Permit Application Status

B0600200


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600200
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF TENANT
02/16/2006
06/20/2006
12/17/2006
01/31/2007
Locations
Contacts
EMALINE BALLROOM, Address:115 SW 3RD ST  
GUY GRONBERG ARCHITECTS, PC, Address:PO BOX 2024  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/17/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 302.1.1.1 - Separation. Where Table 302.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separated fron the remainder of the building with a fire barrier. Where Table 302.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidential use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend fron the floor to the underside of the fire-resistance-rated floor/ceiling assembly or fire-resistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

Fire Department- IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- [M] IFC 610.2 Where required.AType I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. 
Correction

Codes Administration - The project cost has not been provided.
Correction

Codes Administration - Plans for the deck including must be provided prior to construction of the deck.
Correction

Codes Administration - Plans for the fire line from the main to the structure have not been provided.
Correction

Codes Administration - Information has not been provided for the construction of the platform.
Correction

Codes Administration - I am unable to locate information for the construction of the new interior walls.
Correction

Codes Administration - I am unable to locate information regarding auxilary and secondary drain systems as required by Section 307.2.3 of the 2003 IMC.
Correction

Codes Administration - I am unable to locate information about the fixures and/or equipment for the plumbing.
Correction

Fire Department- IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Correction

Codes Administration - 2002 NEC 210.63 - Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disonnecting means.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IMC 507.2.3 - Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes in accordance with Sections 507.2, 507.2.1 and 507.2.2.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Lee's Summit Code of Ordinances, Section 17-6.D - Regulated smoking environments classified. No persons with ownership, management, or control of a food service establishment shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, eith primary lettering of not less than one inch in height according to one of the following classifications of food service establishments: 1. Smoke-free establishment (existing and new establishments) 2. Smoking establishment (existing establishments only) 3. Mixed smoking/non-smoking establishment (existing establishments only) 4. Smoking restricted establishment (existing and new establishments)
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $487.18 $487.18 Paid 06/20/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Partial 08/02/2006
Correction
Partial Correction
08/02/2006
ELECTRICAL SERVICE INSTALLATION PROTECT ENTRY CABLE FROM PENETRATION @ CAVITY OF EAST EXTERIOR WALL. SECURE GROUNDING ELECTRODE CONDUCTOR CONDUIT TO BASEMENT WALL. 400 AMP MAIN DISCONNECT RELEASE SERVICE
All Rough Inspection - Commercial Not Ready 08/02/2006
Correction
Corrective Action Required
08/02/2006
WALL FRAMING + IN-WALL SYSTEMS CONNECT EQUIPMENT GROUND CONDUCTORS AT BOXES WITH LISTED WIRE NUT OR CRIMP CONNECTOR; KEEP NM CABLE >= 1-1/4" FROM FACE OF STUDS & PLATES -- OR PROTECT; SECURE NM CABLE WITHIN 8" OF NM BOXES ELECTRICAL ONLY SPACES 108-111
All Rough Inspection - Commercial Failed 09/05/2006
Correction
Corrective Action Required
09/05/2006
