Summary
B0600620
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
NEW COMMERCIAL
NEW HOSPITAL AND MOB
04/25/2006
07/20/2006
01/16/2007
11/19/2010
Locations
Contacts
J E DUNN CONSTRUCTION, Address:929 HOLMES  
PERKINS AND WILL, Address:6200 N CENTRAL EXPRESSWAY  
KLEINFELDER, Address:7802 BARTON  
U S ENGINEERING COMPANY, Address:3433 ROANOKE RD  
U S ENGINEERING COMPANY, Address:3433 ROANOKE RD  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
U S ENGINEERING COMPANY, Address:3433 ROANOKE RD  
U S ENGINEERING COMPANY, Address:3433 ROANOKE RD  
MIDWEST DIVISION LSH LLC, Address:PO BOX 1504  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/16/2007 10/29/2010
Correction

Codes Administration - 2003 IBC 1019.1 - Enclosures required. Interior exit stairways and interior exit ramps shall be enclosed with fire barriers. Exit enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the shaft enclosure shall include any basements but not any mezzanines. An exit enclosure shall not be used for any purposes other than means of egress. Enclosures shall be constructed as fire barriers in accordance with Section 706.
Correction

Codes Administration - 2003 IBC 3006.4 - Machine rooms and machinery spaces. Elevator machine rooms and machinery spaces shall be enclosed with construction having a fire-resistance rating not less than the required rating of the hoistway enclosure served by the machinery. Openings shall be protected with assemblies having a fire-resistance rating not less than that required for the hoistway enclosure doors.
Correction

Codes Administration - 2003 IBC 302.1.1 - Incidental use areas. Spaces which are incidental to the main occupancy shall be separated or protected, or both, in accordance with Table 302.1.1 or the building shall be classified as a mixed occupancy and comply with Section 302.3. Areas that are incidental to the main occupancy shall be classified in accordance with the main occupancy of the portion of the building in which the incidental use area is located.
Correction

Codes Administration - 2003 IBC 407.3 - Corridor walls. Corridor walls shall be constructed as smoke partitions.
Correction

Codes Administration - 2003 IBC 705.6 - Vertical continuity. Fire walls shall extend from the foundation to a termination point at least 30 inches (762 mm) above both adjacent roofs.
Correction

Codes Administration - 2003 IBC 705.6.1 - Stepped buildings. Where a fire wall serves as an exterior wall for a building and separates buildings having different roof levels, such wall shall terminate at a point not less than 30 inches (762 mm) above the lower roof level, provided the exterior wall for a height of 15 feet (4572 mm) above the lower roof is not less than 1-hour fire-resistance-rated construction from both sides with opeinings protected by assemblies having a 3/4-hour fire protection rating.
Correction

Codes Administration - 2003 IBC 715.3 - Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any materials or assembly of component materials that conforms to the test requirements of Section 715.3.1, 715.3.2 or 715.3.3 and the fire protection rating indicated in Table 715.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.
Correction

Fire Department- Complete a Hazardous Materials Permit Application. Include all materials subject to Tier II reporting. Provide MSDS's , quantities, methods of storage, and container specifications.
Correction

Fire Department- Confirm if medical gas will be stored in the Med-Gas Room or if it is used for medical air and vaccum only.
Correction

Fire Department- Batteries for UPS systems shall comply with IFC Sections 608 and 609.
Correction

Fire Department- Provide specifications for the two 8,000-gallon fuel tanks and piping system.
Correction

Fire Department- The storage liquid oxygen storage shall comply with IFC chapters 30,32, and NFPA 50 and 99.
Correction

Fire Department-905.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section and as required by the Code Offical. Fire hose threads used in connection with standpipe systems shall comply with NFPA 1963 or as otherwise approved and shall be compatible with fire department hose threads. The location of fire department hose connections shall be approved.
Correction

Fire Department- A site plan depicting proposed fire apparatus access, location of fire lanes and parking areas and for fire hydrant locations shall be submitted to the fire department for review and approval prior to construction.
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

Codes Administration - Some of the walls of the incidental use areas are not shown as rated on Sheet A-201A. Two of the areas are Laundry Room 1-HK1146 and Dry Storage 1-DI1730. These spaces are not required to be rated per Table 302.1.1 as the building is fully sprinkled but are required to resist the passage of smoke.
Correction

Per Ordinance 6074 and 6074. The Cumberland Drive extension, south of Shenandoah Drive to Blue Parkway, shall be constructed with the first phas of development and shall be substantially complete prior to any certificate of occupancy.
Correction

Per Ordinance 6074 and 6074. The following road improvements shall be constructed with the first phase of development, and shall be substantially complete prior to any certificate of occupancy: a) Construct a raised median on Todd George Road at the Blue Parkway intersection tha will limit movements, at a minimum, to left-turns off of Todd George Road, and right-turns on and off of Blue Parkway. Traffic turning left from Blue Parkway or attempting to cross Todd George Road would not be permitted. The design of this improvement will nteed to be coordinated with the Missouri Department of Transportation. b) Construct a northbound right-turn lane on Todd George Road at Shenandoah. This turn lane should be aproximately 150 feet in length, plus taper. c) Construct a second westbound left-turn lane on Shenandoah at Todd George Road. This lane should be approximately 200 feet in length, plus taper, and can occur within the existing median noted on the plans as Common Area Tract B. d) With the modifications outlined above, additional signal modifications will be needed at the intersection of Todd George Road and Shenandoah. A permanent traffic signal, with interconnect to the traffic signals on Todd George Road at US 50 and 5th Terrace, will be required as per the City's Access Management Code. e) Left-turn lanes will be required on Blue Parkway at each of the proposed driveways and public street intersections. These eastbound left-turn lans should be approximately 200 feet in length, plus taper. f) Two southboudn lanes will be required at all drives and intersections intersecting SE Blue Parkway. The two lanes should provide a minimum of 150 feet in storage.
Correction

Per Ordinance 6074 and 6074. The Excess Flow Holding Basin (EFHB) shall be constructed by the owner and shall be dedicated to the City, and shall be designed as a grass lined earthen basin to meet the required sanitary sewer wet weather capacity conditions for the portion of the subwatershed where the proposed HCA development is located prior to the issuance of a Certificate of Occupancy.
Correction

Codes Administration - Section 1013.2.2 allows for suites of rooms, other than patient sleeping rooms, shall to be a maximum of 10,000 square feet. Suite 1D-2 exceeds this allowable area.
Correction

Codes Administration - Suite 2A-1 shows an allowable area of 14,000 square feet.
Correction

Codes Administration - ANSI A117.1-1998 503.1 - General. Accessible passenger loading zones shall comply with Section 503.
Correction

Codes Administration - This review does not include any of the electrical systems for the hospital. The review of this area must be performed by a third party approved by the Codes Administration Department.
Correction

Codes Administration - As I did not receive civil plans, I do not know the size of the water services.
Correction

Codes Administration - 2003 IBC 716.5 - Where required. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers shall be provided at the locations prescribed in this section. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and a smoke damper shall be required.
Correction

Codes Administration - 2003 IMC 504.1 - Clothes dryers shall be exhausted in acordance with the manufacturer's instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building.
Correction

