Permit Application Status

B0502080


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0502080
Building Permit - Commercial
Certificate of Occupancy
THE NORTHWESTERN MUTUAL LIFE INS CO
NEW MULTI-FAMILY
BUILDING G TYPE IV
11/17/2005
10/10/2006
03/11/2008
10/22/2007
Locations
Contacts
AMLI RESIDENTIAL CONSTRUCTION LLC, Address:10800 FARLEY SUITE 304  
CLIFFORD WONG, Address:5757 ALPHA RD SUITE 505  
THE NORTHWESTERN MUTUAL LIFE INS CO, Address:PO BOX 3151  
JVM NEW LONGVIEW LLC, Address:PO BOX 06494  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/27/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1405.3 - Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashing shall be installed at the perimeters of exterior doors and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projecting flanges shall be installed on both sides and the ends of copings, under sills and continuously above projecting trim.
Correction

Codes Administration - 2003 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602.
Correction

Codes Administration - Notes on Sheet D3 are overlapping.
Correction

Codes Administration - I am unable to locate specifications regarding the installation of mechanical, electrical and plumbing systems.
Correction

Codes Administration - I am unable to locate a detail for the water heater and furnace installation.
Correction

Fire Department- IFC 903.3.7 The location of fire department connections shall be approved by the fire code official. Connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant.
Correction

Fire Department- IFC D105.2 Width. Fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm) in the immediate vicinity of any building or portion of building more than 30 feet (9144 mm) in height.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 504.5 - Makeup air. Installations exhausting more than 200 cfm shall be provided with makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of not less than 100 square inches shall be provided in the closet inclosure.
Correction

Codes Administration - 2003 IBC 504.6.1 - Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet from the dryer loction to the outlet terminal. The maximum length of duct shall be reduced 2.5 feet for each 45-degree bend and 5 feet for each 90-degree bend. The maximum length of the exhaust duct does not include the transition duct.
Correction

