Permit Application Status

B0502077


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0502077
Building Permit - Commercial
Certificate of Occupancy
THE NORTHWESTERN MUTUAL LIFE INS CO
NEW MULTI-FAMILY
BUILDING D TYPE III
11/17/2005
09/14/2006
03/11/2008
10/22/2007
Locations
Contacts
AMLI RESIDENTIAL CONSTRUCTION LLC, Address:10800 FARLEY SUITE 304  
CLIFFORD WONG, Address:5757 ALPHA RD SUITE 505  
THE NORTHWESTERN MUTUAL LIFE INS CO, Address:PO BOX 3151  
JVM NEW LONGVIEW LLC, Address:PO BOX 06494  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/27/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1013.3 - Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 75 feet. In occupancies in Groups H-1, H-2, Nd H-3, the common path of egress travel shall not exceed 25 feet.
Correction

Codes Administration - 2003 IBC 1405.3 - Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashing shall be installed at the perimeters of exterior doors and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projecting flanges shall be installed on both sides and the ends of copings, under sills and continuously above projecting trim.
Correction

Codes Administration - 2003 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602.
Correction

Codes Administration - Notes on Sheet D3 are overlapping.
Correction

Codes Administration - Factory-built fireplaces shall be installed per the manufactores installation requirements and meet the requirements of Section 2111.14 of the 2003 IBC.
Correction

Codes Administration - I am unable to locate specifications regarding the installation of the mechancial, electrical and plumbing systems.
Correction

Codes Adminsitration - I am unable to locate a detail for the water heater and furnace installation.
Correction

Fire Department- IFC 903.3.7 The location of fire department connections shall be approved by the fire code official. Connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant.
Correction

Fire Department- IFC D105.2 Width. Fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm) in the immediate vicinity of any building or portion of building more than 30 feet (9144 mm) in height.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 504.5 - Makeup air. Installations exhausting more than 200 cfm shall be provided with makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of not less than 100 square inches shall be provided in the closet inclosure.
Correction

Codes Administration - 2003 IBC 504.6.1 - Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet from the dryer loction to the outlet terminal. The maximum length of duct shall be reduced 2.5 feet for each 45-degree bend and 5 feet for each 90-degree bend. The maximum length of the exhaust duct does not include the transition duct.
Correction

