Permit Application Status

B0601615


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0601615
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW HANGER
07/26/2006
09/25/2006
04/30/2008
07/07/2008
Locations
Contacts
HIRST AND ASSOCIATES PC, Address:621 NE WOODS CHAPEL RD  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
LAND AND WATER, Address:9003 E 92ND ST  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/25/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 412.2.1 - Exterior walls. Exterior walls locatd less than 30 feet from property lines, lot lines or a public way shall have a fire-resistance rating not less than 2 hours.
Correction

Codes Adminsitration - 2003 IBC 412.2.3 - Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump.
Correction

Codes Administration - 2003 IBC 412.2.4 - Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire-resistance-rated construction. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation. Exception 1. Unit heaters suspended at least 10 feet above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hanger and at least 8 feet above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.
Correction

Codes Administration - 2003 IBC 412.2.6 - Fire suppression. Aircraft hangars shall be provided with fire suppression as required in NFPA 409. Exception: Group II hangars as defined in NFPA 409 storing private aircraft without major maintenance or overhaul are exempt from foam suppression requirements.
Correction

Fire Department- It is understood that the hangar (Group- III, per NFPA 409) will be used for storage purposes only. Any use other than that, or use as a vehicle or aircraft maintenace facility will require additional fire protection.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $361.00 $361.00 Paid 09/25/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Not Ready 05/23/2007
Correction
Corrective Action Required
05/23/2007
INSTALLATION PER APPROVED DRAWINGS DRAWINGS AMENDED AND UNCLEAR. REVISE DRAWINGS TO MATCH NEW DETAILS. ALSO, MAINTAIN 3" CLEARANCE BETWEEN STEEL & DIRT. BOTTOM REBAR MUST BE CONTINUOUSLY TIED. PIER BASES ARE NOT PER DRAWINGS. PROVIDE GROUND WIRE.
Footing Inspection - Commercial Passed 06/13/2007
Correction
Resolved
06/13/2007
INSTALLATION PER APPROVED DRAWINGS APPROVED TO POUR CONTINGENT UPON MAINTAINING MIN. 3" CLEARANCE OF STEEL FROM SOIL DURING POUR
Electrical Service Inspection Not Ready 06/22/2007
Correction
Corrective Action Required
06/22/2007
System Service Ground (IRC) WATER SERVICE PIPING NOT LONG ENOUGH TO BE VALID GROUND. PROVIDE ADDITIONAL GROUND ROD AT SERVICE. (MIN. 6' AWAY FROM OTHER ROD)
Underslab Plumbing Inspection - Commercial Partial 06/22/2007
Correction
Partial Correction
06/22/2007
None OK TO COVER BATHROOM GROUP & EXTERIOR STUBS. NOTE: REVISE PLANS TO DEPICT OMITTED PLUMBING & MECHANICAL.
Miscellaneous Inspection Failed 10/10/2007
Correction
Corrective Action Required
10/10/2007
CONTRACTOR LICENSING NO SUBCONTRACTORS HAVE BEEN LISTED FOR THIS PROJECT. PROVIDE ALL PERTINENT INFORMATION TO CODES OFFICE FOR INCLUSION ON PERMIT. INSPECTIONS MAY NOT BE PERFORMED PRIOR TO VERIFICATION THAT SUBCONTRACTORS ARE LICENSED.
Electrical Service Inspection Failed 10/12/2007
Correction
Corrective Action Required
10/12/2007
System Service Ground (IRC) WATER SERVICE PIPING NOT LONG ENOUGH TO BE VALID GROUND. OK **GROUND TO BUILDING STEEL
Electrical Service Inspection Passed 10/18/2007
Correction
Resolved
10/18/2007
System Service Ground (IRC)
Correction
Resolved
10/18/2007
None 200 AMP PANEL IN HANGAR
Underslab Plumbing Inspection - Commercial Partial 11/01/2007
Correction
Partial Correction
11/01/2007
None OK TO COVER BATHROOM GROUP & EXTERIOR STUBS. NOTE: REVISE PLANS TO DEPICT OMITTED PLUMBING & MECHANICAL.
Miscellaneous Inspection Failed 11/01/2007
Correction
Corrective Action Required
11/01/2007
CONTRACTOR LICENSING NO SUBCONTRACTORS HAVE BEEN LISTED FOR THIS PROJECT. PROVIDE ALL PERTINENT INFORMATION TO CODES OFFICE FOR INCLUSION ON PERMIT. INSPECTIONS MAY NOT BE PERFORMED PRIOR TO VERIFICATION THAT SUBCONTRACTORS ARE LICENSED.
Occupancy Inspection - Codes Commercial Failed 11/01/2007
Correction
Corrective Action Required
11/01/2007
Panel Circuit Identification (IRC) LABEL BREAKERS WITH A PERMANENT MARKER. LABEL 20 AMP BREAKER - RIGH SIDE 3 rd FROM BOTTOM. SERVICE PANEL
Correction
Corrective Action Required
11/01/2007
EMERGENCY LIGHTS INSTALL EMERGENCY LIGHTS - BATTERY BACK - UP.
Correction
Corrective Action Required
11/01/2007
LICENSE TAX LICENSE TAX REQUIRED TO B E PAID PRIOR TO ANY OCCUPANCY. DO NOT OCCUPY.
Occupancy Inspection - Codes Commercial Failed 11/02/2007
Correction
Resolved
11/02/2007
Panel Circuit Identification (IRC)
Correction
Resolved
11/02/2007
EMERGENCY LIGHTS
Underslab Plumbing Inspection - Commercial Passed 07/02/2008
Correction
Resolved
07/02/2008
None
Miscellaneous Inspection Passed 07/02/2008
Correction
Resolved
07/02/2008
CONTRACTOR LICENSING
Occupancy Inspection - Codes Commercial Passed 07/02/2008
Correction
Resolved
07/02/2008
LICENSE TAX NOT REQUIRED
Documents & Images

No documents are currently available for viewing.

Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home