WALL FRAMING + IN-WALL SYSTEMS CONNECT EQUIPMENT GROUND CONDUCTORS AT BOXES WITH LISTED WIRE NUT OR CRIMP CONNECTOR; KEEP NM CABLE >= 1-1/4" FROM FACE OF STUDS & PLATES -- OR PROTECT; SECURE NM CABLE WITHIN 8" OF NM BOXES ELECTRICAL ONLY SPACES 108-111
Correction
Corrective Action Required
09/05/2006
Premises Identification (IRC) PROVIDE ADDRESS
Correction
Corrective Action Required
09/05/2006
Junction Box Required (IRC) OUTLET BOX AT DOORWAY - FILL COUNT IS AT 24.75- MAX HANDY BOX FILL ACCORDING TO NEC IS 18.0 RM # 108, 109
Correction
Corrective Action Required
09/05/2006
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE ADEQUATE PLUMBING PROTECTIVE PLATES THROUGHOUT
Correction
Corrective Action Required
09/05/2006
Cleanout Accessibility (IRC) PROVIDE A CLEANOUT ON VENT SIDE OF LOOP VENT SERVING ROOM RM #110
All Rough Inspection - Commercial Failed 09/06/2006
Correction
Resolved
09/06/2006
WALL FRAMING + IN-WALL SYSTEMS
Correction
Resolved
09/06/2006
Premises Identification (IRC)
Correction
Corrective Action Required
09/06/2006
Junction Box Required (IRC) OUTLET BOX AT DOORWAY - FILL COUNT IS AT 24.75- MAX HANDY BOX FILL ACCORDING TO NEC IS 18.0 NOTE:WILL BE REMOVED AND CHANGED. RM # 108, 109
Correction
Resolved
09/06/2006
Water/DWV Preotection Against Physical Damage (IRC)
Correction
Resolved
09/06/2006
Cleanout Accessibility (IRC)
All Rough Inspection - Commercial Partial 09/22/2006
Correction
Corrective Action Required
09/22/2006
Junction Box Required (IRC) OUTLET BOX AT DOORWAY - FILL COUNT IS AT 24.75- MAX HANDY BOX FILL ACCORDING TO NEC IS 18.0 NOTE:WILL BE REMOVED AND CHANGED. RM # 108, 109
Correction
Resolved
09/22/2006
FRAMING AT NEW DOOR OPENING @ WEST WALL OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 09/25/2006
Rough Electrical Inspection - Commercial Failed 09/29/2006
Correction
Corrective Action Required
09/29/2006
EXISTING ELECTRICAL WORK IN ATTIC DISCUSSED W/ BRAD COX W/O 9/25/06 WIRING NON-COMPLIANT SECURING, PROTECTION...
Rough Electrical Inspection - Commercial Failed 10/17/2006
Correction
Corrective Action Required
10/17/2006
EXISTING ELECTRICAL WORK IN ATTIC DISCUSSED W/ BRAD COX W/O 9/25/06. INSPECTED W/ NORM OF CIMMERON ELECTRIC 10/17/06. WIRING NON-COMPLIANT SECURING, PROTECTION...
Gas Piping Inspection - Commercial Passed 10/26/2006
Gas Service Inspection - Commercial Not Ready 10/26/2006
Correction
Corrective Action Required
10/26/2006
TEST PRESSURE LEVEL PRESSURIZE SYSTEM TO HOLD STEADY AT OR ABOVE MINIMUM 10 PSI BELOW REQUIRED MINIMUM BOTH FEEDER LINES
Gas Service Inspection - Commercial Passed 10/30/2006
Correction
Resolved
10/30/2006
TEST PRESSURE LEVEL BELOW REQUIRED MINIMUM BOTH FEEDER LINES
Correction
Resolved
10/30/2006
None GAS APPROVED FOR 3 RD ST ADDRESS. 1 INCH PIPE TEST PRESSURE 12 PSI. 2 INCH PIPE TEST PRESSURE 10 PSI. RELEASE GAS
Electrical Service Inspection Passed 11/14/2006
Correction
Resolved
11/14/2006
ELECTRICAL SERVICE INSTALLATION
Rough Electrical Inspection - Commercial Passed 11/14/2006
Correction
Resolved
11/14/2006
EXISTING ELECTRICAL WORK IN ATTIC
All Rough Inspection - Commercial Passed 11/14/2006
Correction
Resolved
11/14/2006
WALL FRAMING + IN-WALL SYSTEMS
Correction
Resolved
11/14/2006
Premises Identification (IRC)
Correction
Resolved
11/14/2006
Junction Box Required (IRC)
Correction
Resolved
11/14/2006
Water/DWV Preotection Against Physical Damage (IRC)
Correction
Resolved
11/14/2006
Cleanout Accessibility (IRC)
Correction
Resolved
11/14/2006
FRAMING AT NEW DOOR OPENING @ WEST WALL
Occupancy Inspection - Codes Commercial Failed 11/20/2006
Correction
Resolved
11/20/2006
Receive Fire Department approval PER J DIR 11/20/06 NO PROHIBITIVE ISSUES
Correction
Corrective Action Required
11/20/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
11/20/2006
Receive Public Works Approval
Correction
Corrective Action Required
11/20/2006
Receive Water Utilities Approval
Correction
Corrective Action Required
11/20/2006
