) ROUTE DISCHARGE LINE FOR BACKFLOW PROTECTION
Correction
Corrective Action Required
06/26/2007
INSTALLATION OF RANGE AT 204 MUST PROVIDE ANTI-TIP HARDWARE WITH APPLIANCE
Correction
Corrective Action Required
06/26/2007
ELECT RECEPTACLE BELOW PANEL LP1 UNUSED OPENING NOT PLUGGED
Correction
Corrective Action Required
06/26/2007
LABELING OF CUIRCUITS IN PANEL LP1 UPDATE / CONSOLIDATE ENSURE ALL ACCURATE
Correction
Corrective Action Required
06/26/2007
LABELING OF SWITCHES AT MDP IDENTIFY ALL
Correction
Corrective Action Required
06/26/2007
DESIGNATION OF ELECT PANEL RIGHT OF MDP LABEL WITH IDENTIFIER
Correction
Corrective Action Required
06/26/2007
SECURING OF COPPER PIPING AT WAREHOUSE ADDITION WEST WALL TIGHTEN CLAMP ATTACHMENT
Correction
Corrective Action Required
06/26/2007
Receive Fire Department approval
Correction
Corrective Action Required
06/26/2007
Receive Planning & Development Approval REQUEST INSPECTION WHEN LANDSCAPING COMPLETE
Correction
Corrective Action Required
06/26/2007
Receive Public Works Approval
Correction
Corrective Action Required
06/26/2007
Receive Water Utilities Approval
Correction
Corrective Action Required
06/26/2007
LOW VOLTAGE CABLE ABOVE CEILING PROVIDE CERTIFICATION ALL ARE PLENUM-RATED
Underground Electrical Inspection - Commercial Passed 06/26/2007
Correction
Resolved
06/26/2007
PREP TO POUR LIGHT POLE BASES
Correction
Resolved
06/26/2007
UNDERGROUND CONDUIT FOR LIGHT POLE FEEDERS
Correction
Resolved
06/26/2007
GROUNDING ELECTRODE CONNECTIONS TO GROUND RODS @ L.P.'S
Correction
Resolved
06/26/2007
SECONDARY SERVICE CONDUIT
Correction
Resolved
06/26/2007
UNDERGROUND ELECTRICAL TO 5 LIGHT POLES
Above Ceiling Inspection Passed 06/26/2007
Correction
Resolved
06/26/2007
None
Correction
Resolved
06/26/2007
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS SEE ISSUES DESCRIBED AT OCCUPANCY INSPECTION
Correction
Resolved
06/26/2007
RETURN-AIR ABOVE-CEILING PLENUM SPACE
Occupancy Inspection - Codes Commercial Failed 07/11/2007
Correction
Partial Correction
07/11/2007
USE/OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
07/11/2007
ABOVE CEILING INSPECTION PLACE NO CEILING TILE PRIOR TO ABOVE-CEILING INSPECTION. CAUTION TO G.C. ON FUTURE INSPECTIONS
Correction
Resolved
07/11/2007
ELECT RECEPTACLE AT COUNTERTOP @ SPACE 202
Correction
Corrective Action Required
07/11/2007
INSTALLATION OF DISHWASHERS AT 202 & 204 IRC P2717.2: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO PROVIDE HIGH POINT IN DISCHARGE LINE.) ROUTE DISCHARGE LINE FOR BACKFLOW PROTECTION
Correction
Corrective Action Required
07/11/2007
INSTALLATION OF RANGE AT 204 MUST PROVIDE ANTI-TIP HARDWARE WITH APPLIANCE
Correction
Resolved
07/11/2007
ELECT RECEPTACLE BELOW PANEL LP1
Correction
Resolved
07/11/2007
LABELING OF CUIRCUITS IN PANEL LP1
Correction
Resolved
07/11/2007
LABELING OF SWITCHES AT MDP
Correction
Resolved
07/11/2007
DESIGNATION OF ELECT PANEL RIGHT OF MDP
Correction
Resolved
07/11/2007
SECURING OF COPPER PIPING AT WAREHOUSE ADDITION
Correction
Resolved
07/11/2007
Receive Fire Department approval PER JOE DIR 7/11/07
Correction
Resolved
07/11/2007
Receive Public Works Approval NO ISSUES PRESENTED
Correction
Resolved
07/11/2007
Receive Water Utilities Approval NO ISSUES PRESENTED
Occupancy Inspection - Codes Commercial Failed 07/25/2007
Correction
Resolved
07/25/2007
WINDOWWALL GLAZING AT SPACE 205 EAST AND SOUTH
Occupancy Inspection - Codes Commercial Failed 07/30/2007
Occupancy Inspection - Codes Commercial Passed 10/04/2007
Correction
Resolved
10/04/2007
USE/OCCUPANCY APPROVAL STATUS
Correction
Resolved
10/04/2007
INSTALLATION OF DISHWASHERS AT 202 & 204
Correction
Resolved
10/04/2007
INSTALLATION OF RANGE AT 204
Correction
Resolved
10/04/2007
Receive Planning & Development Approval PER TOM SCANNELL 10/4/07
Correction
Resolved
10/04/2007
LOW VOLTAGE CABLE ABOVE CEILING CERTIFICATION RECEIVED R-7 LETTER DATED 6/1/07
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home