Permit Application Status

B0601871


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0601871
Building Permit - Commercial
Certificate of Occupancy
DKML LLC
NEW COMMERCIAL
NEW WAREHOUSE
08/08/2006
10/13/2006
04/11/2007
10/09/2008
Locations
Contacts
CHAPMAN ARCHITECTS, Address:2412 W 71ST STREET  
STRUCTURE COMPONENTS INC, Address:PO BOX 9358  
MD ELECTRIC INC, Address:24625 JINGO RD  
AFC HEATING & COOLING INC, Address:824 NW MAIN ST  
PLUMBING BY FISHER INC, Address:9875 KILL CREEK RD  
DKML LLC, Address:1161 SE HAMBLEN RD  
DKML LLC, Address:1161 SE HAMBLEN RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/09/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 1704.1.1 - Building permit requirements. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

Codes Administration - 2003 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

Codes Administration - A backflow preventor will be required in this building as the service ties into the existing water service prior to the backflow.
Correction

Fire Department- The Knox Box on the existing building may be utilized instead of the one shown.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Fire Department- Indicate the method of storage within the building ie. high rack, high pile etc..
Correction

Codes Administration - Multiple buildings on one property can create confussion for emergency responce personnel. The Fire Department requests that the buildings be identified by some means, such as Building A and Building B.
Correction

