Permit Application Status

B0600027


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0600027
Building Permit - Commercial
Certificate of Occupancy
MALOUFF JAMES M III
REPAIR REPLACE UPGRADE
FIRE REPAIR /SHEETROCK
01/06/2006
01/06/2006
07/05/2006
08/01/2006
Locations
Contacts
RE'BILL'DERS, INC, Address:12201 WEST 150TH CIRCLE  
MALOUFF JAMES M III, Address:1204 ROMANY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/28/2007 10/29/2010
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Any deviation from the approved plans shall be approved by the City of Lee's Summit. This shall include but is not limited to building layout, facilities provided, building materials and equipment, finishes used, landscaping and site improvements. Information about the changes shall be submitted to the Codes Administration Department for review and a determination will be provided within five (5) working days.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $65.10 $65.10 Paid 01/06/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Commercial Not Ready 01/12/2006
Correction
Partial Correction
01/12/2006
PROXIMITY OF VANITY TO WATER CLOSET & TUB OK TO RETAIN EXISTING DIMENSIONS / CLEARANCE
All Rough Inspection - Commercial Not Ready 01/24/2006
Correction
Partial Correction
01/24/2006
ROUGH ELECTRICAL WORK WHEN ALL TRADES ARE READY FOR INSPECTION, CONTACT CODES ADMINISTRATION AND REQUEST ALL-ROUGH INSPECTION. REQUESTED FOR INSPECTION 1/24/06 ELECT ONLY OK
All Rough Inspection - Commercial Failed 02/02/2006
Correction
Resolved
02/02/2006
ROUGH ELECTRICAL WORK
Correction
Corrective Action Required
02/02/2006
PROTECTION OF COPPER & PVC PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES AT STUDS & PLATES. AT DOUBLE TOP PLATES PLACE PROTECTION AT BOTH TOP & BOTTOM MEMBERS. CHECK ALL < 1-1/2" FROM FACE OF STUD / PLATE
Electrical Service Inspection Failed 02/02/2006
Correction
Corrective Action Required
02/02/2006
PANEL WIRING GROUND/NEUTRAL BUSES NOT ISOLATED
Electrical Service Inspection Failed 02/06/2006
All Rough Inspection - Commercial Passed 02/06/2006
Correction
Resolved
02/06/2006
PROTECTION OF COPPER & PVC PIPING
Electrical Service Inspection Passed 02/07/2006
Correction
Resolved
02/07/2006
PANEL WIRING
Correction
Resolved
02/07/2006
ELECTRICAL SERVICE ENTRY + PANEL RELEASE SERVICE REMOTE DISCONNECT 100 AMP
Occupancy Inspection - Codes Commercial Failed 07/21/2006
Correction
Resolved
07/21/2006
PROXIMITY OF VANITY TO WATER CLOSET & TUB
Correction
Corrective Action Required
07/21/2006
Premises Identification (IRC) DISPLAY APARTMENT # AT ENTRANCE
Correction
Corrective Action Required
07/21/2006
ANTI-TIPPING DEVICE @ KITCHEN RANGE SEE MANUFACTURER'S INSTRUCTIONS + HARDWARE PROVIDED IN PLASTIC BAG IN OVEN NOT FOUND IN PLACE
Correction
Corrective Action Required
07/21/2006
GAS FEEDER LINE AT WATER HEATER & FURNACE NOT SECURED TO STRUCTURE TO PREVENT DAMAGE
Correction
Corrective Action Required
07/21/2006
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES IRC E3901.10; E3902.6 <> NEC 380-10; 410-56(f) CHECK ALL SOME NOT TIGHT TO BOX EXAMPLE: LR + BR'S
Correction
Corrective Action Required
07/21/2006
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 110-22; 384-13; IRC E36O6.2. EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. INCOMPLETE SERVICE PANEL
Correction
Corrective Action Required
07/21/2006
CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VA OR 1/8 HP NEC 422.31B: IF NOT WITHIN SIGHT OF PANELBOARD IF TO SERVE AS DISCONNECT MUST BE LOCKABLE
Correction
Corrective Action Required
07/21/2006
OCCUPANCY APPROVAL STATUS IBC 110.1 / IRC R110: PRIOR TO APPROVAL DO NOT OCCUPY NOR PLACE PERSONAL PROPERTY
Correction
Corrective Action Required
07/21/2006
BACKFLOW PREVENTION AT DISHWASHER IRC P2717.2: LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED NOT PROVIDED KITCHEN
Correction
Corrective Action Required
07/21/2006
FURNACE, WATER HEATER VENT DUCT JOINTS EQUALLY SPACED AS POSSIBLE AROUND CIRCUMFERENCE INCOMPLETELY FASTENED 3 SCREWS MINIMUM / JOINT
Occupancy Inspection - Codes Commercial Passed 07/31/2006
Correction
Resolved
07/31/2006
Premises Identification (IRC)
Correction
Resolved
07/31/2006
ANTI-TIPPING DEVICE @ KITCHEN RANGE
Correction
Resolved
07/31/2006
GAS FEEDER LINE AT WATER HEATER & FURNACE SECURE BLOCK TO STRUCTURE
Correction
Resolved
07/31/2006
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES
Correction
Resolved
07/31/2006
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
07/31/2006
CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VA OR 1/8 HP AVAILABLE FOR THIS PANEL ELECT CONTR STATES LOCKOUT HARDWARE NOT
Correction
Resolved
07/31/2006
OCCUPANCY APPROVAL STATUS
Correction
Resolved
07/31/2006
BACKFLOW PREVENTION AT DISHWASHER
Correction
Resolved
07/31/2006
FURNACE, WATER HEATER VENT DUCT JOINTS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home