Permit Application Status

B0600986


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600986
Building Permit - Commercial
Certificate of Occupancy
CALIFORNIA TIGERS LLC
CHANGE OF TENANT
TENANT FINISH
06/22/2006
08/07/2006
02/03/2007
09/22/2006
Locations
Contacts
RON SPARKS INC, Address:PO BOX 2102  
CALIFORNIA TIGERS LLC, Address:4400 SHAWNEE MISSION PKWY STE 209  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/20/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - 2003 IBC 302.1 - General. Structures of portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. Structures with multiple uses shall be classified according to Section 302.3. Where a structure is proposes for a purpose which is not specifically provided for in this code, such structure shall be classified in the group which the occupancy most nearly resemblies, according to the fire safety and relative hazard involved.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign eadily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - The Building Code Summary on Sheet CS1 indicates that the building is not sprinkled but the MP sheets make reference to a fire sprinkler.
Correction

Codes Administration - The demolition plan does not reference the removal of existing hvac equipment but the mechanical, electrical and plumbing plans indicate that the systems are new.
Correction

Codes Administration - Display layout information was not provided.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $175.66 $175.66 Paid 08/07/2006
89 Sewer Tap Fees $120.00 $120.00 Paid 08/07/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 08/23/2006
Correction
Corrective Action Required
08/23/2006
See Comment PLANS CALL FOR A 4" MAIN SANITARY LINE. 3" LINE INSTALLED. PROVIDE LETTER FROM ENGINEER AUTHORIZING CHANGE OR REPLACE LINE & CALL FOR REINSPECTION. COVER AT OWN RISK
All Rough Inspection - Commercial Partial 08/30/2006
Correction
Partial Correction
08/30/2006
None 1. CONDUIT & J-BOXES INSTALLED IN ACCESSIBLE TRAYS ALONG EAST & SOUTH WALLS. J-BOXES, TO BE MOUNTED AT FRONT OF TRAYS, & WHIPS NOT INSTALLED. 2. POWER POLES AT CHECK OUT LOCATION NOT INSTALLED
All Rough Inspection - Commercial Failed 08/31/2006
Correction
Partial Correction
08/31/2006
None 1. CONDUIT & J-BOXES INSTALLED IN ACCESSIBLE TRAYS ALONG EAST & SOUTH WALLS. J-BOXES, TO BE MOUNTED AT FRONT OF TRAYS, & WHIPS NOT INSTALLED. 2. POWER POLES AT CHECK OUT LOCATION NOT INSTALLED Electrical
Correction
Corrective Action Required
08/31/2006
Fittings REPLACE FERNCO TYPE FITTINGS ON PVC TO PVC JOINTS WITH GLUED FITTINGS DWV
Correction
Corrective Action Required
08/31/2006
See Comment OKAY TO ROCK INTERIOR WALLS - EXCEPT AT LOCATIONS WHERE FERNCO TYPE FITTINGS HAVE BEEN INSTALLED ON PVC TO PVC JOINTS. Walls
Correction
Corrective Action Required
08/31/2006
See Comments WINDOW INFILL WALLS AT NORTH & NORTH SIDES - PLANS DO NOT PROSCRIBE SIZE OF METAL STUDS. 1 5/8" STUDS INSTALLED. PROVIDE LETTER FROM ENGINEER DESIGNATING SIZE OF STUDS TO BE USED. Walls
Rough Framing Inspection - Commercial Request Complete 8/30/2006 8/31/2006 08/31/2006
All Rough Inspection - Commercial Failed 09/01/2006
Correction
Resolved
09/01/2006
Fittings REPLACE FERNCO TYPE FITTINGS ON PVC TO PVC JOINTS WITH GLUED FITTINGS DWV
Correction
Resolved
09/01/2006
See Comment OKAY TO ROCK INTERIOR WALLS - EXCEPT AT LOCATIONS WHERE FERNCO TYPE FITTINGS HAVE BEEN INSTALLED ON PVC TO PVC JOINTS. INSTALL BOCCA PLATES AT PVC AT NORTH RESTROOM WALL Walls
All Rough Inspection - Commercial Failed 09/12/2006
Correction
Resolved
09/12/2006
See Comments WINDOW INFILL WALLS AT NORTH & NORTH SIDES - PLANS DO NOT PROSCRIBE SIZE OF METAL STUDS. 1 5/8" STUDS INSTALLED. PROVIDE LETTER FROM ENGINEER DESIGNATING SIZE OF STUDS TO BE USED. Walls