Codes Adminsitration - 2003 IPC 802.1.6 - Domestic dishwashing machines. Domestic dishwashing machines shall dishcharge indirectly through an air gap or air break into a standpipe or waste receptor in accordance with Section 802.2, or discharge into a wye-branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste grinder. The waste line of a domestic dishwashing machine discharging into a kitchen sink tailpiece or food waste grinder shall connect to a deck-mounted air gap or the waste line shall rise and be securely fastenend to the underside of the sink rim or counter.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $4,685.57 $4,685.57 Paid 10/10/2006
89 Sewer Tap Fees $3,000.00 $3,000.00 Paid 10/10/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Failed 01/10/2007
Correction
Corrective Action Required
01/10/2007
NOT READY WALK THROUGH
All Rough Inspection - Commercial Failed 01/16/2007
Correction
Corrective Action Required
01/16/2007
NOT READY NOT READY
All Rough Inspection - Commercial Partial 01/23/2007
Correction
Resolved
01/23/2007
NOT READY
Correction
Corrective Action Required
01/23/2007
DRAFT STOP SEAL DRAFT STOP PENETRATIONS. THROUGH OUT
Correction
Corrective Action Required
01/23/2007
DRAFT STOP DRAFT STOP REQUIRED AT CEILING OFF SET BETWEEN UNITS/ CEILING OFFSET
Correction
Corrective Action Required
01/23/2007
Roof Ventilation Required (IRC) ROOF VENTS NOT INSTALLED. ROOF
Correction
Corrective Action Required
01/23/2007
Water/DWV Preotection Against Physical Damage (IRC) INSTALL BOCA PLATES ON DWV PIPE. OK INSULATION THROUHGH OUT
Correction
Partial Correction
01/23/2007
None TODAYS INSPECTION 1 - 23 - 07 IS FROM THE STEP DOWN AT THE FOUNDATION SOUTH. THIS AREA IS APPROVED FOR INSULATION.
Electrical Service Inspection Failed 01/23/2007
Correction
Corrective Action Required
01/23/2007
PANEL MAKE UP PANEL 736 A 3 NOT MADE UP.
Rough Framing Inspection - Commercial Passed 01/23/2007
Correction
Resolved
01/23/2007
NOT READY
All Rough Inspection - Commercial Partial 01/25/2007
Correction
Resolved
01/25/2007
DRAFT STOP THROUGH OUT
Correction
Resolved
01/25/2007
DRAFT STOP CEILING OFFSET
Correction
Resolved
01/25/2007
Water/DWV Preotection Against Physical Damage (IRC) THROUHGH OUT
Correction
Resolved
01/25/2007
None OK ROCK
Correction
Corrective Action Required
01/25/2007
Stair Treads and Risers (IRC) STEPS NOT INSTALLED PER PLANS. CORRIDOR CHANGE OF ELEVATION
Electrical Service Inspection Failed 01/25/2007
Correction
Corrective Action Required
01/25/2007
PANEL MAKE UP PANEL 736 A 3 NOT MADE UP.
Erosion Control Inspection Residential Passed 01/25/2007
Erosion Control Inspection Residential Passed 02/08/2007
All Rough Inspection - Commercial Partial 02/08/2007
Correction
Corrective Action Required
02/08/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE SOUTH 4 GARAGES AND THE NORTH GARAGE. APT. 712, 713,714 AND 722. OK TO TAPE OTHER AREAS EXCEPT HALLWAY CEILINGS.
All Rough Inspection - Commercial Partial 02/12/2007
Correction
Corrective Action Required
02/12/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE SOUTH 4 GARAGES AND THE NORTH GARAGE. HALLWAYS - SCREW INSPECTION NOT APPROVED. OK TO TAPE ALL APARTMENTS.
Electrical Service Inspection Failed 03/30/2007
Correction
Corrective Action Required
03/30/2007
NOT READY NOT READY
Electrical Service Inspection Passed 04/02/2007
Correction
Resolved
04/02/2007
PANEL MAKE UP
Correction
Resolved
04/02/2007
NOT READY
Correction
Resolved
04/02/2007
None 2 -800 AMP SERVICES APPROVED. 22 - 100 AMP SERVICE PANELS FOR APT #s 712,713, 714, 715, 716, 718, 721, 722, 723, 724, 725, 726, 727, 728,731, 732, 733, 734, 735, 736,737, 738 AND HOUSE PANEL 3341 SW SENSATION DR. GROUND BREEZWAY 712 AND SPRINKLER ROOM.
Erosion Control Inspection Residential Passed 04/02/2007
All Rough Inspection - Commercial Partial 04/12/2007
Correction
Corrective Action Required
04/12/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE NORTH GARAGE. HALLWAYS - SCREW INSPECTION NOT APPROVED. OK TO TAPE ALL APARTMENTS.
All Rough Inspection - Commercial Partial 04/16/2007
Correction
Corrective Action Required
04/16/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE NORTH GARAGE. SCREW INSPECTION NOT APPROVED. OK TO TAPE ALL APARTMENTS. ALL SHEETROCK JOINTS ARE REQUIRED TO BE TIGHT.
All Rough Inspection - Commercial Partial 04/17/2007
Correction
Corrective Action Required
04/17/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE NORTH GARAGE. SCREW INSPECTION NOT APPROVED. OK TO TAPE ALL APARTMENTS. ALL SHEETROCK JOINTS ARE REQUIRED TO BE TIGHT.
Correction
Corrective Action Required
04/17/2007
Through Penetrations (IRC) SPOT CHECK OF FIRST LAYER OF ROCK AFTER 2 ND. LAYER OF ROCK WAS REMOVED REVEALED SEVERAL AREAS OF ROCK NOT INSTALLED PER PLANS. REMOVE 2 ND. LAYER OF ROCK IN ALL AREAS AND CALL FOR INSPECTION. BREEZWAYS
All Rough Inspection - Commercial Partial 04/18/2007
Correction
Corrective Action Required
04/18/2007
INSPECTION CANCELLED CANCELLED BY DAVID.
All Rough Inspection - Commercial Partial 05/14/2007
Correction
