Permit Application Status

B0600852


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600852
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
NEW TENANT FINISH
STATE FARM INSURANCE TENANT FINISH
06/02/2006
07/05/2006
01/01/2007
01/31/2007
Locations
Contacts
MEYER COMPANIES INC, Address:200 NE MISSOURI DR STE 100  
TK ARCHITECTS, Address:106 W 11TH ST STE 1900  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/27/2006 10/29/2010
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Fire Department- Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Codes Administration - The plans indicate that a fireplace insert is to be installed in office 114 but information on the type of fireplace to be installed is not provided. The plans do not indicate any gas piping to the unit or exhaust/vent.
Correction

Codes Administration - The plans indicate that awnings are to be attached to the structure but details are not provided.
Correction

Codes Administration - I am unable to find structural load information on the mezzanine/second floor.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Codes Administration - 2003 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Codes Administration - ANSI A117.1-1998 804.7.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer space 54 inches maximum above the floor or ground. The clear floor or ground space shall be positioned for a parallel approach to the space dedicated to a refrigerator/freezer with the centerline of the clear floor or ground space offset 24 inches maximum from the centerline of the dedicated space.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $233.43 $233.43 Paid 07/05/2006
89 Sewer Tap Fees $210.00 $210.00 Paid 07/05/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 08/08/2006
Underslab Plumbing Inspection - Commercial Passed 08/08/2006
Underground Electrical Inspection - Commercial Request Complete 8/7/2006 8/8/2006 08/08/2006
Electrical Service Inspection Passed 08/16/2006
Correction
Resolved
08/16/2006
None 200 AMP SERVICE APPROVED - RELEASE
All Rough Inspection - Commercial Partial 08/25/2006
Correction
Partial Correction
08/25/2006
None WALL ELECT. APPROVED 1 ST. FLOOR ONLY. OK TO ROCK 1 ST. FLOOR WALLS ONLY.
Correction
Partial Correction
08/25/2006
None 1 ST. FLOOR ONLY.
Correction
Partial Correction
08/25/2006
None WALL FRAMING APPROVED 1 ST. FLOOR ONLY.
Gas Service Inspection - Commercial Passed 09/05/2006
Correction
Resolved
09/05/2006
None GAS APPROVED TEST PRESSURE 11 PSI. RELEASE GAS.
Gas Piping Inspection - Commercial Passed 09/05/2006
Correction
Resolved
09/05/2006
None GAS PIPE INSTALLATION APPROVED. TWO 1 INCH GAS PIPE FOR FUTURE APPROVED THROUGH SOUTH WALL AND CAPED OFF.
Gas Service Inspection - Commercial Passed 09/05/2006
Correction
Resolved
09/05/2006
None GAS APPROVED TEST PRESSURE 11 PSI. RELEASE GAS. TWO 1 INCH GAS PIPE RUN INTO FUTURE TENNANT SPACES. TEST PRESSURE 11 PSI. RETEST REQUIRED WHEN FUTURE PIPE IS COMPLETED.
All Rough Inspection - Commercial Partial 09/14/2006
Correction
Partial Correction
09/14/2006
None WALL ELECT. APPROVED OK TO ROCK MEZZ. MEZZANINE
Correction
Partial Correction
09/14/2006
None APPROVED -- WALLS ONLY MEZZANINE
Correction
Partial Correction
09/14/2006
None MEZZANINE APPROVED. OK ROCK MEZZANINE
Above Ceiling Inspection Passed 10/04/2006
All Rough Inspection - Commercial Passed 10/04/2006
Correction
Resolved
10/04/2006
None MEZZANINE
Correction
Resolved
10/04/2006
None MEZZANINE
Correction
Resolved
10/04/2006
None MEZZANINE
Occupancy Inspection - Codes Commercial Failed 10/11/2006
Correction
Corrective Action Required
10/11/2006
LABEL GAS METER
Correction
Corrective Action Required
10/11/2006
Handrails (IRC) INSTALL HANDRAIL TO MEZZANINE
Correction
Corrective Action Required
10/11/2006
Electrical Listing & Labeling (IRC) PERMANENT LABELS IN SERVICE PANEL
Correction
Corrective Action Required
10/11/2006
FIRE DEPT. CORRECTIONS DUCT DETERCTORS LABEL SPRiNKLER ROOM KEY FOR KNOX BOX.
Correction
Corrective Action Required
10/11/2006
SEE CORRECTIONS NOT TO BE OPEN TO THE PUBLIC. OK TO INSTALL EQUIPMENT AND SUPPLIES.
Occupancy Inspection - Codes Commercial Failed 10/12/2006
Correction
Resolved
10/12/2006
LABEL GAS METER
Correction
Resolved
10/12/2006
Handrails (IRC)
Correction
Resolved
10/12/2006
Electrical Listing & Labeling (IRC)
Correction
Corrective Action Required
10/12/2006
FIRE DEPT. CORRECTIONS DUCT DETECTOR WILL NOT SHUT DOWN THE UNIT
Correction
Resolved
10/12/2006
SEE CORRECTIONS
Occupancy Inspection - Codes Commercial Passed 01/30/2007
Correction
Resolved
01/30/2007
FIRE DEPT. CORRECTIONS
Correction
Resolved
01/30/2007
None CLOSE PERMIT C. O.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home