Fire Department- Off-site Improvements- Hydrants shall be provided for adequate fire protection in accordance with LS Public Works Engineering and IFC Appendix C. Unable to locate hydrants on Cumberland.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinances, Section 17-6.D - Regulated smoking environments classified. No persons with ownership, management, or control of a food service establishment shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, eith primary lettering of not less than one inch in height according to one of the following classifications of food service establishments: 1. Smoke-free establishment (existing and new establishments) 2. Smoking establishment (existing establishments only) 3. Mixed smoking/non-smoking establishment (existing establishments only) 4. Smoking restricted establishment (existing and new establishments)
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $141,050.10 $141,050.10 Paid 07/20/2006
84 Water Meters $6,060.73 $6,060.73 Paid 07/20/2006
85 Water Taps $75,075.00 $75,075.00 Paid 07/20/2006
89 Sewer Tap Fees $3,000.00 $3,000.00 Paid 07/20/2006
84 Water Meters $1,410.25 $1,410.25 Paid 08/02/2007
85 Water Taps $20,505.00 $20,505.00 Paid 08/02/2007
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 05/26/2006
Correction
Partial Correction
05/26/2006
AREA A 8 INCH PVC S.S. LINE APPROVED FROM 1 LINE TO 7.2 LINE. 6 P.S.I. VERIFIED FOR 5 MIN. 15' SOUTH OF E LINE FROM 1 LINE TO 7.2 LINE
Underslab Plumbing Inspection - Commercial Partial 06/01/2006
Correction
Partial Correction
06/01/2006
AREA A 15 FEET SOUTH OF E LINE 8 INCH PVC S.S. LINE APPROVED FROM 1 LINE TO 15 LINE. @ 14-15 LINE TRANSITION TO 6" PVC APPROVED TO 4 INCH CLEAN OUT EAST OF 15 LINE AREA A-B FROM 1 LINE TO 15 LINE
Underslab Plumbing Inspection - Commercial Partial 06/07/2006
Correction
Partial Correction
06/07/2006
AREA C 8" SS LINE APPROVED FROM 1 LINE TO 8 LINE. FROM 1-8 13 FT. SOUTH OF J-LINE
Underslab Plumbing Inspection - Commercial Partial 06/08/2006
Correction
Partial Correction
06/08/2006
AREA C 8" SS LINE APPROVED FROM 1 LINE TO 17 LINE. FROM 1-8 13 FT. SOUTH OF J-LINE
Underslab Electrical Inspection - Commercial Partial 06/08/2006
Correction
Partial Correction
06/08/2006
AREA A SEVEN RUNS OF 2 INCH SCHEDULE 40 PVC AND 1 RUN OF 1/2 INCH PVC APPROVED. D-2 TO I-5
Underslab Plumbing Inspection - Commercial Partial 06/09/2006
Correction
Partial Correction
06/09/2006
AREA D 6 INCH SS LINE APPROVED FROM 8 INCH SS LINE BETWEEN J LINE AND J.2 RUNNING SOUTH TO NORTH FROM CLEANOUT OUTSIDE OF P LINE BETWEEN 12 AND 13 LINES. 13 FT. SOUTH J TO P LINES BETWEEN 12 AND 13 LINES
Underslab Electrical Inspection - Commercial Partial 06/14/2006
Correction
Partial Correction
06/14/2006
None UNDERSLAB ELECTRICAL RUNNING AT A DIAGNOL 6 - 8.5 LINE E - F.5 LINE
Underslab Electrical Inspection - Commercial Partial 06/15/2006
Correction
Partial Correction
06/15/2006
AREA B 8-3 1/2 ", 9-2", 3-2 1/2", 1-3", 5-1" PVC FROM BETWEEN F & G@7.2 TO BETWEEN G & H@ 9. BETWEEN F & G 7.2 TO 9
Underslab Plumbing Inspection - Commercial Partial 06/15/2006
Correction
Partial Correction
06/15/2006
AREA A 8 INCH PVC S.S. LINE APPROVED FROM 1 LINE TO 15 LINE. BRANCHES TO 8 INCH LINE: 3 LINE, 4 LINE, BRANCHES NORTH AND SOUTH OF 8 " BETWEEN 6-7.2 COLUMN LINES-4 GROUPS. 8" FROM E TO A LINE EAST OF 5 LINE. AREA A-B FROM 1 LINE TO 15 LINE
Underslab Electrical Inspection - Commercial Partial 06/19/2006
Correction
Partial Correction
06/19/2006
None 2 - 2" SERVING ELEVATOR #4 - LINE 1.4 (E TO K LINE) 1 - 2" SERVING ELEVATOR #3- OFF MAIN TRUNK LINE 2 - 2" SERVING ELECTRICAL RM #1-LY1040 - OFF MAIN TRUNK LINE MASS UNDERSLAB @ (8-10) LINE FROM (G-H LINE) INTERIOR
Underslab Plumbing Inspection - Commercial Partial 06/20/2006
Correction
Partial Correction
06/20/2006
STORM PIPE F-LINE AND 1-LINE--10" B-6 LINES--6" F-7.2 LINES TO 8-D--8" 10-E LINES--8" K-10 LINES--8" K-7 LINES-- 6" ALL APPROVED THROUGH SLAB AND TURN UNDER FOOTING.
Correction
Partial Correction
06/20/2006
AREA A WASTE GROUP AT 2 LINE BETWEEN E AND F LINES APPROVED GROUP AT 6 LINE BETWEEN E- G LINES APPROVED GROUP BETWEEN 9 AND 10 AND D AND F LINES APPROVED.
Underslab Electrical Inspection - Commercial Partial 06/20/2006
Correction
Partial Correction
06/20/2006
None 2 - 2" SERVING ELEVATOR #4 - LINE 1.4 (E TO K LINE) 1 - 2" SERVING ELEVATOR #3- OFF MAIN TRUNK LINE 2 - 2" SERVING ELECTRICAL RM #1-LY1040 - OFF MAIN TRUNK LINE MASS UNDERSLAB @ (8-10) LINE FROM (G-H LINE) 10-H LINES TO 11-I. 4-4", 2-2",3-1" 3-1" INTERIOR
Suspended Slab Inspection Partial 06/23/2006
Correction
Corrective Action Required
06/23/2006
INSTALLATION PER PLANS SUSPENDED SLAB = APPROVED AT THE FOLLOWING LOCATION - EAST TO WEST(1-6 LINE), NORTH TO SOUTH(D-3' SOUTH OF F LINE) - SEE GENERAL NOTES S-101(3.7.2) TYPE B 3RD FLOOR EAST SIDE
Underslab Plumbing Inspection - Commercial Partial 06/26/2006
Correction
Partial Correction
06/26/2006
AREA C S. WASTE APPROVED AT BOUNDRIES 1 LINE, D LINE, J LINE, 12 LINE. FROM 1-8 13 FT. SOUTH OF J-LINE
Correction
Partial Correction
06/26/2006
STORM PIPE F-LINE AND 1-LINE--10" B-6 LINES--6" F-7.2 LINES TO 8-D--8" 10-E LINES--8" K-10 LINES--8" K-7 LINES-- 6" 13d-13E 8" ALL APPROVED THROUGH SLAB AND TURN UNDER FOOTING.
Underslab Electrical Inspection - Commercial Partial 06/28/2006
Correction
Partial Correction
06/28/2006
None DEEPEST TURNED UP PIPING ESTABLISHED ON SOUTH WALL IN EMERGENCY ELECTRICAL ROOM EMERGENCY ELEC. ROOM D LINE & 4 LINE
Underslab Electrical Inspection - Commercial Partial 06/29/2006
Correction
Partial Correction
06/29/2006
None 4 - 4" TURN UPS IN RM # 1-ME1131A 6 - 4" TURN UPS IN RM # 1-ME1131 BOTH ROOMS HEAD JUST THROUGH THE SAME TRENCH APPROVED TO JUST NORTH OF 1-LINE D & 1 LINE NW CORNER
Underslab Electrical Inspection - Commercial Partial 06/30/2006
Correction
Partial Correction
06/30/2006
None RM 1-CP2001, 5 - 3-1/2" TURN UPS IN THE MIDDLE OF THE ROOM D LINE & 4 LINE NW CORNER OF BUILDING
Underslab Plumbing Inspection - Commercial Partial 07/07/2006
Correction
Partial Correction
07/07/2006
STORM PIPE F-LINE AND 1-LINE--10" B-6 LINES--6" F-7.2 LINES TO 8-D--8" 10-E LINES--8" K-10 LINES--8" K-7 LINES-- 6"; LINE AT 13-J 13d-13E 8" ALL APPROVED THROUGH SLAB AND TURN UNDER FOOTING.
Correction
Partial Correction
07/07/2006
AREA A WASTE GROUP AT 2 LINE BETWEEN E AND F LINES APPROVED GROUP AT 6 LINE BETWEEN E- G LINES APPROVED GROUP BETWEEN 9 AND 10 AND D AND F LINES APPROVED. GROUP BETWEEN 11 AND 14 AND D AND J LINES APPROVED.
