Summary
B0600653
Building Permit - Commercial
Certificate of Occupancy
VILLE 36 INVESTMENT COMPANY LLC
CHANGE OF TENANT
PORTRAIT INNOVATIONS TENANT FINISH
04/27/2006
05/10/2006
11/06/2006
07/12/2006
Locations
Contacts
CDC, INC, Address:2152 BUFFALO DR  
DMR ARCHITECTURE, Address:1600 EAST WOODLAWN RD STUDIO 360  
VILLE 36 INVESTMENT COMPANY LLC, Address:4740 ROANOKE PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/30/2006 10/29/2010
Correction

Fire Department- IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $204.25 $204.25 Paid 05/10/2006
89 Sewer Tap Fees $120.00 $120.00 Paid 05/10/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 05/17/2006
Correction
Resolved
05/17/2006
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY EXCAVATED; LAID; JOINED SUBSTANTIALLY PER DRAWING
All Rough Inspection - Commercial Passed 05/24/2006
Correction
Resolved
05/24/2006
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Above Ceiling Inspection Failed 06/14/2006
Correction
Corrective Action Required
06/14/2006
EXISTING BALLAST ENCLOSURES @ N & E WALLS SECURE MC CABLES PER NEC INADAQUATE SUPPORT SECURE TO STRUCTURE +
Correction
Corrective Action Required
06/14/2006
INSTALLATION/SUPPORT OF LOW VOLTAGE CABLE SUPPORT WELL ABOVE CEILING GRID; SUPPORT FROM STRUCTURE - NOT FROM OTHER M/E/P SYSTEMS. BROWN TEMP CONTROL LYING LOOSE ON CLG GRID
Correction
Corrective Action Required
06/14/2006
SECURING/SUPPORT OF MC ELECTRICAL CABLE EXCEPT WHERE NO STRUCTURE 4.5' MAX INTERVALS AND WITHIN 12" OF BOXES
Above Ceiling Inspection Passed 06/15/2006
Correction
Resolved
06/15/2006
EXISTING BALLAST ENCLOSURES @ N & E WALLS SECURE MC CABLES PER NEC INADAQUATE SUPPORT SECURE TO STRUCTURE +
Correction
Resolved
06/15/2006
INSTALLATION/SUPPORT OF LOW VOLTAGE CABLE SUPPORT WELL ABOVE CEILING GRID; SUPPORT FROM STRUCTURE - NOT FROM OTHER M/E/P SYSTEMS. BROWN TEMP CONTROL LYING LOOSE ON CLG GRID
Correction
Resolved
06/15/2006
SECURING/SUPPORT OF MC ELECTRICAL CABLE EXCEPT WHERE NO STRUCTURE 4.5' MAX INTERVALS AND WITHIN 12" OF BOXES
Occupancy Inspection - Codes Commercial Failed 06/16/2006
Correction
Corrective Action Required
06/16/2006
Bathroom GFCI Receptacles (IRC) GFCI OUTLET DOES NOT HAVE POWER WOMENS RESTROOM
Correction
Corrective Action Required
06/16/2006
DOOR KNOB INSTALLATION MISSING DUE TO PAINTERS ARE STILL WORKING WOMENS RESTROOM
Correction
Corrective Action Required
06/16/2006
RECEPTACLES DO NOT HAVE POWER RM 102 - OUTLETS ALONG AND UNDER COUNTER DO NOT HAVE POWER RM 111 & RM 112 - OUTLETS AT 6'-6" DO NOT HAVE POWER RM 109 - OUTLETS THAT ARE NOT DESIGNATED DO NOT HAVE POWER THROUGHOUT
Correction
Corrective Action Required
06/16/2006
Electrical Listing & Labeling (IRC) PANEL REQUIRES LABEL Strorage Area
Correction
Corrective Action Required
06/16/2006
DOOR CLOSING SPEED CLOSING DEVICE IS NOT HOOKED UP TO INSPECT AND SEE IF CLOSING SPEED IS CORRECT REAR OF BUILDING
Correction
Corrective Action Required
06/16/2006
Receive Planning & Development Approval SEE SEPERATE COVER
Correction
Corrective Action Required
06/16/2006
Receive Fire Department approval SEE SEPERATE COVER - APPEARS TO HAVE PASSED
Occupancy Inspection - Codes Commercial Failed 06/19/2006
Correction
Resolved
06/19/2006
Bathroom GFCI Receptacles (IRC) GFCI OUTLET DOES NOT HAVE POWER Bathroom Women's
Correction
Resolved
06/19/2006
DOOR KNOB INSTALLATION MISSING DUE TO PAINTERS ARE STILL WORKING Bathroom Women's
Correction
Resolved
06/19/2006
RECEPTACLES DO NOT HAVE POWER RM 102 - OUTLETS ALONG AND UNDER COUNTER DO NOT HAVE POWER RM 111 & RM 112 - OUTLETS AT 6'-6" DO NOT HAVE POWER RM 109 - OUTLETS THAT ARE NOT DESIGNATED DO NOT HAVE POWER Throughout
Correction
Resolved
06/19/2006
Electrical Listing & Labeling (IRC) PANEL REQUIRES LABEL Service Panel
Correction
Corrective Action Required
06/19/2006
DOOR CLOSING SPEED CLOSING DEVICE IS NOT ABLE TO CLOSE DOOR. Door Rear
Correction
Resolved
06/19/2006
Receive Planning & Development Approval no action required
Correction
Resolved
06/19/2006
Receive Fire Department approval SEE SEPERATE COVER
Occupancy Inspection - Codes Commercial Passed 07/11/2006
Correction
Resolved
07/11/2006
Bathroom GFCI Receptacles (IRC)
Correction
Resolved
07/11/2006
DOOR KNOB INSTALLATION
Correction
Resolved
07/11/2006
RECEPTACLES DO NOT HAVE POWER
Correction
Resolved
07/11/2006
Electrical Listing & Labeling (IRC)
Correction
Resolved
07/11/2006
DOOR CLOSING SPEED
Correction
Resolved
07/11/2006
Receive Planning & Development Approval
Correction
Resolved
07/11/2006
Receive Fire Department approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home