WATER CLOSET SEATS IPC 420.3 NOT COMMERCIAL TYPE WITH OPEN FRONT
Correction
Corrective Action Required
11/20/2006
ELECTRICAL PANEL SCHEDULES NEC 110-22; 384-13 TO BE COMPLETED SERVICE PANELS
Correction
Corrective Action Required
11/20/2006
SECURING/SUPPORT OF NM ELECTRICAL CABLE NEC 336-18; IRC E3702.1: WITHIN 8" OF BOXES; THEN 4.5' MAX INTERVALS ABOVE ELECT SVC PANELS + MECH 105 EAST WALL
Correction
Corrective Action Required
11/20/2006
ELECTRICAL RECEPTACLE/SWITCH FACE PLATES NOT IN PLACE STOR 109
Correction
Corrective Action Required
11/20/2006
ANTI-TIPPING DEVICE @ KITCHEN RANGE NOT FOUND IN PLACE SEE MFGR'S INSTRUCTIONS
Correction
Corrective Action Required
11/20/2006
ELECT RECEPTACLES @ CATERING 111 EAST WALL ONE NOT GFCI PROTECTED ONE OBSTRUCTED
Correction
Corrective Action Required
11/20/2006
FIRE SEPARATION AT LOWER LEVEL INSPECTOR TO ADVISE
Gas Service Inspection - Commercial Failed 11/20/2006
Correction
Corrective Action Required
11/20/2006
EXISTING GAS PIPING RUN IN RETURN AIR PLENUM MUST BE RELOCATED PRESSURE RE-TEST REQUIRED
Occupancy Inspection - Codes Commercial Failed 11/22/2006
Correction
Resolved
11/22/2006
WATER CLOSET SEATS
Correction
Resolved
11/22/2006
SECURING/SUPPORT OF NM ELECTRICAL CABLE
Correction
Corrective Action Required
11/22/2006
ELECTRICAL RECEPTACLE/SWITCH FACE PLATES ONE NOT IN PLACE STOR 109
Correction
Corrective Action Required
11/22/2006
ELECT RECEPTACLES @ CATERING 111 EAST WALL ONE LEFT OF TRIPLE SINK NOT TIGHT TO WALL/BOX
Correction
Corrective Action Required
11/22/2006
FIRE SEPARATION AT LOWER LEVEL SPACE MUST BE FULLY DRYWALLED ACCESSIBLE ENCLOSED SPACE UNDER STAIR
Gas Service Inspection - Commercial Failed 11/22/2006
Correction
Resolved
11/22/2006
TEST PRESSURE LEVEL INITIAL TEST SUPERCEDED
Correction
Resolved
11/22/2006
None INITIAL TEST SUPERCEDED
Correction
Corrective Action Required
11/22/2006
EXISTING GAS PIPING RUN IN RETURN AIR PLENUM PRESSURE TEST 11/22/06 DID NOT PASS -- LOST PRESSURE OVER 15 MIN MONITOR PERIOD NOW RELOCATED PRESSURE RE-TEST REQUIRED
Gas Service Inspection - Commercial Not Ready 11/28/2006
Correction
Corrective Action Required
11/28/2006
READINESS FOR INSPECTION IBC 109.1, 109.5: NOT READY. CALL FOR INSPECTION WHEN INSTALLATION IS ACCESSIBLE FOR INSPECTION. PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
Occupancy Inspection - Codes Commercial Failed 11/28/2006
Correction
Resolved
11/28/2006
Receive Water Utilities Approval PER BEN HASKAMP 11/28/06
Occupancy Inspection - Codes Commercial Failed 11/29/2006
Correction
Resolved
11/29/2006
ELECTRICAL RECEPTACLE/SWITCH FACE PLATES
Correction
Resolved
11/29/2006
ANTI-TIPPING DEVICE @ KITCHEN RANGE
Correction
Resolved
11/29/2006
ELECT RECEPTACLES @ CATERING 111 EAST WALL
Correction
Corrective Action Required
11/29/2006
FIRE SEPARATION AT LOWER LEVEL COMPLETE DRYWALL SURFACE AT UNDERSIDE OF BOTH FLIGHTS OF STAIR. ACCESSIBLE ENCLOSED SPACE UNDER STAIR
Gas Service Inspection - Commercial Passed 11/29/2006
Correction
Resolved
11/29/2006
TEST PRESSURE LEVEL TEST PRESSURE LEVEL HELD STEADY AT >= 10 PSI FOR >=20 MIN. RELEASE GAS SERVICE. RE-TEST AFTER RE-ROUTING OF PIPE FROM HVAC PLENUM
Correction
Resolved
11/29/2006
None
Correction
Resolved
11/29/2006
EXISTING GAS PIPING RUN IN RETURN AIR PLENUM NOW RELOCATED
Correction
Resolved
11/29/2006
READINESS FOR INSPECTION
Occupancy Inspection - Codes Commercial Failed 01/04/2007
Correction
Resolved
01/04/2007
Receive Planning & Development Approval NO ISSUES PRESENTED AS OF 1/4/07
Correction
Resolved
01/04/2007
Receive Public Works Approval NO ISSUES PRESENTED AS OF 1/4/07
Occupancy Inspection - Codes Commercial Passed 01/29/2007
Correction
Resolved
01/29/2007
ELECTRICAL PANEL SCHEDULES
Correction
Resolved
01/29/2007
FIRE SEPARATION AT LOWER LEVEL ACCESSIBLE ENCLOSED SPACE UNDER STAIR
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home