Underslab Electrical Inspection - Commercial Partial 07/17/2006
Correction
Partial Correction
07/17/2006
None -RM 1-DX1520 - ALLTURN UPS IN ROOM ARE COMPLETE -RM ME1434 - DEEPEST SET OF TURNUP OF ELECTRICAL PIPING HAS INSTALLED INTERIOR
Underslab Plumbing Inspection - Commercial Partial 07/24/2006
Correction
Partial Correction
07/24/2006
AREA C 4 " BETWEEN K-J LINE EAST OF 10 LINE APPROVED
Correction
Partial Correction
07/24/2006
ER AREA UNDERSLAB APPROVED BETWEEN 16-17 BETWEN J-K
Underslab Electrical Inspection - Commercial Partial 07/24/2006
Correction
Partial Correction
07/24/2006
Area A STUB-UP APPROVED BETWEEN C-D LINES OUTSIDE 4 LINE C-D OUTSIDE 4 LINE
Correction
Partial Correction
07/24/2006
ELECTRIC ROOM AT K-9 AND J-9 UNDERSLAB BETWEEN J AND K LINE AT 9 APPROVED
Underslab Electrical Inspection - Commercial Partial 07/25/2006
Correction
Partial Correction
07/25/2006
ELECTRIC ROOM AT K-9 AND J-9 UNDERSLAB BETWEEN J AND K LINE AT 9 APPROVED 1 1" line from between 9-10 lines & h-j lines to electric room approved. 5 stub ups between 9-10 & H-I lines approved for subpanels.
Underslab Electrical Inspection - Commercial Partial 07/27/2006
Correction
Partial Correction
07/27/2006
ELECTRIC ROOM AT K-9 AND J-9 UNDERSLAB BETWEEN J AND K LINE AT 9 APPROVED 1 1" line from between 9-10 lines & h-j lines to electric room approved. 5 stub ups between 9-10 & H-I lines approved for subpanels. Floor Box @J-7 & Elevator feeders underslab, 3-2" @ J-12 approved.
Underslab Electrical Inspection - Commercial Partial 07/31/2006
Correction
Partial Correction
07/31/2006
Area A STUB-UP APPROVED BETWEEN C-D LINES OUTSIDE 4 LINE 6 4 INCH PVC UNDER 4 LINE FOOTING STUB UP ON BOTH SIDES APPROVED. C-D OUTSIDE 4 LINE
Correction
Partial Correction
07/31/2006
ELECTRIC ROOM AT K-9 AND J-9 UNDERSLAB BETWEEN J AND K LINE AT 9 APPROVED 1 1" line from between 9-10 lines & h-j lines to electric room approved. 5 stub ups between 9-10 & H-I lines approved for subpanels. Floor Box @J-7 & Elevator feeders underslab, 3-2" @ J-12 approved.
Correction
Corrective Action Required
07/31/2006
H-J & 9-12 FLOOR BOX AT J-7 APPORVED. ELEVATOR FEEDS @J-12 ROSOR APPROVED. 3 2" @ H-12 APPROVED
Underslab Electrical Inspection - Commercial Partial 08/02/2006
Correction
Partial Correction
08/02/2006
H-J & 9-12 FLOOR BOX AT J-7 APPORVED. ELEVATOR FEEDS @J-12 ROSOR APPROVED. 3 2" @ H-12 APPROVED f-9 to g-12--9- 2 inch pvc approved g-12 to g-13 4- 2 inch approved.
Correction
Partial Correction
08/02/2006
Main Electrical Room Seventy-Three total stub ups approved from D4-D5-C-4-C5
Underground Electrical Inspection - Commercial Partial 08/31/2006
Correction
Partial Correction
08/31/2006
Light Pole Bases Approved at the following
Underground Electrical Inspection - Commercial Partial 09/08/2006
Correction
Partial Correction
09/08/2006
Light Pole Bases North, South, West Parking lots. Approved at the following
Rated Assembly Inspection Failed 09/22/2006
Correction
Partial Correction
09/22/2006
1ST FL 2HR WALL AT 6 LINE 7'6" AND UP - D.3-H-- APPROVED 1ST LAYER
Rough Framing Inspection - Commercial Failed 09/22/2006
Correction
Partial Correction
09/22/2006
EXTERIOR WALLS WEST WALL LINE #1 D-K
Correction
Partial Correction
09/22/2006
EXTERIOR WALLS WEST ELE. LINE 4 A-D
Correction
Partial Correction
09/22/2006
EXTERIOR WALLS NORTH ELEV. D LINE 1-15
Correction
Partial Correction
09/22/2006
EXTERIOR WALLS LINES 13 & 15 FROM D - H SOUTH WALL LINE F 13-15 EAST LINE 6 A-D NORTH LINE A 4-6 EAST - SOUTH-NORTH
Correction
Partial Correction
09/22/2006
STAIR TOWER EXTERIOR WALLS APPROVED #2-#3
Correction
Resolved
09/22/2006
EXTERIOR WALLS 2ND FLOOR LOWER ROOF FROM LINE 6-15 AND FROM D-H.2 LINE 6-15 AND FROM D-H.2
Underground Electrical Inspection - Commercial Partial 09/25/2006
Correction
Partial Correction
09/25/2006
Light Pole Bases 11 AT SOUTH PARKING AREA, PLATE ELECTODE APPROVED. Approved at the following
Correction
Partial Correction
09/25/2006
Primary Conduit DUCT BANK FROM WEST OF COLUMN LINE H TO FAR SOUTH CURB LINE APPROVED. 2 SIX INCH CONDUIT WITH 3/0 COPPER. From MH w. of J To far south curb line
Underground Electrical Inspection - Commercial Partial 10/05/2006
Correction
Corrective Action Required
10/05/2006
Lightning Protection System 3/0 TIN COPPER INSTALLED AROUND PERIMETER OF BUILDING FROM 5 LINE AT NORTH SIDE OF BUILDING TO 17 LINE AT SOUTH SIDE OF BUILDLING. ALSO FROM 1 TO 5 LINE AT SOUTH SIDE. APPROVED STAMPED DRAWINGS REQUIRED BEFORE APPROVAL. 3/0 Copper Installed at:
Correction
Partial Correction
10/05/2006
CONDUIT FOR FEEDERS MAIN TRANSFORMER 7-4 INCH CONDUIT FOR FEEDERS FOR MAIN POWER TRANSFORMER APPROVED. WEST OF CENTRAL PLANT BETWEEN C AND D LINES
Underground Electrical Inspection - Commercial Partial 10/10/2006
Correction
Corrective Action Required
10/10/2006
Lightning Protection System 3/0 TIN COPPER INSTALLED AROUND PERIMETER OF BUILDING FROM 5 LINE AT NORTH SIDE OF BUILDING TO 17 LINE AT SOUTH SIDE OF BUILDLING. ALSO FROM 1 TO 5 LINE AT SOUTH SIDE. FROM 5 TO 11 COVERED ON 10/10/6 APPROVED STAMPED DRAWINGS REQUIRED BEFORE APPROVAL. 3/0 Copper Installed at:
Correction
Partial Correction
10/10/2006
CONDUIT FOR FEEDERS MAIN TRANSFORMER 7-4 INCH CONDUIT FOR FEEDERS FOR MAIN POWER TRANSFORMER APPROVED FROM D TO A LINE. COVERED IN CONCRETE. WEST OF CENTRAL PLANT
Underground Electrical Inspection - Commercial Partial 10/12/2006
Correction
Corrective Action Required
10/12/2006
LIGHTNING PROTECTION Splices in wire are connected with a compessing fitting and placed upon a sheet of copper (plate). Wire has been run from column (10-11) and from (K-N) lines. 3/0 copper installed at:
Underslab Electrical Inspection - Commercial Partial 10/17/2006
Correction
Corrective Action Required
10/17/2006
HELIPAD CONDUIT FOR UNDERSLAB ELECTRICAL COVERED W/ GRAVEL AT TIME OF INSPECTION. REQUEST FOR AFTERNOON. INSPECTION PERFORMED AT 2:15 PM. EAST SIDE OF SITE
Rated Assembly Inspection Partial 10/17/2006
Correction
Partial Correction
10/17/2006
1ST FL 2HR WALL AT 6 LINE 7'6" AND UP - D.3-H-- APPROVED 1ST LAYER & 2ND LAYER
Rated Assembly Inspection Partial 11/16/2006
Correction
Partial Correction
11/16/2006
1ST FL 2HR WALL AT 6 LINE 7'6" AND UP - D.3-H-- APPROVED 1ST FLOOR 6 LINE D TO J- 1ST FLOOR 1ST LAYER --- APPROVED 1ST LAYER & 2ND LAYER
Rough Framing Inspection - Commercial Failed 11/16/2006
Correction
Partial Correction