Corrective Action Required
05/14/2007
Roof Ventilation Required (IRC) ROOF VENTS NOT INSTALLED. ROOF
Correction
Resolved
05/14/2007
Stair Treads and Risers (IRC) Corridor CHANGE OF ELEVATION
Correction
Corrective Action Required
05/14/2007
Dwelling Unit Separation (IRC) SCREW INSPECTION APPROVED EXCEPT THE FOLLOWING LOCATIONS. NONE OF THE BALCONIES ARE SHEETROCKED, 3 RD FLOOR HALLWAY, THE NORTH GARAGE. SCREW INSPECTION NOT APPROVED. OK TO TAPE ALL APARTMENTS. ALL SHEETROCK JOINTS ARE REQUIRED TO BE TIGHT.
Correction
Corrective Action Required
05/14/2007
Through Penetrations (IRC) SPOT CHECK OF FIRST LAYER OF ROCK AFTER 2 ND. LAYER OF ROCK WAS REMOVED REVEALED SEVERAL AREAS OF ROCK NOT INSTALLED PER PLANS. REMOVE 2 ND. LAYER OF ROCK IN ALL AREAS AND CALL FOR INSPECTION. BREEZWAYS
Correction
Resolved
05/14/2007
INSPECTION CANCELLED
Correction
Corrective Action Required
05/14/2007
Dwelling Unit Separation (IRC) REPAIR OVER BORED HOLES IN GARAGE RATED CEILING FOR THE LIGHTS. NORTH GARAGE
Correction
Corrective Action Required
05/14/2007
SCREW INSTALLATION / NAIL SHEETROCK NOT NAILED OFF. HIGH CEILINGS
Correction
Corrective Action Required
05/14/2007
Through Penetrations (IRC) BALCONYS STILL NEED TO BE SEALED AT CEILING EDGES. BALCONYS
All Rough Inspection - Commercial Partial 05/16/2007
Correction
Corrective Action Required
05/16/2007
Roof Ventilation Required (IRC) ROOF VENTS NOT INSTALLED. ROOF
Rated Assembly Inspection Partial 05/16/2007
Correction
Partial Correction
05/16/2007
None 1 ST. , 2 ND. , AND 3 RD. FLOOR BREEZWAYS SCREW INSPECTION AND SHEETROCK INSTALLATION APPROVED. OK TO INSTALL 3 RD. LAYER OF ROCK IN BREEZWAYS ONLY. HIGH CEILING AREAS NOT APPROVED.
Rated Assembly Inspection Partial 05/17/2007
Correction
Partial Correction
05/17/2007
None 1 ST. , 2 ND. , AND 3 RD. FLOOR BREEZWAYS SCREW INSPECTION AND SHEETROCK INSTALLATION APPROVED. OK TO INSTALL 3 RD. LAYER OF ROCK IN BREEZWAYS ONLY. HIGH CEILING AREAS NOT APPROVED.
Correction
Partial Correction
05/17/2007
None ALL BALCONYS SHEETROCK AND FASTENING APPROVED ON 2 ND. LAYER. OK TO INSTALL 3 RD. LAYER OF ROCK. BALCONYS
Erosion Control Inspection Residential Passed 05/17/2007
All Rough Inspection - Commercial Partial 05/18/2007
Correction
Resolved
05/18/2007
Dwelling Unit Separation (IRC)
Correction
Resolved
05/18/2007
Through Penetrations (IRC) BREEZWAYS
Correction
Corrective Action Required
05/18/2007
Dwelling Unit Separation (IRC) REPAIR OVER BORED HOLES IN GARAGE RATED CEILING FOR THE LIGHTS. NORTH GARAGE
Correction
Resolved
05/18/2007
SCREW INSTALLATION / NAIL HIGH CEILINGS
Correction
Resolved
05/18/2007
Through Penetrations (IRC) BALCONYS
Rated Assembly Inspection Partial 05/18/2007
Correction
Partial Correction
05/18/2007
None HIGH CEILING AREAS OVER STAIRWAYS 3 RD. LAYER NOT APPROVED.
Correction
Partial Correction
05/18/2007
None ALL BALCONYS SHEETROCK AND FASTENING APPROVED ON 3 RD. LAYER. BALCONYS
Rated Assembly Inspection Passed 05/21/2007
Correction
Resolved
05/21/2007
None
Correction
Resolved
05/21/2007
None BALCONYS
Erosion Control Inspection Residential Passed 06/13/2007
All Rough Inspection - Commercial Passed 06/13/2007
Correction
Resolved
06/13/2007
Roof Ventilation Required (IRC) ROOF
Correction
Resolved
06/13/2007
Dwelling Unit Separation (IRC) NORTH GARAGE
Occupancy Inspection - Codes Commercial Failed 06/13/2007
Correction
Corrective Action Required
06/13/2007
ROOF REMOVE TOE BOARDS FROM THE ROOF
Correction
Corrective Action Required
06/13/2007
WEATHER PROOF ALL EXTERIOR UNTREARED WOOD REQUIRED TO BE PAINTED EXTERIOR
Correction
Corrective Action Required
06/13/2007
HOSE BIBB SEAL PENETRATIOIN AROUND HOSE BIBB. SOUTH END OF BLDG.
Correction
Corrective Action Required
06/13/2007
Electrical Equipment Mounting (IRC) SECURE LIQUID TIGHT WITHIN 12 INCHS OF BOX. SOUTH END OF BLDG.
Correction
Corrective Action Required
06/13/2007
Handrails (IRC) RETURN HANDRAIL ENDS TO THE WALL
Correction
Corrective Action Required
06/13/2007
SEWER CLEAN OUT CUT CLEAN OUT PIPE TO GRADE LEVEL. REPLACE COVER ON WEST CLEAN OUT. NORTH END
Correction
Resolved
06/13/2007
None
Occupancy Inspection - Codes Commercial Failed 09/13/2007
Correction
Resolved
09/13/2007
ROOF
Correction
Resolved
09/13/2007
WEATHER PROOF EXTERIOR
Correction
Resolved
09/13/2007
HOSE BIBB SOUTH END OF BLDG.
Correction
Resolved
09/13/2007
Electrical Equipment Mounting (IRC) SOUTH END OF BLDG.
Correction
Resolved
09/13/2007
Handrails (IRC)
Correction
Resolved
09/13/2007
SEWER CLEAN OUT NORTH END
Correction
Resolved
09/13/2007
None
Correction
Corrective Action Required
09/13/2007
Receive Planning & Development Approval
Correction
Corrective Action Required
09/13/2007
Receive Public Works Approval
Erosion Control Inspection Residential Passed 10/19/2007
Occupancy Inspection - Codes Commercial Passed 10/19/2007
Correction
Resolved
10/19/2007
Receive Planning & Development Approval
Correction
Resolved
10/19/2007
Receive Public Works Approval
Correction
Resolved
10/19/2007
None OCCUPANCY APPROVED CLOSE PERMIT C. O.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home