Permit Application Status

B0602499


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0602499
Building Permit - Commercial
Certificate of Occupancy
RAINTREE VILLAGE SHOPPING CENTER LLC
NEW TENANT FINISH
LA FUENTE - TENANT FINISH
09/13/2006
11/03/2006
05/02/2007
01/31/2007
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
RAINTREE VILLAGE SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/02/2007 10/29/2010
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - 2003 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Permanent ladders installed to provide the required access shall comply with the followin minimum design criteria: 1. The side railings shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. 3. Ladders shall have a toe spacing not less tha 6 inches (152 mm) deep. 4. Ther shall be a minimum of 18 inches 9457 mm) between rails. 5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load. 6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms.
Correction

Codes Administration - 2003 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requies a Type I hood, A Type I hood shall be installed. Where a Type II hood is required, a Type I or Typed II hood shall be installed.
Correction

Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and an smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - 2003 IMC 304.10 - Guards. Guards shall be provided where appliances, equipment, fans or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment, for or component and the to of the guard shall be located not less than 42 inches above the elevated surface adjacent to the quard. The guard shall be constructed so as to prevent the passage ofa 21-inch-diameter sphere and shall comply with the loading requirements for quards specified in the International Building Code.
Correction

Codes Administration - 2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm). Exception: Clearance shall not be required from gypsum wallboard attaced to noncombustible structures provided that a smooth, cleanable, nonabsorbant and noncumbustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inces (457 mm) in all directions from the hood.
Correction

Codes Administration - Structural information has not been provided regarding the installation of the new mechanical systems on the roof.
Correction

Codes Administration - The occupant load provided in the Project Synopsis is incorrect. The calculation for the kitchen area is correct at 8. The occupant load for the seating area is 144 when you divide 2,150 by 15. This results in a total occupant load of 152.
Correction

Codes Administration - The Project Synopsis indicates a construction type of IIB but the construction type on the shell building was VB.
Correction

Code Administration - The Project Synopsis indicates an occupancy type of A-3. The actual occupancy type is A-2.
Correction

Fire Department- 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 608.14 - Location of backflow preventers. Access shall be provided to backflow preventers as specified by the installation instructions of the approved manufacturer.
Correction

Codes Administration - 2003 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Correction

Codes Adminsitration - 2003 IPC 802.1.6 - Domestic dishwashing machines. Domestic dishwashing machines shall dishcharge indirectly through an air gap or air break into a standpipe or waste receptor in accordance with Section 802.2, or discharge into a wye-branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste grinder. The waste line of a domestic dishwashing machine discharging into a kitchen sink tailpiece or food waste grinder shall connect to a deck-mounted air gap or the waste line shall rise and be securely fastenend to the underside of the sink rim or counter.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinance - Sec.17-309 - Smoking. A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place. B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
Correction

Lee's Summit Code of Ordinances, Section 17-6.D - Regulated smoking environments classified. No persons with ownership, management, or control of a food service establishment shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, eith primary lettering of not less than one inch in height according to one of the following classifications of food service establishments: 1. Smoke-free establishment (existing and new establishments) 2. Smoking establishment (existing establishments only) 3. Mixed smoking/non-smoking establishment (existing establishments only) 4. Smoking restricted establishment (existing and new establishments)
Correction

Codes Administration - 2003 IPC 409.2 - Water connection. The water supply to a dishwashing macine shall be protected against backlow by an air gap or backflow preventer in accordance with Section 608.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $756.11 $756.11 Paid 11/03/2006
89 Sewer Tap Fees $330.00 $330.00 Paid 11/03/2006
Middle Big Creek Watershed $368.28 $368.28 Paid 11/03/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 11/09/2006
Correction
Resolved
11/09/2006
None
Gas Piping Inspection - Commercial Failed 11/21/2006
Correction
Corrective Action Required
11/21/2006
Gas Piping--Drips (IRC) -1 INSTALL DRIP LEG AS PER PLANS. -2 LOW PSI ON TEST. -3 PROVIDE ACCESS TO ROOF
Gas Service Inspection - Commercial Failed 11/21/2006
Correction
Corrective Action Required
11/21/2006
Gas Test Pressure (IRC) NO PSI
Rough Framing Inspection - Commercial Failed 11/21/2006
Correction
Corrective Action Required
11/21/2006
WALL LAYOUT REVISE PLANS AT FRONT EGRESS. REMOVED DOOR AT LEFT OF ENTRANCE,(SOLID WALL, NO DOOR). WALL ROUGH APPROVED PENDING REVISED PLANS
Rough Plumbing Inspection - Commercial Failed 11/21/2006
Correction
Corrective Action Required
11/21/2006
None REVISE PLANS TO AS BUILT OR INSTALL VENTING AS PER APPROVED PLANS. PLANS SHOWS (2) ROOF VENT LOCATIONS.
Electrical Service Inspection Passed 11/21/2006
Correction
Resolved
11/21/2006
None 1- 400 AMP METER 2-200 AMP PANELS.--APPROVED TO RELEASE
Rough Electrical Inspection - Commercial Passed 11/21/2006
Correction
Resolved
11/21/2006
None
Gas Piping Inspection - Commercial Passed 12/05/2006
Correction
Resolved
12/05/2006
Gas Piping--Drips (IRC)
Gas Service Inspection - Commercial Passed 12/05/2006
Correction
Resolved
12/05/2006
Gas Test Pressure (IRC)
Above Ceiling Inspection Failed 12/18/2006
Correction
Partial Correction
12/18/2006
PARTIAL DO NOT COVER KITCHEN AREA, KITCHEN NOT COMPLETE. BATHROOMS AND EATING AREA - APPROVED TO IN STALL CEILING TILE.
Hood/Duct Inspection Passed 01/05/2007
Correction
Resolved
01/05/2007
None
Above Ceiling Inspection Passed 01/10/2007
Correction
Resolved
01/10/2007
PARTIAL
Final Inspection - Commercial Failed 01/24/2007
Correction
Corrective Action Required
01/24/2007
HEALTH DEPT APPROVAL REQUIRED FINAL BUILDING APPROVED PENDING APPROVAL FROM HEALTH DEPT.
Occupancy Inspection - Codes Commercial Passed 01/26/2007
Correction
Resolved
01/26/2007
None
Rough Plumbing Inspection - Commercial Passed 01/29/2007
Correction
Resolved
01/29/2007
None
Rough Framing Inspection - Commercial Passed 01/29/2007
Correction
Resolved
01/29/2007
WALL LAYOUT
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home