11/16/2006
EXTERIOR WALLS S.W. CORNER "1" LINE TO 15. WEST --FROM K THROUGH P. APPROVED SOUTH ELEVATION
Gas Piping Inspection - Commercial Failed 11/17/2006
Correction
Corrective Action Required
11/17/2006
Protective Coatings & Wrapping (IFGC 404.8.2) Verification of the wrapping used to protect metallic fuel gas piping installed underground is to be verified. Manufacturer's installation instructions shall be provided on any protection used for metallic piping installed underground. North of Central Plant
Gas Service Inspection - Commercial Not Ready 11/17/2006
Correction
Corrective Action Required
11/17/2006
Gas Test Pressure (IFGC) NOT READY FOR INSPECTION. NO GUAGE ON GAS PIPING. Central Plant
Rated Assembly Inspection Partial 11/20/2006
Correction
Partial Correction
11/20/2006
2nd LAYER WEST FACING SIDE, 2ND LAYER APPROVED FLOOR TO CEILING. THROUGH PENETRATIONS OF PIPING AND DUCT SYSTEMS ARE NOT APPROVED PER PLAN. 6 LINE H-D LINES
Gas Service Inspection - Commercial Partial 11/21/2006
Correction
Resolved
11/21/2006
Gas Test Pressure (IFGC) Central Plant
Correction
Partial Correction
11/21/2006
None 6 INCH WELDED PIPE ONLY FROM METER LOCATION TO BOILER ROOM { CENTERAL PLANT }. TEST PRESSURE 60 PSI. RELEASE GAS.
All Rough Inspection - Commercial Partial 11/22/2006
Correction
Partial Correction
11/22/2006
AREAS INSPECTED IN-WALL D LINE TO H LINE FROM 1 TO SIX OKAY TO COVER.
Correction
Resolved
11/22/2006
Water/DWV protection from damage (IPC) PROTECTION OF PLUMBING, OTHER THAN STEEL OR CAST IRON, MINIMUM 2 INCHES ABOVE AND BELOW TOP AND BOTTOM PLATES AND PLUMBING RAN HORZ THROUGH STUDS < 1.5" FROM FACE OF STUD OR PLATE TO BE PROTECTED W/ SHEILD PLATES SHALL BE MIN 0.062" THICK(1.6 MM) STEEL. THROUGHOUT 1-6 D-H LINES
Correction
Resolved
11/22/2006
MISC ELECTRICAL INCOMPLETE OUTLET CONDUCTORS NOT INSTALLED. EAST WALL REPAIR SHOP 1-ME1144
Correction
Corrective Action Required
11/22/2006
SWITCHES CONDUCTORS FOR SWITCHES ARE NOT INSTALLED. M.C. RAN, WILL CHECK BOXES AT ABOVE CEILING INSPECTION. 1-6 D-H LINES
Correction
Resolved
11/22/2006
Cleanout Accessability
Correction
Resolved
11/22/2006
Electrical Conductor Protection ELECTRICAL CONDUCTORS REQUIRE PROTECTION THROUGH STUDS WHERE PUSHED BACK FROM PLUMBING. SOUTH SIDE SOUTH WALL BREAK ROOM 1-B01130
All Rough Inspection - Commercial Partial 11/29/2006
Correction
Partial Correction
11/29/2006
IN-WALL 2ND FLOOR EXTERIOR MECHANICAL 2-ME1500, 2-ME1291, 2-ME1292, 2-ME1263 AND STAIRWAY 3. BOXES METALLIC TUBING, VERIFY BONDING. AREAS LISTED BELOW OKAY TO COVER 11-29-06
Rated Assembly Inspection Partial 12/06/2006
Correction
Partial Correction
12/06/2006
2 HOUR FS 2 HOUR FIRE SEPARATION WALL REQUIRED NEXT TO VEST. 1ST LAYER APPROVED STAIR TOWER 3
All Rough Inspection - Commercial Partial 12/07/2006
Correction
Partial Correction
12/07/2006
IN-WALL MOB AREA C 12/7/06-ALL AREAS FROM 3-6/H-L LINES. OFFICES: 1-D11710, 1-D11709,1-D11705, 1-D11702, WAREWASHING ROOM, LOCKERS & TOILET, RECEPTION/WAITING ROOM 1-EH1067, JANITOR LY1206, CORRIDORS: 1-LY1210, 1-LY1225. OKAY TO COVER AREAS LISTED BELOW
Rated Assembly Inspection Partial 12/18/2006
Correction
Resolved
12/18/2006
2 HOUR FS 2 HOUR FIRE SEPARATION WALL REQUIRED NEXT TO VEST. 1ST LAYER APPROVED 2ND LAYER APPROVED STAIR TOWER 3
All Rough Inspection - Commercial Partial 12/18/2006
Correction
Corrective Action Required
12/18/2006
MISC ELECTRICAL INCOMPLETE METALLIC CONDUIT INSTALLED TO J BOXES, LEAVE FACEPLATES OFF UNTIL ABOVE CEILING INSPECTION TO VERIFY MAKEUP. ALL AREAS
Correction
Resolved
12/18/2006
IN-WALL 2ND FLOOR EXTERIOR MECHANICAL 2-ME1500, 2-ME1291, 2-ME1292, 2-ME1263 AND STAIRWAY 3. BOXES METALLIC TUBING, VERIFY BONDING. AREAS LISTED BELOW OKAY TO COVER 11-29-06
Correction
Resolved
12/18/2006
IN-WALL MOB AREA C 12/7/06-ALL AREAS FROM 3-6/H-L LINES. OFFICES: 1-D11710, 1-D11709,1-D11705, 1-D11702, WAREWASHING ROOM, LOCKERS & TOILET, RECEPTION/WAITING ROOM 1-EH1067, JANITOR LY1206, CORRIDORS: 1-LY1210, 1-LY1225. OKAY TO COVER AREAS LISTED BELOW
Correction
Partial Correction
12/18/2006
NONE FROM 9 LINE TO 12 LINE/H LINE TO D LINE. IN-WALL, OKAY TO COVER. OKAY TO COVER AREAS LISTED BELOW
All Rough Inspection - Commercial Partial 12/29/2006
Correction
Partial Correction
12/29/2006
AREAS INSPECTED IN-WALL D LINE TO H LINE FROM 1 TO SIX OKAY TO COVER.
Correction
Resolved
12/29/2006
Water/DWV protection from damage (IPC) PROTECTION OF PLUMBING, OTHER THAN STEEL OR CAST IRON, MINIMUM 2 INCHES ABOVE AND BELOW TOP AND BOTTOM PLATES AND PLUMBING RAN HORZ THROUGH STUDS < 1.5" FROM FACE OF STUD OR PLATE TO BE PROTECTED W/ SHEILD PLATES SHALL BE MIN 0.062" THICK(1.6 MM) STEEL. THROUGHOUT 1-6 D-H LINES
Correction
Resolved
12/29/2006
IN-WALL INWALL INSPECTION LINE 6 TO11 LINE K- LINE TO H LINE - APPROVED TO COVER 6-LINE -11 H-TO K
Rough Framing Inspection - Commercial Request Complete 1/10/2007 1/11/2007 01/11/2007
All Rough Inspection - Commercial Partial 01/17/2007
Correction
Resolved
01/17/2007
IN-WALL INWALL INSPECTION LINE 6 TO11 LINE K- LINE TO H LINE - APPROVED TO COVER 6 line to 11 d to h approved except 4 Operating Rooms 6-LINE -11 H-TO K
Correction
Partial Correction
01/17/2007
Stair Towers IN Wall approved in stair towers 1, 2, 3, and 4.
Correction
Resolved
01/17/2007
EXTERIOR WALL FRAMING ALL EXTERIOR WALL FRAMING APPROVED.
Gas Piping Inspection - Commercial Passed 01/17/2007
Correction
Resolved
01/17/2007
Protective Coatings & Wrapping (IFGC 404.8.2) North of Central Plant
Correction
Resolved
01/17/2007
None Kitchen area @ MOB to Roof-top units pressure test approved. 60 psig held for 30 min. Kitchen Area to central p
Rated Assembly Inspection Partial 01/22/2007
Correction
Resolved
01/22/2007
STAIR TOWER 1 ONE LAYER 5/8 TYPE X APPROVED
Correction
Partial Correction
01/22/2007
STAIR TOWER 4 STAIR TOWER 4 1ST LAYER APPROVED
All Rough Inspection - Commercial Partial 01/22/2007
Correction
Partial Correction
01/22/2007
AREA B IN WALL APPROVED. OKAY TO COVER. 12 LINE TO 15 LINE 12 LINE TO 15 LINE
Rated Assembly Inspection Partial 01/26/2007
Correction
Partial Correction
01/26/2007
1ST FL 2HR WALL AT 6 LINE 1ST LAYER & 2ND LAYER
Correction
Corrective Action Required
01/26/2007
2nd LAYER WEST FACING, 2ND LAYER APPROVED FLOOR TO CEILING EAST FACING, 2ND LAYER APPROVED ABOVE FALSE CEILING. 1ST LAYER APPROVED BELOW. THROUGH PENETRATIONS (2 OPENINGS BETWEEN D-F LINES) OF PIPING AND DUCT SYSTEMS ARE NOT APPROVED PER PLAN. 6 LINE H-D LINES
