Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
05/02/2007
|
10/29/2010
|
|
|
|
Correction
CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
|
|
Correction
Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances.
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location.
3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
|
|
Correction
Codes Administration - 2003 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope).
Permanent ladders installed to provide the required access shall comply with the followin minimum design criteria:
1. The side railings shall extend above the parapet or roof edge not less than 30 inches.
2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center.
3. Ladders shall have a toe spacing not less tha 6 inches (152 mm) deep.
4. Ther shall be a minimum of 18 inches 9457 mm) between rails.
5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load.
6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot.
7. Ladders shall be protected against corrosion by approved means.
Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms.
|
|
Correction
Codes Administration - 2003 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requies a Type I hood, A Type I hood shall be installed. Where a Type II hood is required, a Type I or Typed II hood shall be installed.
|
|
Correction
Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and an smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
|
|
Correction
CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
|
|
Correction
Codes Administration - 2003 IMC 304.10 - Guards. Guards shall be provided where appliances, equipment, fans or other components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall extend not less than 30 inches beyond each end of such appliance, equipment, for or component and the to of the guard shall be located not less than 42 inches above the elevated surface adjacent to the quard. The guard shall be constructed so as to prevent the passage ofa 21-inch-diameter sphere and shall comply with the loading requirements for quards specified in the International Building Code.
|
|
Correction
Codes Administration - 2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exception: Clearance shall not be required from gypsum wallboard attaced to noncombustible structures provided that a smooth, cleanable, nonabsorbant and noncumbustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inces (457 mm) in all directions from the hood.
|
|
Correction
Codes Administration - Structural information has not been provided regarding the installation of the new mechanical systems on the roof.
|
|
Correction
Codes Administration - The occupant load provided in the Project Synopsis is incorrect. The calculation for the kitchen area is correct at 8. The occupant load for the seating area is 144 when you divide 2,150 by 15. This results in a total occupant load of 152.
|
|
Correction
Codes Administration - The Project Synopsis indicates a construction type of IIB but the construction type on the shell building was VB.
|
|
Correction
Code Administration - The Project Synopsis indicates an occupancy type of A-3. The actual occupancy type is A-2.
|
|
Correction
Fire Department- 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
|
|
Correction
Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance
testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
|
|
Correction
Fire Department; Construction documents for fire alarm systems shall be submitted for review
and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following:
1. A floor plan.
2. Locations of alarm-initiating and notification appli-
ances.
3. Alarm control and trouble signaling equipment.
4. Annunciation.
5. Power connection.
6. Battery calculations.
7. Conductor type and sizes.
8. Voltage drop calculations.
9. Manufacturers, model numbers and listing informa-
tion for equipment, devices and materials.
10. Details of ceiling height and construction.
11. The interface of fire safety control functions.
|
|
Correction
Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
|
|
Correction
CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
|
|
Correction
CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
|
|
Correction
CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
|
|
Correction
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
|
|
Correction
Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
|
|
Correction
Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
|
|
Correction
Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
|
|
Correction
CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
|
|
Correction
CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
|
|
Correction
CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
|
|
Correction
CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
|
|
Correction
Codes Administration - 2003 IPC 608.14 - Location of backflow preventers. Access shall be provided to backflow preventers as specified by the installation instructions of the approved manufacturer.
|
|
Correction
Codes Administration - 2003 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
|
|
Correction
Codes Adminsitration - 2003 IPC 802.1.6 - Domestic dishwashing machines. Domestic dishwashing machines shall dishcharge indirectly through an air gap or air break into a standpipe or waste receptor in accordance with Section 802.2, or discharge into a wye-branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste grinder. The waste line of a domestic dishwashing machine discharging into a kitchen sink tailpiece or food waste grinder shall connect to a deck-mounted air gap or the waste line shall rise and be securely fastenend to the underside of the sink rim or counter.
|
|
Correction
P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
|
|
Correction
P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
|
|
Correction
Lee's Summit Code of Ordinance - Sec.17-309 - Smoking.
A. "No Smoking" signs or the international "No Smoking" symbol (consisting of a pictorial representation of a burning cigarette enclosed in a red circle with a red bar across it) shall be clearly and conspicicuously posted at every public place and place of emplyment where smoking is prohibited by this Article, by the owner, operator, manager, or other person in control of that place.
B. Every public place and place of employment where smoking is prohibited by this Article shall have posted at every entrance a conspicuous sign clearly stating that smoking is prohibited.
|
|
Correction
Lee's Summit Code of Ordinances, Section 17-6.D - Regulated smoking environments classified. No persons with ownership, management, or control of a food service establishment shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, eith primary lettering of not less than one inch in height according to one of the following classifications of food service establishments:
1. Smoke-free establishment (existing and new establishments)
2. Smoking establishment (existing establishments only)
3. Mixed smoking/non-smoking establishment (existing establishments only)
4. Smoking restricted establishment (existing and new establishments)
|
|
Correction
Codes Administration - 2003 IPC 409.2 - Water connection. The water supply to a dishwashing macine shall be protected against backlow by an air gap or backflow preventer in accordance with Section 608.
|
|
|