Permit Application Status

B0600165


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600165
Building Permit - Commercial
Certificate of Occupancy
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT
ADDITION COMMERCIAL
ADDITION
02/07/2006
03/23/2006
09/19/2006
11/02/2006
Locations
Contacts
INTERNATIONAL ARCHITECTS, Address:912 BROADWAY SUITE 300  
LYTLE CONSTRUCTION INC, Address:1051 SE BROADWAY DR  
ABUNDANT LIFE BAPTIST CHURCH OF LEES SUMMIT, Address:414 SW PERSELS RD, Phone:(816) 554-8181  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/18/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Fire Department- IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-1300.
Correction

Fire Department- IFC 1003.2.10.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- What type of seating is being used in the theater and what is the occupant load?
Correction

Codes Administration - The finish schedule mentions a flocked wall covering but additional information explaining what exactly that is is not provided.
Correction

Codes Administration - The plans show fire-treated wood trusses are to be used in the roof assembly but Type II-B does not allow for wood construction.
Correction

Codes Administration - Wood flooring is shown in theater room for the seating area. Wood is not an allowable material in this type of construction.
Correction

Codes Administration - The door schedule indicates that doors 201 and 216B are to be 90 minute rated but the plans do not indicate any fire-rated assemblies.
Correction

Codes Administration - I am unable to locate information on the door hardware to be used.
Correction

Codes Administration - I am unable to locate information on the design of the precast hollow-core planks.
Correction