Correction
Partial Correction
01/26/2007
STAIR TOWER 4 STAIR TOWER 4 1ST AND 2ND LAYER APPROVED.
Correction
Resolved
01/26/2007
TYPE YOUR OWN TEXT 1ST LAYER 1 HOUR (ELEVATOR 4) APPROVED. 1ST LAYER 2 HOUR (ELEVATOR 1, 2, 3) APPROVED. ELEVATOR
Correction
Partial Correction
01/26/2007
9 LINE 1 HOUR WALL 1 HOUR WALL AT 9 LINE ON 1ST FLOOR APPROVED. 1ST FLOOR
All Rough Inspection - Commercial Partial 02/05/2007
Correction
Partial Correction
02/05/2007
AREA D IN-WALL OKAY TO COVER 11-LINE TO 17 H-LINE TO K-LINE
All Rough Inspection - Commercial Partial 02/12/2007
Correction
Partial Correction
02/12/2007
1st fl. Area D Okay to cover except rooms: RAD/FLONRO, HOT LAB, STAP TLT, NUCLEAR MEDICINE, STAIR TOWER 5. 11-13,K-P lines
Correction
Partial Correction
02/12/2007
2ND FLOOR OKAY TO COVER IN-WALL EXCEPT ROOM 1093 13-17,H-K & 11-13,D-H
Electrical Service Inspection Passed 02/12/2007
Correction
Resolved
02/12/2007
TEMPORARY 1200 AMP SERVICE 1200 AMP TEMPORARY SERVICE 3 PHASE APPROVED. NORTH WEST CORNER ROOM B10
All Rough Inspection - Commercial Partial 02/21/2007
Correction
Partial Correction
02/21/2007
1st fl. Area D OKAY TO COVER IN WALL 11-13,K-P lines
Gas Piping Inspection - Commercial Passed 02/22/2007
Correction
Resolved
02/22/2007
None GAS PIPING APPROVED FROM BULDING ENTRANCE THROUGH ROOF PENETRATION AT RM - (2-ME1500) AREA A - MOB
Gas Service Inspection - Commercial Partial 02/22/2007
Correction
Resolved
02/22/2007
None SEE GAS PIPING FOR AREA (BUILDING ENTRANCE TO ROOF PENETRATION)- HELD 60 PSI FOR 2-1/2 HRS - AREA - A MOB
Rated Assembly Inspection Partial 02/26/2007
Correction
Partial Correction
02/26/2007
SHAFT ENCLOSURE IN-WALL APPROVED ON TOWER 6. 1ST LAYER APPROVED AT TOWER 5. STAIR TOWER 5 AND 6
Rated Assembly Inspection Partial 03/05/2007
Correction
Partial Correction
03/05/2007
SHAFT ENCLOSURE IN-WALL & 1ST LAYER APPROVED ON TOWER 6. 1ST & 2ND LAYER APPROVED AT TOWER 5. STAIR TOWER 5 AND 6
All Rough Inspection - Commercial Partial 03/05/2007
Correction
Partial Correction
03/05/2007
2ND FLOOR OKAY TO COVER IN-WALL 7-17,H-K & 11-13,D-H
Correction
Partial Correction
03/05/2007
1st FLOOR OKAY TO COVER OR ROOMS
Sidewalk Inspection Partial 03/05/2007
Sidewalk Inspection Partial 03/06/2007
All Rough Inspection - Commercial Partial 03/19/2007
Correction
Corrective Action Required
03/19/2007
Prevent Physical Damage (IRC) 2-NU1099 = EAST WALL + NORTH WALL 2-NU1101 = SOUTH WALL = INSTALL PROTECTIVE PLATES SECOND FLOOR (F-H) - (11-13) LINES
Correction
Corrective Action Required
03/19/2007
GAS PIPING PROTECTION 2-MS 1135, 2-NU1098 SECOND FLOOR (F-H) - (11-13) LINES
Correction
Corrective Action Required
03/19/2007
FRAME WORK INCOMPLETE 2-OB133 SECOND FLOOR (F-H) - (11-13) LINES
Correction
Corrective Action Required
03/19/2007
Prevent Physical Damage (IRC) 2-MS 1026 PROTECT ELECTRICAL WIRING WHEN CLOSER THAN 1-1/4" FROM STUD FACE SECOND FLOOR (8-11) - (H-L) LINE
Correction
Corrective Action Required
03/19/2007
OPEN WHIPS 2-MS1021, 2-MS1019 SECOND FLOOR (8-11) - (H-L) LINE
Correction
Corrective Action Required
03/19/2007
Water/DWV Preotection Against Physical Damage (IRC) 2-MS1008 SECOND FLOOR (8-11) - (H-L) LINE
Correction
Corrective Action Required
03/19/2007
STUD WALLS MISSING 2-MS1014, 2-MS1009 FRAMING MISSING AROUND PLUMBING AND ROOFTOP DRAIN LINES *INSPECTION STOPPED HAVE SUPER. WALK PRIOR TO INSPECTION* SECOND FLOOR (8-11) - (H-L) LINE
Electrical Service Inspection Passed 03/23/2007
Correction
Resolved
03/23/2007
MAIN 3000 AMP ELECTRICAL SERVICE APPROVED FOR RELEASE OF MAIN 3000 AMP ELECTRICAL SERVICE
All Rough Inspection - Commercial Partial 03/28/2007
Correction
Resolved
03/28/2007
SOUTH EAST SIDE 2ND FLOOR 12 ROOMS , 4 INTERIOR ROOMS , APPROVED IN-WALL LINE"L-N, 11-13
Electrical Service Inspection Passed 04/12/2007
Correction
Resolved
04/12/2007
1600 AMP SUPPLEMENTAL SERVICE APPROVED FOR RELEASE
Gas Piping Inspection - Commercial Passed 04/25/2007
Correction
Resolved
04/25/2007
None GAS PIPING APPROVED FROM BULDING ENTRANCE THROUGH ROOF PENETRATION AT RM - (2-ME1500) AREA A - MOB
Correction
Resolved
04/25/2007
None GAS PIPING IN THIS AREA APPROVED AREA -A RTU 1 & 2
Above Ceiling Inspection Failed 05/02/2007
Correction
Corrective Action Required
05/02/2007
Area B Ducts penetrating room shall be constructed of sheet steel not less than 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals to waive damper requirements. pa1323 1st floor
Correction
Partial Correction
05/02/2007
Area B okay to drop tile except dir office 1-1c1392. power for exit lighting not installed. Will verify at final inspection. d to f line 9 line to 15 line
Above Ceiling Inspection Failed 05/08/2007
Correction
Corrective Action Required
05/08/2007
AREA C ALL SYSTEMS IN THIS AREA APPROVED EXCEPT HOODS. HOODS HAVE NOT BEEN INSPECTED. H-K, 1-3 LINES
Correction
Corrective Action Required
05/08/2007
AREA B DO NOT DROP IN LAUNDRY, IT TECH/WORK, AND BIO MED ROOMS. 2 HOUR FIRE WALL SHALL BE CONTINUOUS TO DECK THROUGH 2ND FLOOR. AS IS, ROCK TERMINATES AT BOTTOM OF STRUCTURAL BEAM. F-H, 3-6 LINES
Correction
Corrective Action Required
05/08/2007
AREA B NOT READY FOR INSPECTION. F-H, 9-13 LINES
Correction
Corrective Action Required
05/08/2007
AREA A 6 LINE FIRE WALL- COORIDOR HAS 4 INCH DUCT PENETRATION ABOVE DOORWAY UNPROTECTED. 2 HOUR WALL SHALL EXTEND TO THE DECK FOR 2ND FLOOR. AS IS, TERMINATES AT BOTTOM OF STRUCTURAL BEAM. DO NOT DROP AREAS ALONG WEST SIDE OF 6 LINE. COORIDOR, STAFF BREAK RM LOCKERS
Above Ceiling Inspection Failed 05/10/2007
Correction
Corrective Action Required
05/10/2007
AREA B OKAY TO DROP EXCEPT FOLLOWING AREAS: DECONTAM-LOW VOLT. LINES ON SPRINKLER ICU WAITING RM., RESPIRATORY WORK RM., NURSE LOUNGE-??? QUARTER BENDS/LONG SWEEP ON SAN. LINES F-H, 9-13 LINES
Above Ceiling Inspection Failed 05/16/2007
Correction
Partial Correction
05/16/2007
AREA D OKAY TO DROP EXCEPT FOLLOWING LOCATIONS: 1507 1552: CLEANOUT REQUIRED FOR 90 DEGREE CHANGE IN DIRECTION FOR SAN. LINES. MRI ROOM, 1513: NOT READY 11-15, H-P
Hood/Duct Inspection Not Ready 05/16/2007
Correction
Corrective Action Required
05/16/2007
AREA A HOOD COVERED W/ WRAP BEFORE INSPECTION. LEDGES/LIPS IDENTIFIED IN AREAS OF TRANSITION FROM VERTICAL TO HORIZONTAL. ACCESS OPENINGS REQUIRED EVERY 20 FEET ON HORZ. EXPOSE AS REQUESTED FOR INSPECTION. KITCHEN 1ST FLOOR
Above Ceiling Inspection Failed 05/21/2007
Correction
Corrective Action Required
05/21/2007