Codes Adminsitration - 2003 IPC 802.1.6 - Domestic dishwashing machines. Domestic dishwashing machines shall dishcharge indirectly through an air gap or air break into a standpipe or waste receptor in accordance with Section 802.2, or discharge into a wye-branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste grinder. The waste line of a domestic dishwashing machine discharging into a kitchen sink tailpiece or food waste grinder shall connect to a deck-mounted air gap or the waste line shall rise and be securely fastenend to the underside of the sink rim or counter.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $4,685.57 $4,685.57 Paid 09/14/2006
89 Sewer Tap Fees $3,000.00 $3,000.00 Paid 09/14/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Partial 12/14/2006
Correction
Partial Correction
12/14/2006
DISCONECTS PANEL INSTALLATION IN ALL APARTMENTS APPROVED. ALL UNITS
All Rough Inspection - Commercial Partial 12/14/2006
Correction
Corrective Action Required
12/14/2006
ROOF VENTS ROOF VENTS NOT INSTALLED.
Correction
Corrective Action Required
12/14/2006
Dwelling Unit Separation (IRC) ROOF TRUSS BRACING CAN NOT PENETRATE FIRE WALLS. Attic Area
Correction
Corrective Action Required
12/14/2006
Fireblocking (IRC) FIRE CAULK ALL PENETRATION OF FLOOR AND CEILING. PLUMBING, ELECT. SPRINKLER PIPES ETC. THROUGH OUT
Correction
Corrective Action Required
12/14/2006
DRAFT STOP SEAL ALL PENETRATIONS OF DRAFT STOP. THROUGH OUT
Correction
Partial Correction
12/14/2006
None OK INSULATION OF EXTERIOR WALLS 1 ST. AND 2 ND. FLOOR ONLY.
All Rough Inspection - Commercial Partial 12/15/2006
Correction
Resolved
12/15/2006
Dwelling Unit Separation (IRC) Attic Area
Correction
Resolved
12/15/2006
Fireblocking (IRC) THROUGH OUT
Correction
Resolved
12/15/2006
DRAFT STOP THROUGH OUT
Correction
Resolved
12/15/2006
None
Correction
Corrective Action Required
12/15/2006
Stair Treads and Risers (IRC) STAIRS NOT INSTALLED IN HALLWAYS AT CHANGE OF ELEVATIONS OK INSULATION AND ROCK HALL WAYS
Correction
Corrective Action Required
12/15/2006
FIREPLACE CHASE FIREPLACE INSTALLATION INCOMPLETE 3 RD. FLOOR. 3 RD. FLOOR
Rated Assembly Inspection Failed 12/27/2006
Correction
Corrective Action Required
12/27/2006
RATED ASSEMBLY FIRE ROCK BATHROOM ROCK INCOMPLETE 434 - C4
Correction
Corrective Action Required
12/27/2006
TYPE OF ROCK BATHROOM REQUIRES GREEN BOARD 424 - C- 4 AND 435 -C4B BATHROOM
Correction
Partial Correction
12/27/2006
None SCREW INSPECTION APTS. ONLY APPROVED.
Electrical Service Inspection Passed 12/27/2006
Correction
Resolved
12/27/2006
DISCONECTS ELECT. SERVICE APPROVED APTS. 411, 412, 414, 416, 417, 418, 421, 422, 423, 424, 425, 426, 427, 428, 431, 432,433, 434, 435, 436, 437, 438 AND HOUSE PANEL 460 SW TOWER PARK DR. RELEASE ABOVE LISTED ELECT SERVICES. 800 AMP MAIN. ALL UNITS
Correction
Resolved
12/27/2006
None WATER PIPE GROUND IN PANTRY OF 412.
Rated Assembly Inspection Failed 12/28/2006
Correction
Resolved
12/28/2006
RATED ASSEMBLY FIRE ROCK 434 - C4
Correction
Corrective Action Required
12/28/2006
TYPE OF ROCK BATHROOM REQUIRES GREEN BOARD 424 - C- 4 BATHROOM
Correction
Partial Correction
12/28/2006
None SCREW INSPECTION APTS. ONLY APPROVED.
Rated Assembly Inspection Partial 12/29/2006
Correction
Resolved
12/29/2006
TYPE OF ROCK 424 - C- 4 BATHROOM
Correction
Partial Correction
12/29/2006
None SCREW INSPECTION APTS. ONLY APPROVED.
Rated Assembly Inspection Passed 02/12/2007
Correction
Resolved
02/12/2007
RATED ASSEMBLY FIRE ROCK INSP. SHOULD HAVE BEEN ON PERMIT #B0502074 434 - C4
Correction
Resolved
02/12/2007
TYPE OF ROCK INSPECTION SHOULD HAVE BE ON PERMIT #B0502074. 424 - C- 4 BATHROOM
Correction
Resolved
02/12/2007
None SCREW INSPECTION APTS. ONLY APPROVED. INSPECTION SHOULD HAVE BEEN ON PERMIT #B0502074.
All Rough Inspection - Commercial Partial 02/12/2007
Correction
Corrective Action Required
02/12/2007
ROOF VENTS ROOF VENTS NOT INSTALLED.
Correction
Resolved
02/12/2007
Stair Treads and Risers (IRC) STAIRS NOT INSTALLED IN HALLWAYS AT CHANGE OF ELEVATIONS OK INSULATION AND ROCK. INSPECTION IS WRONG PERMIT. SHOULD BE ON PERMIT #B0502074. HALL WAYS
Correction
Resolved
02/12/2007
FIREPLACE CHASE FIREPLACE INSTALLATION INCOMPLETE 3 RD. FLOOR. INSPECTION IS ON WRONG PERMIT #. SHOULD BE ON PERMIT # B0502074. 3 RD. FLOOR
Rated Assembly Inspection Passed 04/10/2007
Correction
Resolved
04/10/2007