Codes Administration - I am unable to locate plumbing plans for the roof drains.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $5,981.58 $5,981.58 Paid 03/23/2006
89 Sewer Tap Fees $1,290.00 $1,290.00 Paid 03/23/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Failed 05/25/2006
Correction
Corrective Action Required
05/25/2006
ELECTRICAL WIRING PROTECTED FROM PHYSICAL DAMAGE WHERE ELECTRICAL WIRING IS LESS THAN 1-1/4" FROM STUD FACE PROVIDE NAIL PLATE PROTECTION THROUGHOUT
Correction
Corrective Action Required
05/25/2006
Metal Boxes (grounding) (IRC) ENSURE THAT METEL BOXES ARE EFFECTIVELY BONDED THROUGHOUT SPOT CHECK
Correction
Corrective Action Required
05/25/2006
INSTALLATION PER MANUFACTUERS INSTRUCTIONS REQUESTING THAT IN THESE LOCATIONS UPON APPROVAL OF DRYWALL ONLY ONE SIDE SHALL BE INSTALLED TO INSPECT INSTALLATION OF HEATING DEVICE RMS 100 & 200 WALL HEATER UNITS
Rough Plumbing Inspection - Commercial Failed 05/25/2006
Correction
Corrective Action Required
05/25/2006
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE NAIL PROTECTION PLATE WHERE DWV IS LESS THAN 1-1/2" FROM STUD FACE THROUGHOUT
Correction
Corrective Action Required
05/25/2006
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE PROTECTIVE NAIL PLATES WHERE WATER PIPING IS LESS THAN 1-1/2" FROM STUD FACE THROUGHOUT
Rough Electrical Inspection - Commercial Passed 05/30/2006
Correction
Resolved
05/30/2006
ELECTRICAL WIRING PROTECTED FROM PHYSICAL DAMAGE WHERE ELECTRICAL WIRING IS LESS THAN 1-1/4" FROM STUD FACE PROVIDE NAIL PLATE PROTECTION THROUGHOUT
Correction
Resolved
05/30/2006
Metal Boxes (grounding) (IRC) ENSURE THAT METEL BOXES ARE EFFECTIVELY BONDED THROUGHOUT SPOT CHECK
Correction
Resolved
05/30/2006
INSTALLATION PER MANUFACTUERS INSTRUCTIONS REQUESTING THAT IN THESE LOCATIONS UPON APPROVAL OF DRYWALL ONLY ONE SIDE SHALL BE INSTALLED TO INSPECT INSTALLATION OF HEATING DEVICE RMS 100 & 200 WALL HEATER UNITS
All Rough Inspection - Commercial Partial 05/30/2006
Correction
Partial Correction
05/30/2006
None REQUESTING TO SEE PVC WRAPPING TO ENSURE INTEGRITY OF RETURN AIR CONDITIONS - OK TO COVER ONE SIDE OF WALL - AS LONG AS IT DOES NOT INTERFERE W/ NEXT INSPECTION
Rough Plumbing Inspection - Commercial Passed 05/30/2006
Correction
Resolved
05/30/2006
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE NAIL PROTECTION PLATE WHERE DWV IS LESS THAN 1-1/2" FROM STUD FACE THROUGHOUT
Correction
Resolved
05/30/2006
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE PROTECTIVE NAIL PLATES WHERE WATER PIPING IS LESS THAN 1-1/2" FROM STUD FACE THROUGHOUT
Above Ceiling Inspection Partial 06/01/2006
Correction
Partial Correction
06/01/2006
PLUMBING PIPES APPROVED FASTENING AND SUPPORT OF PIPES - OK TO COVER W/ PIPE WRAP Basement
All Rough Inspection - Commercial Passed 06/08/2006
Correction
Resolved
06/08/2006
None REQUESTING TO SEE PVC WRAPPING TO ENSURE INTEGRITY OF RETURN AIR CONDITIONS - OK TO COVER
Gas Piping Inspection - Commercial Passed 07/10/2006
Gas Service Inspection - Commercial Passed 07/10/2006
Above Ceiling Inspection Partial 07/12/2006
Correction
Partial Correction
07/12/2006
PLUMBING PIPES APPROVED FASTENING AND SUPPORT OF PIPES - OK TO COVER W/ PIPE WRAP Basement
Correction
Corrective Action Required
07/12/2006
MECHANICAL 2 MECHANICAL DUCTS HAVE YET TO BE INSTALLED - AS WELL AS CEILING GRID BETWEEN RMS 108-110
Correction
Corrective Action Required
07/12/2006
WALL FINISH PAPER FACED INSULATION IS NOT ALLOWED AS WALL FINISH? EXTERIOR WALLS
Correction
Partial Correction
07/12/2006
None OK TO COVER - 2ND FLOOR ONLY - EXCLUDES HIGHER CEILING AT (S1) AND ABOVE MENTIONED AREAS - RMS 108-110 (MECHANICAL AREA) AND AROUND EXTERIOR WALLS FOR WALL FINISH
Above Ceiling Inspection Partial 07/20/2006
Correction
Resolved
07/20/2006
MECHANICAL
Correction
Resolved
07/20/2006
WALL FINISH
Correction
Resolved
07/20/2006
None
Correction
Partial Correction
07/20/2006
2ND FLOOR CEILING FRAMING + ABOVE-CEILING SYSTEMS 2 MECHANICAL DUCTS HAVE YET TO BE INSTALLED - AS WELL AS CEILING GRID OK TO COVER WHEN READY EXCEPT BETWEEN RMS208-210
Correction
Resolved
07/20/2006
1ST FLOOR CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Not Ready 07/20/2006
Correction
Partial Correction
07/20/2006
OWNER STORAGE OF FURNITURE IN RM 215 OK EXCEPT 2' @ PERIMETER AT OWNER'S RISK
Occupancy Inspection - Codes Commercial Failed 08/10/2006
Correction
Corrective Action Required
08/10/2006
DOOR CLOSING SPEED EXIT DOORS - CLOSING SPEED FROM 90 DEGREES TO 12 DEGREES IS REQUIRED TO TAKE 5 SECONDS THROUGHOUT
Correction
Corrective Action Required
08/10/2006
Unused Openings (IRC) FINISH FLOOR OUTLETS RM 211
Correction
Corrective Action Required
08/10/2006
ADA GUARDS LAVATORY'S REQUIRE GUARDS AT PLUMBING RM 212
Correction
Corrective Action Required
08/10/2006
Receive Planning & Development Approval SEE SEPERATE COVER
Correction
Corrective Action Required
08/10/2006
Receive Public Works Approval SEE SEPERATE COVER
Correction
Resolved
08/10/2006
Receive Water Utilities Approval RECIEVED VERBAL OK
Correction
Resolved
08/10/2006
Receive Fire Department approval RECIEVED VERBAL OK
Correction
Corrective Action Required
08/10/2006
ADA PARKING ACCESSIBLE PARKING - MARKING = OWNER IS TAKING RESPONSIBILITY EXTERIOR
Correction
Corrective Action Required
08/10/2006
None FLOOR FINISH REQUIRED PRIOR TO C OF O
Above Ceiling Inspection Passed 08/10/2006
Correction
Resolved
08/10/2006
PLUMBING PIPES APPROVED FASTENING AND SUPPORT OF PIPES - OK TO COVER W/ PIPE WRAP Basement
Correction
Resolved
08/10/2006
2ND FLOOR CEILING FRAMING + ABOVE-CEILING SYSTEMS 2 MECHANICAL DUCTS HAVE YET TO BE INSTALLED - AS WELL AS CEILING GRID OK TO COVER WHEN READY EXCEPT BETWEEN RMS208-210
Occupancy Inspection - Codes Commercial Failed 08/11/2006
Correction
Resolved
08/11/2006
OWNER STORAGE OF FURNITURE IN RM 215 OK EXCEPT 2' @ PERIMETER AT OWNER'S RISK
Correction
Resolved
08/11/2006
Unused Openings (IRC) FINISH FLOOR OUTLETS RM 211
Correction
Resolved
08/11/2006
ADA GUARDS LAVATORY'S REQUIRE GUARDS AT PLUMBING RM 212
Correction
Partial Correction
08/11/2006
Receive Planning & Development Approval SEE SEPERATE COVER - APPROVED FOR TCO
Correction
Corrective Action Required
08/11/2006
ADA PARKING ACCESSIBLE PARKING - MARKING = OWNER IS TAKING RESPONSIBILITY EXTERIOR
Correction
Corrective Action Required
08/11/2006
None FLOOR FINISH REQUIRED PRIOR TO C OF O
Correction
Partial Correction
08/11/2006
None 30 DAY TCO
Occupancy Inspection - Codes Commercial Failed 08/24/2006
Correction
Resolved
08/24/2006
DOOR CLOSING SPEED EXIT DOORS - CLOSING SPEED FROM 90 DEGREES TO 12 DEGREES IS REQUIRED TO TAKE 5 SECONDS THROUGHOUT
Correction
Resolved
08/24/2006
Receive Planning & Development Approval SEE SEPERATE COVER - APPROVED FOR TCO
Correction
Resolved
08/24/2006
Receive Public Works Approval SEE SEPERATE COVER
Correction
Resolved
08/24/2006
ADA PARKING ACCESSIBLE PARKING - MARKING = OWNER IS TAKING RESPONSIBILITY EXTERIOR
Correction
Partial Correction
08/24/2006
None 60 DAY TCO
Occupancy Inspection - Codes Commercial Passed 11/01/2006
Correction
Resolved
11/01/2006
None
Correction
Resolved
11/01/2006
None
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home