Codes Administration - Copies of the engineered steel building package were not provided at the time of permit application.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,776.12 $1,776.12 Paid 10/13/2006
89 Sewer Tap Fees $120.00 $120.00 Paid 10/13/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 10/30/2006
Correction
Partial Correction
10/30/2006
None LINE A FROM FROM 1 TO 9 LINE 1 FROM A TO B LINE 9 FROM A TO B
Footing Inspection - Commercial Partial 10/31/2006
Correction
Partial Correction
10/31/2006
None LINE A APPROVED LINE 9 APPROVED
Underslab Plumbing Inspection - Commercial Passed 11/10/2006
Correction
Resolved
11/10/2006
None
Special Inspections Failed 03/06/2007
Correction
Corrective Action Required
03/06/2007
See Comment NOT RECEIVED
All Rough Inspection - Commercial Failed 03/06/2007
Correction
Partial Correction
03/06/2007
None OKAY TO INSULATE, OKAY O ROCK AT OWN RISK
Correction
Corrective Action Required
03/06/2007
Subpanel NOT ON PLANS. HAVE ARCHITECT SUBMIT CHANGE FOR SUBPANEL.
Correction
Corrective Action Required
03/06/2007
See Comment PLANS ARE TO USE CEILING OF OFFICE SPACES FOR STORAGE. BEARING WALLS & CEILING JOISTS ARE STRUCTUAL STEEL (16 GA) ON 16" CENTERS. STUD & JOISTS SPECIFICATIONS NOT ON PLANS - HAVE ARCHITECT SUBMIT LETTER
Correction
Corrective Action Required
03/06/2007
Water Heater NOT INSTALLED, LOCATION NOT KNOWN
Electrical Service Inspection Failed 03/12/2007
Correction
Corrective Action Required
03/12/2007
System Service Ground (IRC) #2 GROUND WIRE NOT RAN TO WATER LINE, PER APPROVED PLANS
Electrical Service Inspection Passed 03/16/2007
Correction
Resolved
03/16/2007
System Service Ground (IRC) #2 GROUND WIRE NOT RAN TO WATER LINE, PER APPROVED PLANS
Correction
Resolved
03/16/2007
None 400 AMP PANEL & 100 MP SUB PANEL
Gas Piping Inspection - Commercial Passed 03/16/2007
Correction
Resolved
03/16/2007
None
Gas Service Inspection - Commercial Passed 03/16/2007
Correction
Resolved
03/16/2007
None HELD 14 PSI. RELEASE METER
Special Inspections Passed 03/28/2007
Correction
Resolved
03/28/2007
See Comment see letter Lorac Design Group dated 23 Mrch 2007.
Above Ceiling Inspection Failed 03/28/2007
Correction
Corrective Action Required
03/28/2007
Electrical Equipment Mounting (IRC) SECURE 2 X 4 LIGHT FIXTURES
All Rough Inspection - Commercial Failed 03/28/2007
Water Service Inspection Failed 04/05/2007
Correction
Corrective Action Required
04/05/2007
See Comment NO RECORD OF INSPECTION
Above Ceiling Inspection Passed 04/05/2007
Correction
Resolved
04/05/2007
Electrical Equipment Mounting (IRC) SECURE 2 X 4 LIGHT FIXTURES
All Rough Inspection - Commercial Passed 04/05/2007
Correction
Resolved
04/05/2007
None OKAY TO INSULATE, OKAY TO ROCK AT OWN RISK
Correction
Resolved
04/05/2007
Subpanel NOT ON PLANS. HAVE ARCHITECT SUBMIT CHANGE FOR SUBPANEL.
Correction
Resolved
04/05/2007
See Comment PLANS ARE TO USE CEILING OF OFFICE SPACES FOR STORAGE. BEARING WALLS & CEILING JOISTS ARE STRUCTUAL STEEL (16 GA) ON 16" CENTERS. STUD & JOISTS SPECIFICATIONS NOT ON PLANS - HAVE ARCHITECT SUBMIT LETTER
Correction
Resolved
04/05/2007
Water Heater NOT INSTALLED, LOCATION NOT KNOWN
Occupancy Inspection - Codes Commercial Failed 04/05/2007
Correction
Corrective Action Required
04/05/2007
Ladder INSTALL LADDER TO STORAGE AREA ABOVE OFFICE SPACE
Correction
Corrective Action Required
04/05/2007
Guard Rail INSTALL GUARD RAIL AREA STORAGE/MECHANICAL AREA ABOVE OFFICE SPACE
Correction
Corrective Action Required
04/05/2007
Panel Circuit Idenification LABEL BREAKERS Service Panel
Correction
Corrective Action Required
04/05/2007
Breaker Size MAX BREAKER FOR AC UNIT I 20 AMP - INSTALLED 30 AMP
Correction
Corrective Action Required
04/05/2007
Egress INSTALL EGRESS PATHWAY FROM EXIT DOOR AT SW CORNER
Correction
Corrective Action Required
04/05/2007
License Tax MUST BE PAID PRIOR TO TEMPORARY OCCUPANCY
Correction
Corrective Action Required
04/05/2007
Receive Public Works Approval
Correction
Corrective Action Required
04/05/2007
Receive Water Utilities Approval
Correction
Corrective Action Required
04/05/2007
Receive Planning & Development Approval
Correction
Corrective Action Required
04/05/2007
Receive Fire Department approval
Footing Inspection - Commercial Passed 04/05/2007
Correction
Resolved
04/05/2007
None LINE A FROM FROM 1 TO 9 LINE 1 FROM A TO B LINE 9 FROM A TO B
Correction
Resolved
04/05/2007
None LINE A APPROVED LINE 9 APPROVED
Sewer Service Inspection Failed 04/05/2007
Correction
Corrective Action Required
04/05/2007
See Comment NO RECORD OF INSPECTION
Occupancy Inspection - Codes Commercial Failed 04/06/2007
Correction
Resolved
04/06/2007
License Tax MUST BE PAID PRIOR TO TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Failed 08/02/2007
Correction
Resolved
08/02/2007
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 08/06/2007
Correction
Resolved
08/06/2007
Receive Water Utilities Approval se e-mail from Ben Haskamp dated 6 Aug 07
Correction
Resolved
08/06/2007
Ladder INSTALL LADDER TO STORAGE AREA ABOVE OFFICE SPACE AREA NOT A STORAGE AREA
Correction
Resolved
08/06/2007
Guard Rail INSTALL GUARD RAIL AREA STORAGE/MECHANICAL AREA ABOVE OFFICE SPACE AREA NOT A STORAGE AREA
Correction
Resolved
08/06/2007
Panel Circuit Idenification LABEL BREAKERS Service Panel
Correction
Resolved
08/06/2007
Breaker Size MAX BREAKER FOR AC UNIT I 20 AMP - INSTALLED 30 AMP
Correction
Resolved
08/06/2007
Egress INSTALL EGRESS PATHWAY FROM EXIT DOOR AT SW CORNER
Occupancy Inspection - Codes Commercial Passed 10/07/2008
Correction
Resolved
10/07/2008
Receive Planning & Development Approval
Correction
Resolved
10/07/2008
Receive Public Works Approval
Water Service Inspection Passed 10/08/2008
Correction
Resolved
10/08/2008
See Comment
Sewer Service Inspection Passed 10/08/2008
Correction
Resolved
10/08/2008
See Comment
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit