Permit Application Status

B0600392


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600392
Building Permit - Commercial
Certificate of Occupancy
BHUMIKA LLC
NEW COMMERCIAL
NEW COMMERCIAL BUILDING
03/22/2006
06/19/2006
12/16/2006
02/14/2007
Locations
Contacts
ARCHER ENGINEERS, Address:3731 NE TROON DR  
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
BHUMIKA LLC, Address:3151 NE CARNEGIE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/12/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Codes Administration - The application does not fully describe the use of this facility.
Correction

Codes Administration - The code analysis indicates a construction type of V but does not indicate if it is A or B.
Correction

Codes Administration - The architectural plans indicate the rated wall with a solid line which is not consistant with the details for the assembly.
Correction

Codes Administration - The structural plans indicate that they are designed to the requirements of the 2000 IBC. We are currently under the 2003 IBC.
Correction

Codes Administration - 2003 IPC 609.6 - Clinical, hydortherapeutic and radiological equipment. All clinical, hydrotherapeutic and radiological or any equipment that is supplied with water or that discharges to the waste system shall conform to the requirements of this section and Section 608.
Correction

Codes Administration - Specifications for the mechanical, electrical and plumbing systems have not been provided.
Correction

Codes Administration - The mechanical plans show a unducted return air grill in the foyer. This grill dumps into the surgical suite which has a ducted system and the air is not able to return to the supply system.
Correction

Codes Administration - 2003 IFC 3006.4 - Medical gas systems. Medical gas systems including, but not limited to distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter.
Correction

Codes Administration - 2003 IMC 607.4 - Access and identification. Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 0.5 inch (12.7 mm) in height reading: SMOKE DAMPER OR FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ANSI A117.1-1998 804.7.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer space 54 inches maximum above the floor or ground. The clear floor or ground space shall be positioned for a parallel approach to the space dedicated to a refrigerator/freezer with the centerline of the clear floor or ground space offset 24 inches maximum from the centerline of the dedicated space.
Correction

CA - ANSI A117.1-1998 406.4 - Sides of Curb Ramps. Where pedestrians must walk across a curb ramp, the ramp shall have flared sides. Slope of flares shall not be steeper than 1:10. Where the width of the walking surface at the top of the ramp and parrellel to the run of the ramp is less than 48 inches (1220 mm) wide, the flared sides shall have a slope not steeper than 1:12. Curb ramps and returned curbs shall be permitted where pedestrians would not normally walk across the ramp.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 302.1.1 - Incidental use areas. Spaces which are incidental to the main occupancy shall be separated or protected, or both, in accordance with Table 302.1.1 or the building shall be classified as a mixed occupancy and comply with Section 302.3. Areas that are incidental to the main occupancy shall be classified in accordance with the main occupancy of the portion of the building in which the incidental use area is located.
Correction

Fire Department- Provide specifications for the generator.
Correction

Fire Department- IFC 3006.2.1 Medical Gas Storage Rooms-One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire.
Correction

Fire Department- The fire main and backflow shall be a minimum of 6" up to the fire hydrant.
Correction

Fire Department- The use of the space is better defined as an I-2 occupancy and not a B occupancy.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO Chapter 7, Section 7-803 - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following; Exception: The Building Official may approve a decreased R-value for building exterior walls provided the space is not occupied by employees and is associated with storage/warehouse or manufactoring. a) Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or openings or approved penetrations nor does it apply to unfinished basement concrete walls. b) Floor assemblies forming portions of a building envelope shall meet or exceed a R factor rating of 19. Exception: Concrete floor in contact with the earth need not be insulated. c) Roof assemblies forming portions of a building envelope shall meet or exceed an R factor of 19.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and an smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $2,344.12 $2,344.12 Paid 06/19/2006
89 Sewer Tap Fees $720.00 $720.00 Paid 06/19/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection - Commercial Request Complete 6/21/2006 6/21/2006 06/21/2006
Gas Service Inspection - Commercial Passed 09/19/2006
Correction
Resolved
09/19/2006
Gas Test Pressure (IRC) # OF DEVICES UNKNOWN - NO ACCESS TO ROOF
Gas Piping Inspection - Commercial Partial 09/19/2006
Correction
Partial Correction
09/19/2006
None PIPING FROM EXTERIOR ENTRY TO PENETRATION THRU ROOF APPROVED. ROOF PIPING NOT INSPECTED. PROVIDE ACCESS AND SCHEDULE INSPECTION.
All Rough Inspection - Commercial Not Ready 09/26/2006
Correction
Corrective Action Required
09/26/2006
APPROVED DRAWINGS APPROVED DRAWINGS MUST BE ON SITE FOR ALL INSPECTIONS
All Rough Inspection - Commercial Failed 09/27/2006
Correction
Partial Correction
09/27/2006
None OK TO INSULATE COLD WALLS - DO NOT ROCK
Correction
Corrective Action Required
09/27/2006
Water/DWV Preotection Against Physical Damage (IRC) DWV IS NOT READY - PROTECTIVE PLATES ARE NOT YET INSTALLED THROUGHOUT
Correction
Corrective Action Required
09/27/2006
Unused Openings (IRC) WIRE HAS YET TO BE RUN FOR LIGHTING SERVING LIGHTS ON WEST SIDE OF ENTRY RM 101
Correction
Resolved
09/27/2006
APPROVED DRAWINGS APPROVED DRAWINGS MUST BE ON SITE FOR ALL INSPECTIONS
Driveway Inspection Passed 09/28/2006
All Rough Inspection - Commercial Passed 09/29/2006
Correction
Resolved
09/29/2006
None OK TO INSULATE OK TO ROCK
Correction
Resolved
09/29/2006
Water/DWV Preotection Against Physical Damage (IRC)
Correction
Resolved
09/29/2006
Unused Openings (IRC)
Underground Electrical Inspection - Commercial Passed 10/09/2006
Correction
Resolved
10/09/2006
LIGHT POLE BASES
Rated Assembly Inspection Not Ready 10/26/2006
Correction
Corrective Action Required
10/26/2006
NOT READY FOR INSPECTION COMPLETE ROCK AND SCREWS. PROVIDE INFORMATION AS TO WHAT SCREW PATTERN IS REQUIRED.
Rated Assembly Inspection Not Ready 10/30/2006
Correction
Corrective Action Required
10/30/2006
NOT READY FOR INSPECTION COMPLETE ROCK AND SCREWS.
Rated Assembly Inspection Passed 11/01/2006
Correction
Resolved
11/01/2006
NOT READY FOR INSPECTION FIRE RATED WALL APPROVED PER PLANS
Erosion Control Inspection Residential Failed 11/01/2006
Correction
Corrective Action Required
11/01/2006
Erosion Control PROVIDE SILT FENCE 2 DAYS TO COMPLY
Electrical Service Inspection Failed 11/02/2006
Correction
Corrective Action Required
11/02/2006
System Service Ground (IRC) FULL SIZE GROUND WIRE MUST RUN CONTINUOUS AND UNINTERRUPTED FROM MAIN SOURCES OF DISCONNECT TO WATER SERVICE ENTRY. BUILDING STEEL NOT ACCEPTABLE AS SYSTEM SERVICE GROUND.
Erosion Control Inspection Residential Failed 11/02/2006
Correction
Corrective Action Required
11/02/2006
Erosion Control PROVIDE SILT FENCE NO FURTHER INSPECTIONS UNTIL COMPLIANT 2ND NOTICE
Electrical Service Inspection Passed 11/06/2006
Correction
Resolved
11/06/2006
System Service Ground (IRC) RELEASE SERVICE
Erosion Control Inspection Residential Failed 12/07/2006
Correction
Corrective Action Required
12/07/2006
Erosion Control PROVIDE SILT FENCE NO FURTHER INSPECTIONS UNTIL COMPLIANT 3RD NOTICE
Above Ceiling Inspection Failed 12/07/2006
Correction
Corrective Action Required
12/07/2006
MECHANICAL 1- COMPLETE INSTALLAITON OF DIFFUSERS/GRILLES 2- PROVIDE ACCESS DOORS TO ALL FIRE DAMPERS. 3- PROVIDE FIRE DAMPER LABELS. MIN. 1/2" HIGH, RED. NOTE: OK TO INSTALL TILES CONTINGENT UPON LEAVING ALL FIRE DAMPERS EXPOSED FOR INSPECTION THROUGHOUT
Above Ceiling Inspection Passed 12/20/2006
Correction
Resolved
12/20/2006
MECHANICAL
Occupancy Inspection - Codes Commercial Failed 12/20/2006
Correction
Corrective Action Required
12/20/2006
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/20/2006
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/20/2006
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/20/2006
Required Inspections PROVIDE SPRINKLER PERMIT
Correction
Corrective Action Required
12/20/2006
EXPOSED CONDUCTORS COMPLETE TRANSFORMER WIRING AND PROVIDE COVER ROOM 143
Correction
Corrective Action Required
12/20/2006
OVERCURRENT PROTECTION 1- BREAKERS SERVING ROOFTOP UNITS MUST MATCH NAMEPLATE DATA. PROVIDE INFORMATION ON LARGEST UNIT IF OTHER THAN 100 AMP BREAKER. (NO MINIMUM LISTED) 2- LABEL ALL ROOFTOP UNITS ROOF & ELEC. ROOMS
Correction
Corrective Action Required
12/20/2006
SERVICE CLEARANCE & REQUIRED RECEPTACLES 1- DISC. SWITCH SERVING LARGEST RTU HAS INADEQUATE CLEARANCE. 2- PROVIDE SERVICE CLEARANCE INFORMATION FOR LARGEST RTU. 3- GFCI RECEPTACLE REQUIRED WITHIN 25' OF ANY SERVICABLE EQUIPMENT. Roof
Correction
Corrective Action Required
12/20/2006
None DO NOT OCCUPY
Correction
Corrective Action Required
12/20/2006
Receive Fire Department approval UNDER SEPARATE COVER
Erosion Control Inspection Residential Passed 12/20/2006
Correction
Resolved
12/20/2006
Erosion Control
Gas Piping Inspection - Commercial Passed 12/20/2006
Correction
Resolved
12/20/2006
None
Occupancy Inspection - Codes Commercial Failed 12/28/2006
Correction
Corrective Action Required
12/28/2006
None OK TO FURNISH AND STOCK DO NOT OCCUPY
Correction
Resolved
12/28/2006
SERVICE CLEARANCE & REQUIRED RECEPTACLES Roof
Correction
Corrective Action Required
12/28/2006
OVERCURRENT PROTECTION 1- PROVIDE INFORMATION ON LARGEST UNIT IF OTHER THAN 100 AMP BREAKER. (NO MINIMUM LISTED) ROOF & ELEC. ROOMS
Correction
Resolved
12/28/2006
EXPOSED CONDUCTORS
Correction
Corrective Action Required
12/28/2006
Required Inspections PROVIDE SPRINKLER PERMIT WATER SERVICE NOT INSPECTED.
Correction
Resolved
12/28/2006
Receive Water Utilities Approval
Correction
Resolved
12/28/2006
Receive Fire Department approval
Occupancy Inspection - Codes Commercial Failed 01/18/2007
Correction
Resolved
01/18/2007
Required Inspections
Correction
Resolved
01/18/2007
OVERCURRENT PROTECTION
Correction
Partial Correction
01/18/2007
None 30 DAY TCO
Water Service Inspection Passed 01/18/2007
Occupancy Inspection - Codes Commercial Failed 02/06/2007
Correction
Resolved
02/06/2007
Receive Public Works Approval Approved per Public Works UNDER SEPARATE COVER
Occupancy Inspection - Codes Commercial Passed 02/13/2007
Correction
Resolved
02/13/2007
Receive Planning & Development Approval
Correction
Resolved
02/13/2007
None
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home