Permit Application Status

B0603185


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0603185
Building Permit - Commercial
Certificate of Occupancy
THE RAVEN COMPANY OF LEES SUMMIT LLP
CHANGE OF TENANT
TENANT FINISH
10/30/2006
10/30/2006
04/28/2007
01/25/2007
Locations
Contacts
PURE, Address:803 NE LAKWOOD BLVD  
THE RAVEN COMPANY OF LEES SUMMIT LLP, Address:4210 NW LAKE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/28/2007 10/29/2010
Correction

Codes Administration - This permit was issued over the counter and a complete plan review was not performed on this project.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $30.00 $30.00 Paid 10/30/2006
89 Sewer Tap Fees $30.00 $30.00 Paid 10/30/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 11/08/2006
Correction
Corrective Action Required
11/08/2006
ENGINEERED PLANS APPROVED PLANS MUST BE ON SITE FOR ALL INSPECTIONS
Correction
Partial Correction
11/08/2006
TEXT APPROVED TO INSULATE & ROCK AT YOUR OWN RISK CONTINGENT UPON PROPERLY SUPPORTING ABOVE CEILING CONDUITS
All Rough Inspection - Commercial Passed 11/14/2006
Correction
Resolved
11/14/2006
ENGINEERED PLANS MOVED TO FINAL
Correction
Resolved
11/14/2006
TEXT
Occupancy Inspection - Codes Commercial Failed 11/14/2006
Correction
Corrective Action Required
11/14/2006
LIGHT SWITCHES MUST BE GROUNDED THROUGHOUT
Correction
Corrective Action Required
11/14/2006
GFCI PROTECTION RECEPTACLE MUST BE GFCI PROTECTED Restroom
Correction
Corrective Action Required
11/14/2006
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Partial Correction
11/14/2006
Receive Fire Department approval APPROVED FOR TCO BY CAPTAIN DIRR UNDER SEPARATE COVER
Correction
Corrective Action Required
11/14/2006
LABELLING OF DEVICES 1- PROVIDE PERMANENT LABELING OF ELECTRIC AND GAS METERS. 2- LABEL AND NUMBER ALL PANEL CIRCUITS (IN INK) EXTERIOR & STORAGE
Correction
Corrective Action Required
11/14/2006
ACCESSIBILITY RESTROOM MUST BE ACCESSIBLE. 1- SINK PIPING TO BE INSULATED 2- SINK HANDLES MUST BE A.D.A. COMPLIANT 3- TOILET TO BE A.D.A. COMPLIANT (17-19" HIGH AT SEAT) 4- GRAB BARS (36" BEHIND TOILET & 42" AT SIDE) 5- PROVIDE A.D.A. COMPLIANT DOOR SIGNAGE Restroom
Correction
Resolved
11/14/2006
30 DAY TCO 30 DAY TCO
Occupancy Inspection - Codes Commercial Failed 12/05/2006
Correction
Resolved
12/05/2006
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 12/14/2006
Correction
Resolved
12/14/2006
LIGHT SWITCHES MUST BE GROUNDED
Correction
Resolved
12/14/2006
GFCI PROTECTION
Correction
Corrective Action Required
12/14/2006
LABELLING OF DEVICES 1- PROVIDE PERMANENT LABELING OF ELECTRIC AND GAS METERS. "SHARPIE" OR MAGIC MARKER NOT ACCEPTABLE. EXTERIOR & STORAGE
Correction
Corrective Action Required
12/14/2006
ACCESSIBILITY RESTROOM MUST BE ACCESSIBLE. 1- SINK PIPING TO BE INSULATED (ALL PIPING) 3- TOILET TO BE A.D.A. COMPLIANT (17-19" HIGH AT SEAT) (MUST BE HINGED, & OPEN FRONT) 5- PROVIDE A.D.A. COMPLIANT DOOR SIGNAGE (LABELED AS RESTROOM) Restroom
Correction
Corrective Action Required
12/14/2006
PANEL CLEARANCE NO STORAGE ALLOWED IN FRONT OF PANEL. ALLOW 30"WIDE x 36" DEEP IN FRONT OF PANEL AT ALL TIMES REAR STORAGE ROOM
Occupancy Inspection - Codes Commercial Failed 12/27/2006
Correction
Resolved
12/27/2006
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Failed 01/16/2007
Correction
Corrective Action Required
01/16/2007
LABELLING OF DEVICES 1- PROVIDE PERMANENT LABELING OF ELECTRIC METER. "SHARPIE" OR MAGIC MARKER NOT ACCEPTABLE. EXTERIOR & STORAGE
Correction
Resolved
01/16/2007
ACCESSIBILITY
Correction
Resolved
01/16/2007
PANEL CLEARANCE NO STORAGE ALLOWED IN FRONT OF PANEL. ALLOW 30"WIDE x 36" DEEP IN FRONT OF PANEL AT ALL TIMES REAR STORAGE ROOM
Occupancy Inspection - Codes Commercial Passed 01/24/2007
Correction
Resolved
01/24/2007
LABELLING OF DEVICES
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home