Area B Ducts penetrating room shall be constructed of sheet steel not less than 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals to waive damper requirements. pa1323 1st floor
Correction
Partial Correction
05/21/2007
Area B okay to drop tile except dir office 1-1c1392. power for exit lighting not installed. Will verify at final inspection. 1ST FLOOR d to f line 9 line to 15 line
Correction
Corrective Action Required
05/21/2007
AREA C ALL SYSTEMS IN THIS AREA APPROVED EXCEPT HOODS. SEE HOOD INSPECTION H-K, 1-3 LINES
Correction
Corrective Action Required
05/21/2007
AREA B DO NOT DROP IN LAUNDRY, IT TECH/WORK, AND BIO MED ROOMS. 2 HOUR FIRE WALL SHALL BE CONTINUOUS TO DECK THROUGH 2ND FLOOR. AS IS, ROCK TERMINATES AT BOTTOM OF STRUCTURAL BEAM. 1ST FLOOR F-H, 3-6 LINES
Correction
Resolved
05/21/2007
AREA B OKAY TO DROP 1ST FLOOR F-H, 9-13 LINES
Correction
Corrective Action Required
05/21/2007
AREA A 6 LINE FIRE WALL- COORIDOR HAS 4 INCH DUCT PENETRATION ABOVE DOORWAY UNPROTECTED. 2 HOUR WALL SHALL EXTEND TO THE DECK FOR 2ND FLOOR. AS IS, TERMINATES AT BOTTOM OF STRUCTURAL BEAM. DO NOT DROP AREAS ALONG WEST SIDE OF 6 LINE. 1ST FLOOR
Correction
Partial Correction
05/21/2007
AREA D OKAY TO DROP EXCEPT FOLLOWING LOCATIONS: 1507 MRI ROOM, 1513: NOT READY 1ST FLOOR 11-15, H-P
Correction
Corrective Action Required
05/21/2007
AREA A OKAY TO DROP EXCEPT THR FOLLOWING: ANY AREAS ALONG 6 LINE. 2HOUR WALL TO EXTEND TO DECK ABOVE. 2 OPENINGS WITH SYSTEMS PASSING THROUGH. LISTED 3M PILLOW INSTALLATION WAS NOT INSPECTED OR APPROVED. 1-5, D-L
Above Ceiling Inspection Failed 05/25/2007
Correction
Resolved
05/25/2007
AREA A CORRIDOR EAST OF LINE 9 6-9 D-H
Correction
Corrective Action Required
05/25/2007
AREA C ELEVATOR LOBBY AREA - INSTALL LIGHTS ROOM 1025- HVAC PANEL H-K 6-9
Correction
Corrective Action Required
05/25/2007
AREA D ROOM 1286 INSPECT CATH LAB REAR ROOM - INSTALL LIGHTS AND HVAC GRILLS 9- 12 K-H ROOM 1286
Rated Assembly Inspection Partial 05/30/2007
Correction
Partial Correction
05/30/2007
SHAFTS FOR MECHANICAL SHAFTS FOR 9 MECHANICAL UNITS ON 2ND FLOOR-1ST LAYER ROCK APPROVED. MECHANICAL ROOMS 2ND FLOOR
Rated Assembly Inspection Partial 06/01/2007
Correction
Resolved
06/01/2007
SHAFTS FOR MECHANICAL SHAFTS FOR 9 FLOOR MECHHANICAL UNITS ON 2ND FLOOR APPROVED. MECHANICAL ROOMS 2ND FLOOR
Above Ceiling Inspection Failed 06/01/2007
Correction
Corrective Action Required
06/01/2007
2ND FLOOR AREA B OKAY TO COVER EXCEPT FOLLOWING. BATHROOMS IN PATIENT ROOMS NOT INSPECTED. SOIL ROOM 2MS1161: DUCT PENETRATING 1 HOUR WALL MUST BE EITHER 26G. STEEL MINIMUM OR PROVIDE FIRE RATED DAMPER. D-G, 11-13 LINES
Correction
Corrective Action Required
06/01/2007
2ND FLOOR AREA D OKAY TO COVER EXCEPT FOLLOWING: BATHROOMS IN PATIENT ROOMS NOT INSPECTED(HARD LIDS) ROOM 2-MS1222-DUCTS PENETRATING 1 HOUR WALL MUST BE MIN 26 G. STEEL TO OUTLET OR PROVIDE FIRE RATED DAMPER. 13-17, H-K LINES
Hood/Duct Inspection Passed 06/01/2007
Correction
Resolved
06/01/2007
AREA A KITCHEN HOODS APPROVED. KITCHEN 1ST FLOOR
All Rough Inspection - Commercial Passed 06/05/2007
Correction
Resolved
06/05/2007
AREAS INSPECTED IN-WALL
Correction
Resolved
06/05/2007
MISC ELECTRICAL INCOMPLETE ALL AREAS
Correction
Resolved
06/05/2007
SWITCHES 1-6 D-H LINES
Correction
Resolved
06/05/2007
NONE OKAY TO COVER AREAS LISTED BELOW
Correction
Resolved
06/05/2007
Stair Towers
Correction
Resolved
06/05/2007
AREA B 12 LINE TO 15 LINE 12 LINE TO 15 LINE
Correction
Resolved
06/05/2007
AREA D IN-WALL OKAY TO COVER 11-LINE TO 17 H-LINE TO K-LINE
Correction
Resolved
06/05/2007
1st fl. Area D OKAY TO COVER IN WALL 11-13,K-P lines
Correction
Resolved
06/05/2007
2ND FLOOR OKAY TO COVER IN-WALL 7-17,H-K & 11-13,D-H
Correction
Resolved
06/05/2007
1st FLOOR OKAY TO COVER
Correction
Resolved
06/05/2007
Prevent Physical Damage (IRC) SECOND FLOOR (F-H) - (11-13) LINES
Correction
Resolved
06/05/2007
GAS PIPING PROTECTION 2-MS 1135, 2-NU1098 SECOND FLOOR (F-H) - (11-13) LINES
Correction
Resolved
06/05/2007
FRAME WORK INCOMPLETE SECOND FLOOR (F-H) - (11-13) LINES
Correction
Resolved
06/05/2007
Prevent Physical Damage (IRC) SECOND FLOOR (8-11) - (H-L) LINE
Correction
Resolved
06/05/2007
OPEN WHIPS SECOND FLOOR (8-11) - (H-L) LINE
Correction
Resolved
06/05/2007
Water/DWV Preotection Against Physical Damage (IRC) SECOND FLOOR (8-11) - (H-L) LINE
Correction
Resolved
06/05/2007
STUD WALLS MISSING SECOND FLOOR (8-11) - (H-L) LINE
Correction
Resolved
06/05/2007
AREA C 1ST FLOOR ROOMS 1054, 1056, 1058 APPROVED TO COVER WHEN READY RE-MODEL ROOMS
Rated Assembly Inspection Partial 06/05/2007
Correction
Resolved
06/05/2007
SHAFTS FOR MECHANICAL SHAFTS FOR 9 FLOOR MECHHANICAL UNITS ON 2ND FLOOR APPROVED. MECHANICAL ROOMS 2ND FLOOR
Above Ceiling Inspection Failed 06/05/2007
Correction
Corrective Action Required
06/05/2007
2ND FLOOR AREA C OKAY TO COVER EXCEPT FOLLOWING: SOIL ROOM 2-MS1066-DUCTS PENETRATING 1 HOUR WALL MUST HAVE DAMPER OR BE MIN 26 G. STEEL FROM REGISTER TO SOURCE. AREAS WITH HARD LIDS, PROVIDE ACCESS FOR INSPECTION. H-K, 7-11 LINES
Above Ceiling Inspection Failed 06/08/2007
Correction
Corrective Action Required
06/08/2007
Area B Ducts penetrating room shall be constructed of sheet steel not less than 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals to waive damper requirements. 1 HOUR WALLS
Correction
Resolved
06/08/2007
Area B 1ST FLOOR d to f line 9 line to 15 line
Correction
Resolved
06/08/2007
AREA B OKAY TO DROP 1ST FLOOR F-H, 9-13 LINES
Correction
Corrective Action Required
06/08/2007
AREA A 2 HOUR WALL SHALL EXTEND TO THE DECK FOR 2ND FLOOR. AS IS, TERMINATES AT BOTTOM OF STRUCTURAL BEAM. DO NOT DROP AREAS ALONG WEST SIDE OF 6 LINE. 1ST FLOOR
Correction
Resolved
06/08/2007
AREA D 1ST FLOOR 11-15, H-P
Correction
Resolved
06/08/2007
AREA C H-K 6-9
Correction
Resolved
06/08/2007
AREA D 9- 12 K-H ROOM 1286
Correction
Partial Correction
06/08/2007
2ND FLOOR AREA D OKAY TO COVER EXCEPT THE FOLLOWING: WAITING AREA 2-LY1002: DUCT PENTRATING 1 HOUR WALL FROM COORIDOR 2-MS1283, TURNS TO FLEX AT REGISTER. MUST BE 26 G. STEEL OR PROVIDE DAMPER AT 1 HOUR WALL. SOIL ROOM 2-MS1254-SEAL ALL PENETRATIONS THROUGH 1 HOUR WAL 11-13, K-P LINES
Above Ceiling Inspection Failed 06/13/2007
Correction
Resolved
06/13/2007
Area B 1 HOUR WALLS
Correction
Resolved
06/13/2007
AREA C H-K, 1-3 LINES
Correction
Resolved
06/13/2007
AREA B OKAY TO DROP 1ST FLOOR F-H, 9-13 LINES
Correction
Corrective Action Required
06/13/2007