Correction
Partial Correction
09/12/2006
None 1. CONDUIT & J-BOXES INSTALLED IN ACCESSIBLE TRAYS ALONG EAST & SOUTH WALLS. J-BOXES, TO BE MOUNTED AT FRONT OF TRAYS, & WHIPS NOT INSTALLED. 2. POWER POLES AT CHECK OUT LOCATION NOT INSTALLED Electrical
Above Ceiling Inspection Failed 09/12/2006
Correction
Corrective Action Required
09/12/2006
See Comment REMOVE CEILING TILES FOR INSPECTION. WILL CHECK WATER HEATER ON ABOVE CEILING INSPECTION.
Above Ceiling Inspection Failed 09/13/2006
Correction
Corrective Action Required
09/13/2006
See Comment ABOVE OFFICE - HVAC DIFFUSSIER NOT CONNECTED. POWER POLES - ELECTRICAL CONNECTIONS NOT COMPLETED. OKAY TO INSTALL TILE EXCEPT IN AREAS LISTED ABOVE
Correction
Resolved
09/13/2006
See Comment REMOVE CEILING TILES FOR INSPECTION. WILL CHECK WATER HEATER ON ABOVE CEILING INSPECTION.
Underslab Plumbing Inspection - Commercial Failed 09/18/2006
Above Ceiling Inspection Passed 09/18/2006
Correction
Resolved
09/18/2006
See Comment ABOVE OFFICE - HVAC DIFFUSSIER NOT CONNECTED. POWER POLES - ELECTRICAL CONNECTIONS NOT COMPLETED. OKAY TO INSTALL TILE EXCEPT IN AREAS LISTED ABOVE
All Rough Inspection - Commercial Passed 09/18/2006
Correction
Resolved
09/18/2006
None 1. CONDUIT & J-BOXES INSTALLED IN ACCESSIBLE TRAYS ALONG EAST & SOUTH WALLS. J-BOXES, TO BE MOUNTED AT FRONT OF TRAYS, & WHIPS NOT INSTALLED. 2. POWER POLES AT CHECK OUT LOCATION NOT INSTALLED Electrical
Occupancy Inspection - Codes Commercial Failed 09/18/2006
Correction
Corrective Action Required
09/18/2006
See Comment DO NOT OCCUPY
Correction
Corrective Action Required
09/18/2006
Bathroom ventilation (IRC) Bathroom
Correction
Corrective Action Required
09/18/2006
Plumbing Lines WRAP Bathroom
Correction
Corrective Action Required
09/18/2006
Electrical Equipment Mounting (IRC) LOOSE J-BOX Office
Correction
Corrective Action Required
09/18/2006
Receive Fire Department approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
09/18/2006
Receive Water Utilities Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
09/18/2006
Receive Public Works Approval RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
09/18/2006
Receive Planning & Development Approval RECEIVE UNDER SEPARATE COVER
Gas Service Inspection - Commercial Passed 09/20/2006
Correction
Resolved
09/20/2006
None HELD 12 PSI. METER ALREADY SET.
Gas Piping Inspection - Commercial Passed 09/20/2006
Correction
Resolved
09/20/2006
None
Occupancy Inspection - Codes Commercial Failed 09/20/2006
Correction
Resolved
09/20/2006
Receive Planning & Development Approval NOT REQUIRED
Correction
Resolved
09/20/2006
Receive Fire Department approval RECEIVE UNDER SEPARATE COVER
Correction
Resolved
09/20/2006
Electrical Equipment Mounting (IRC)
Correction
Resolved
09/20/2006
Plumbing Lines
Correction
Resolved
09/20/2006
Bathroom ventilation (IRC)
Correction
Partial Correction
09/20/2006
See Comment OKAY TO STOCK. DO NOT OPEN FOR BUSINESS
Correction
Corrective Action Required
09/20/2006
Signage KEYED FRONT DOOR - READILY VISIBLE SIGN -"THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS"
Correction
Resolved
09/20/2006
Receive Public Works Approval NOT REQUIRED
Correction
Resolved
09/20/2006
Receive Water Utilities Approval
Underslab Plumbing Inspection - Commercial Passed 09/21/2006
Correction
Resolved
09/21/2006
See Comment PLANS CALL FOR A 4" MAIN SANITARY LINE. 3" LINE INSTALLED. PROVIDE LETTER FROM ENGINEER AUTHORIZING CHANGE OR REPLACE LINE & CALL FOR REINSPECTION. COVER AT OWN RISK
Occupancy Inspection - Codes Commercial Passed 09/21/2006
Correction
Resolved
09/21/2006
See Comment
Correction
Resolved
09/21/2006
Signage KEYED FRONT DOOR - READILY VISIBLE SIGN -"THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS"
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home