AREA A 2 HOUR WALL SHALL EXTEND TO THE DECK FOR 2ND FLOOR. AS IS, TERMINATES AT BOTTOM OF STRUCTURAL BEAM. DO NOT DROP AREAS ALONG WEST SIDE OF 6 LINE. 1ST FLOOR
Correction
Resolved
06/13/2007
AREA D 1ST FLOOR 11-15, H-P
Correction
Corrective Action Required
06/13/2007
AREA A OKAY TO DROP EXCEPT THR FOLLOWING 2 OPENINGS WITH SYSTEMS PASSING THROUGH. 1-5, D-L
Correction
Resolved
06/13/2007
AREA A CORRIDOR EAST OF LINE 9 6-9 D-H
Correction
Resolved
06/13/2007
AREA C H-K 6-9
Correction
Resolved
06/13/2007
AREA D 9- 12 K-H ROOM 1286
Correction
Corrective Action Required
06/13/2007
2ND FLOOR AREA B OKAY TO COVER EXCEPT FOLLOWING. BATHROOMS IN PATIENT ROOMS NOT INSPECTED. D-G, 11-13 LINES
Correction
Corrective Action Required
06/13/2007
2ND FLOOR AREA D OKAY TO COVER EXCEPT FOLLOWING: BATHROOMS IN PATIENT ROOMS NOT INSPECTED(HARD LIDS) 13-17, H-K LINES
Correction
Corrective Action Required
06/13/2007
2ND FLOOR AREA C OKAY TO COVER EXCEPT FOLLOWING: AREAS WITH HARD LIDS, PROVIDE ACCESS FOR INSPECTION. H-K, 7-11 LINES
Correction
Resolved
06/13/2007
2ND FLOOR AREA D 11-13, K-P LINES
Correction
Resolved
06/13/2007
2ND FLOOR AREA B OKAY TO DROP F-H, 9-13& ROTUNDA
Above Ceiling Inspection Failed 06/19/2007
Correction
Resolved
06/19/2007
MISC. 1ST FLOOR: WC STORAGE, ELEC, PHONES, VALET STORAGE ROOMS @ MAIN ENTRANCE. 2ND FLOOR MOB CORRIDOR (2-LY1035, 2-LY1307, 2-LY1042, 2-LY1043) STAIR TOWER 6 AREAS APPROVED LISTED BELOW
Rated Assembly Inspection Partial 06/28/2007
Correction
Partial Correction
06/28/2007
1ST FL 2HR WALL AT 6 LINE FRAMING AT WALL CONDITION AT 2HR SEPARATION. FRAMING APPROVED- APPROVED TO INSTALL 1ST LAYER LINE 6 1ST LAYER & 2ND LAYER I BEAM LINE 6
Above Ceiling Inspection Failed 06/28/2007
Correction
Resolved
06/28/2007
None 6 STAIR TOWERS ABOVE CEILING APPROVED STAIR TOWERS
Issue Temporary C of O Complete 6/28/2007 7/2/2007 07/02/2007
Rated Assembly Inspection Not Ready 07/05/2007
Correction
Corrective Action Required
07/05/2007
Not Ready
Rated Assembly Inspection Not Ready 07/06/2007
Correction
Corrective Action Required
07/06/2007
Not Ready @ I BEAM SOFFIT, ALONG LINE 6 (2 HR SEP.) -FRAMING APPROVED FOR APPLICATION OF 1ST LAYER. NO RECORD OF INSP. OF 1ST LAYER -WHAT IS THE UL LISTING OF FIRE ASSY? SCREW PATTERN?
Electrical Service Inspection Passed 07/09/2007
Correction
Resolved
07/09/2007
2051 SE SHENANDOAH RELEASE 60 AMP SERVICE FOR EXCESS FLOW HOLDING BASIN. PLEASE ADVISE AQUILA, 2051 SE SHENANDOAH FOR BILLING PURPOSE. PERMIT UNDER 2100 SE BLUE PKWY. EXCESS HOLDING BASIN SERVICE FOR
Suspended Slab Inspection Passed 07/11/2007
Correction
Resolved
07/11/2007
INSTALLATION PER PLANS SUSPENDED SLAB = APPROVED AT THE FOLLOWING LOCATION - EAST TO WEST(1-6 LINE), NORTH TO SOUTH(D-3' SOUTH OF F LINE) - SEE GENERAL NOTES S-101(3.7.2) TYPE B 3RD FLOOR EAST SIDE
Water Service Inspection Passed 07/11/2007
Correction
Resolved
07/11/2007
INSPECTIONS DONE BY PUBLIC WORKS
Underground Electrical Inspection - Commercial Passed 07/11/2007
Correction
Resolved
07/11/2007
Light Pole Bases Approved at the following
Correction
Resolved
07/11/2007
Primary Conduit From MH w. of J To far south curb line
Correction
Resolved
07/11/2007
Lightning Protection System 3/0 Copper Installed at:
Correction
Resolved
07/11/2007
CONDUIT FOR FEEDERS MAIN TRANSFORMER WEST OF CENTRAL PLANT
Correction
Resolved
07/11/2007
LIGHTNING PROTECTION 3/0 copper installed at:
Above Ceiling Inspection Passed 07/11/2007
Correction
Resolved
07/11/2007
AREA B 1ST FLOOR F-H, 3-6 LINES
Correction
Resolved
07/11/2007
AREA A 1ST FLOOR
Correction
Resolved
07/11/2007
AREA A 1-5, D-L
Correction
Resolved
07/11/2007
2ND FLOOR AREA B D-G, 11-13 LINES
Correction
Resolved
07/11/2007
2ND FLOOR AREA D 13-17, H-K LINES
Correction
Resolved
07/11/2007
2ND FLOOR AREA C H-K, 7-11 LINES
Occupancy Inspection - Codes Commercial Failed 07/11/2007
Correction
Corrective Action Required
07/11/2007
Backflow protection kitchen 608.16.1 Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an air gap. SODA MACHINE
Correction
Corrective Action Required
07/11/2007
Backflow protection kitchen DISHWASHER AND COOKING UNIT CONNECTED TO POTABLE WATER. BACKFLOW DEVICE QUESTION. SINK IN CLOSET ADJACENT TO DISHWASHER: HOSE SPRAYER CAPABLE OF BEING PLACED BELOW FLOOD LE VEL OF SINK. misc kitchen equipment
Correction
Corrective Action Required
07/11/2007
STATE ELEVATOR CERTIFICATE PLEASE SUBMIT STATE ELEVATOR INSPECTION
Correction
Corrective Action Required
07/11/2007
SPECIAL INSPECTIONS SUBMIT FINAL SPECIAL INSPECTIONS REPORT SHOWING NO VIOLATIONS.
Correction
Corrective Action Required
07/11/2007
Receive Public Works Approval PUBLIC WORKS LIST OF CORRECTIONS UNDER SEPARATE COVER.
Correction
Corrective Action Required
07/11/2007
Receive Planning & Development Approval PLANNING & DEVELOPMENT LIST OF CORRECTIONS UNDER SEPARATE COVER
Correction
Corrective Action Required
07/11/2007
Receive Water Utilities Approval
Correction
Corrective Action Required
07/11/2007
SPRINKLER HEADS UNTAPE AND FINISH ALL HEADS THROUGHOUT BUILDING
Correction
Corrective Action Required
07/11/2007
FINISH FLOOR FINISH FLOOR SURFACE IN STAIR TOWER AS TO NO CHANGE IN ELEVATION. STAIR #2 & # 5
Correction
Corrective Action Required
07/11/2007
MISC ELECTRICAL THROUGHOUT BUILDING- OPEN BOXES AND MISSING FIXTURES. OPEN JUNCTION BOXES SHOULD HAVE FACEPLATES.
Correction
Corrective Action Required
07/11/2007
SIGNAGE ACCESSABLE SIGNAGE TO BE INSTALLED THROUGHOUT THE BUILDING
Correction
Corrective Action Required
07/11/2007
KNEE GUARDS TO BE INSTALLELD AT LAVS AT ALL ACCESSABLE RESTROOMS
Underslab Plumbing Inspection - Commercial Passed 07/11/2007
Correction
Resolved
07/11/2007
AREA A AREA A-B FROM 1 LINE TO 15 LINE
Correction
Resolved
07/11/2007
AREA C FROM 1-8 13 FT. SOUTH OF J-LINE
Correction
Resolved
07/11/2007
AREA D 13 FT. SOUTH J TO P LINES BETWEEN 12 AND 13 LINES
Correction
Resolved
07/11/2007
STORM PIPE
Correction
Resolved
07/11/2007
AREA A WASTE
Correction
Resolved
07/11/2007
AREA C
Correction
Resolved
07/11/2007
ER AREA BETWEEN 16-17 BETWEN J-K
Underslab Electrical Inspection - Commercial Passed 07/11/2007
Correction
Resolved
07/11/2007
AREA A D-2 TO I-5
Correction
Resolved
07/11/2007
None 6 - 8.5 LINE E - F.5 LINE
Correction
Resolved
07/11/2007
AREA B BETWEEN F & G 7.2 TO 9
Correction
Resolved
07/11/2007
None INTERIOR
Correction
Resolved
07/11/2007
None EMERGENCY ELEC. ROOM D LINE & 4 LINE
Correction
Resolved
07/11/2007
None D & 1 LINE NW CORNER
Correction
Resolved
07/11/2007
None D LINE & 4 LINE NW CORNER OF BUILDING
Correction
Resolved
07/11/2007
None INTERIOR
Correction
Resolved
07/11/2007
Area A C-D OUTSIDE 4 LINE
Correction
Resolved
07/11/2007
ELECTRIC ROOM AT K-9 AND J-9
Correction
Resolved
07/11/2007
H-J & 9-12
Correction
Resolved
07/11/2007
Main Electrical Room
Correction
Resolved
07/11/2007
HELIPAD EAST SIDE OF SITE
Sewer Service Inspection Passed 07/11/2007
Correction
Resolved
07/11/2007
INSPECTIONS DONE BY PUBLIC WORKS
Rough Framing Inspection - Commercial Passed 07/11/2007
Correction
Resolved
07/11/2007
EXTERIOR WALLS WEST WALL LINE #1 D-K
Correction
Resolved
07/11/2007
EXTERIOR WALLS WEST ELE. LINE 4 A-D
Correction
Resolved
07/11/2007
EXTERIOR WALLS NORTH ELEV. D LINE 1-15
Correction
Resolved
07/11/2007
EXTERIOR WALLS EAST - SOUTH-NORTH
Correction
Resolved
07/11/2007
STAIR TOWER #2-#3
Correction
Resolved
07/11/2007
EXTERIOR WALLS SOUTH ELEVATION
Gas Service Inspection - Commercial Passed 07/11/2007
Correction
Resolved
07/11/2007
None
Occupancy Inspection - Codes Commercial Failed 07/12/2007
Correction
Corrective Action Required
07/12/2007
Backflow protection kitchen 608.16.1 Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an air gap. SODA MACHINE
Correction
Corrective Action Required
07/12/2007
Backflow protection kitchen SINK IN CLOSET ADJACENT TO DISHWASHER: HOSE SPRAYER CAPABLE OF BEING PLACED BELOW FLOOD LEVEL OF SINK. misc kitchen equipment
Correction
Corrective Action Required
07/12/2007
FINISH FLOOR FINISH FLOOR SURFACE INCOMPLETE IN STAIR TOWERS. COMPLETE SO NO CHANGE IN ELEVATION EXISTS ON FLOOR SURFACE. STAIR #2 & # 5
Correction
Corrective Action Required
07/12/2007
Premises Identification ADDRESS NUMBERS TO VISABLE FROM THE PUBLIC WAY.
Correction
Corrective Action Required
07/12/2007
MISC. PLUMBING FIXTURES NOT INSTALLED AT TIME OF FINAL INSPECTION. FIXTURE TRAPS FOR PLUMBING FIXTURES ARE TO REMAIN CAPPED UNTIL FIXTURES ARE INSTALLED.
Correction
Resolved
07/12/2007
EMERGENCY POWER EMERGENCY POWER WAS TESTED AND APPROVED BOTH SYSTEMS. MOB & HOSPITAL
Correction
Corrective Action Required
07/12/2007
BUILDING USE OKAY TO STOCK FURNITURE AND FIXTURES. DO NOT OCCUPY.
Occupancy Inspection - Codes Commercial Failed 07/16/2007
Correction
Corrective Action Required
07/16/2007
License Tax Must be paid in full prior to any type of occupancy being issued.
Occupancy Inspection - Codes Commercial Failed 07/25/2007
Correction
Resolved
07/25/2007
SPECIAL INSPECTIONS
Correction
Corrective Action Required
07/25/2007
Receive Public Works Approval Provide permanent generator for excess flow holding basis. Minor plat shall be submitted to Planning and Development for the excess flow holding basin.
Correction
Resolved
07/25/2007
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Failed 07/26/2007
Correction
Resolved
07/26/2007
Backflow protection kitchen SODA MACHINE
Correction
Corrective Action Required
07/26/2007
Backflow protection kitchen SINK IN CLOSET ADJACENT TO DISHWASHER: HOSE SPRAYER CAPABLE OF BEING PLACED BELOW FLOOD LEVEL OF SINK. misc kitchen equipment
Correction
Resolved
07/26/2007
STATE ELEVATOR CERTIFICATE PLEASE SUBMIT STATE ELEVATOR INSPECTION
Correction
Corrective Action Required
07/26/2007
Receive Public Works Approval Provide permanent generator for excess flow holding basis. Minor plat shall be submitted to Planning and Development for the excess flow holding basin.
Correction
Resolved
07/26/2007
FINISH FLOOR STAIR #2 & # 5
Correction
Resolved
07/26/2007
MISC ELECTRICAL
Correction
Corrective Action Required
07/26/2007
SIGNAGE ACCESSABLE SIGNAGE TO BE INSTALLED THROUGHOUT THE BUILDING
Correction
Resolved
07/26/2007
Premises Identification
Correction
Resolved
07/26/2007
MISC. PLUMBING FIXTURES
Correction
Resolved
07/26/2007
BUILDING USE
Correction
Resolved
07/26/2007
License Tax
Correction
Corrective Action Required
07/26/2007
Identification of Service & Backup Identification of disconnecting means for all services shall be labeled in accordance with 2002 NEC. Label dedicated rooms as well as all means to disconnect power. Label all subpanels and main panels. central plant & Backup For MOB & Hosp.
Correction
Corrective Action Required
07/26/2007
Temp lighting Remove temp lighting in unfinished lease space. 1st floor MOB
Correction
Corrective Action Required
07/26/2007
Receive Fire Department Approval UNDER SEPARATE COVER. MUST SUBMIT PLANS FOR NEW FUEL STORAGE TANKS AT NORTH END OF BUILDING TO FIRE DEPARTMENT. SEE JOE DIR.
Correction
Corrective Action Required
07/26/2007
HANDRAILS HANDRAILS SHALL RETURN TO THE GUARD AT THE TOP OF THE STAIRS ON THE GUARD SIDE OF THE STAIRS. STAIR TOWERS 5, 4, 6, 1 GUARD SIDE HANDRAIL
Issue Temporary C of O Complete 7/25/2007 7/26/2007 07/26/2007
Occupancy Inspection - Codes Commercial Failed 08/20/2007
Correction
Resolved
08/20/2007
Backflow protection kitchen misc kitchen equipment
Correction
Resolved
08/20/2007
SPRINKLER HEADS THROUGHOUT BUILDING
Correction
Corrective Action Required
08/20/2007
SIGNAGE ACCESSABLE SIGNAGE TO BE INSTALLED THROUGHOUT THE BUILDING
Correction
Resolved
08/20/2007
Identification of Service & Backup central plant & Backup For MOB & Hosp.
Correction
Resolved
08/20/2007
HANDRAILS
Correction
Corrective Action Required
08/20/2007
5th Water Tap & Meter Provide payment for water meter and tap for 3" line. By Helipad East Side of Campus
Occupancy Inspection - Codes Commercial Failed 02/18/2009
Correction
Resolved
02/18/2009
SIGNAGE
Correction
Resolved
02/18/2009
KNEE GUARDS TO BE INSTALLELD AT LAVS AT ALL ACCESSABLE RESTROOMS
Correction
Resolved
02/18/2009
Temp lighting Remove temp lighting in unfinished lease space. 1st floor MOB
Correction
Resolved
02/18/2009
Receive Fire Department Approval
Correction
Resolved
02/18/2009
5th Water Tap & Meter Provide payment for water meter and tap for 3" line. By Helipad East Side of Campus
Occupancy Inspection - Codes Commercial Failed 07/20/2009
Correction
Resolved
07/20/2009
Receive Fire Department Approval see email from J. Dir dated 20 July 09.
Occupancy Inspection - Codes Commercial Failed 02/10/2010
Correction
Resolved
02/10/2010
Receive Planning & Development Approval - meeting on 10 Feb 10 - approved
Occupancy Inspection - Codes Commercial Full C of O 11/18/2010
Documents & Images
Date Uploaded File Type Document Name
11/18/2010 Letter Field Certificate of Occupancy
11/19/2010 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home