Attic Separation (IRC) 433-435 FIREPLACE ROCK INSPECTION- APPROVED FIREPLACE INSIDE LAYER
All Rough Inspection - Commercial Passed 04/19/2007
Correction
Resolved
04/19/2007
ROOF VENTS
Occupancy Inspection - Codes Commercial Failed 04/19/2007
Correction
Corrective Action Required
04/19/2007
PENETRATIONS / HOLES BALCONY APT. 437, 438 AND 411 EXTERIOR SIDING
Correction
Corrective Action Required
04/19/2007
Electrical Equipment Mounting (IRC) BALCONY LIGHT LOOSE. APT. 437
Correction
Corrective Action Required
04/19/2007
EMERGENCY LIGHT NOT WORKING APT. 424
Correction
Corrective Action Required
04/19/2007
Smoke Alarms (IRC) NOT INSTALLED APT. 425
Correction
Corrective Action Required
04/19/2007
OPEN BULB FIXTURE OPEN BULB FIXTURER IN CLOSET APT. 426
Correction
Corrective Action Required
04/19/2007
ANTI TIP DEVICE STOVE REQUIRES ANTI-TIP DEVICE APT. 424, 417, 414
Correction
Corrective Action Required
04/19/2007
Receptacles at Wall Counter Spaces (IRC) OUTLET RIGHT OF STOVE NOT WORKING APT.424 KITCHEN
Correction
Corrective Action Required
04/19/2007
APT.418 NOT READY APT. 418
Correction
Corrective Action Required
04/19/2007
BATHROOM GROUT BATHROOM TILE APT. 416
Correction
Corrective Action Required
04/19/2007
FIREPLACES FIREPLCES INCOMPLETE APT. #s 433 AND 435
Correction
Corrective Action Required
04/19/2007
LIGHT FIXTURE KITCHEN LIGHTS NOT INSTALLED APT# 412
Correction
Corrective Action Required
04/19/2007
FIRE STOP REPAIR RATED CEILING OF SW. BEDROOM APT. #411 APT. #s 412, 411
Correction
Corrective Action Required
04/19/2007
Outlet Box Covers & Faceplates (IRC) INNSTALL SWITCH PLATES APT #. 412, 411
Correction
Corrective Action Required
04/19/2007
RATED WALL GROUND ACCESS REQUIRES A RATED COVER PLATE APT. 412
Correction
Corrective Action Required
04/19/2007
SPRINKLER ESCUTCHEON PLATE ESCUTCHEON PLATES REQUIRED TO FIT FLUSH AGAINST WALL.
Correction
Corrective Action Required
04/19/2007
Handrails (IRC) INSTALL HAND RAILS
Correction
Corrective Action Required
04/19/2007
LABELS LABEL ALL METERS AND DISCONECTS
Correction
Corrective Action Required
04/19/2007
CLEAN OUTS CUT CLEAN OUTS OFF AND INSTALL CAPS AT GRADE LEVEL.
Correction
Corrective Action Required
04/19/2007
NOT READY COMPLETE ALL EXTERIOR ELECT. LIGHTS / OUTLETS. EXTERIOR
Correction
Corrective Action Required
04/19/2007
Receive Fire Department approval
Correction
Partial Correction
04/19/2007
Receive Public Works Approval
Correction
Partial Correction
04/19/2007
Receive Planning & Development Approval PLANNING OK FOR TEMP. OCCUPANCY
Correction
Corrective Action Required
04/19/2007
NOT READY BUILDING IS NOT READY FOR TEMPORARY OCCUPANCY. APT .# 424 OK TO COMPLETE AS A MODEL - NOT TO BE OPEN TO THE PUBLIC. DO NOT OCCUPY
Occupancy Inspection - Codes Commercial Failed 04/26/2007
Correction
Resolved
04/26/2007
PENETRATIONS / HOLES EXTERIOR SIDING
Correction
Resolved
04/26/2007
Electrical Equipment Mounting (IRC) APT. 437
Correction
Resolved
04/26/2007
EMERGENCY LIGHT APT. 424
Correction
Resolved
04/26/2007
Smoke Alarms (IRC) APT. 425
Correction
Resolved
04/26/2007
OPEN BULB FIXTURE APT. 426
Correction
Resolved
04/26/2007
ANTI TIP DEVICE APT. 424, 417, 414
Correction
Resolved
04/26/2007
Receptacles at Wall Counter Spaces (IRC) APT.424 KITCHEN
Correction
Corrective Action Required
04/26/2007
APT.418 NOT READY APT. 418
Correction
Resolved
04/26/2007
BATHROOM APT. 416
Correction
Resolved
04/26/2007
FIREPLACES APT. #s 433 AND 435
Correction
Resolved
04/26/2007
LIGHT FIXTURE APT# 412
Correction
Resolved
04/26/2007
FIRE STOP APT. #s 412, 411
Correction
Resolved
04/26/2007
Outlet Box Covers & Faceplates (IRC) APT #. 412, 411
Correction
Resolved
04/26/2007
RATED WALL GROUND ACCESS REQUIRES A RATED COVER PLATE PANTRY APT. 412. GROUND FOR SOUTH SERVICE IS IN PANTRY APT. 417. APT. 412
Correction
Resolved
04/26/2007
SPRINKLER ESCUTCHEON PLATE
Correction
Corrective Action Required
04/26/2007
Handrails (IRC) INSTALL HAND RAILS BREEZWAYS EXTERIOR STEPS
Correction
Resolved
04/26/2007
LABELS
Correction
Resolved
04/26/2007
CLEAN OUTS
Correction
Resolved
04/26/2007
NOT READY EXTERIOR
Correction
Resolved
04/26/2007
Receive Fire Department approval OK TEMP.
Correction
Partial Correction
04/26/2007
Receive Public Works Approval
Correction
Resolved
04/26/2007
Receive Planning & Development Approval
Correction
Resolved
04/26/2007
NOT READY
Erosion Control Inspection Residential Passed 04/26/2007
Issue Temporary C of O Complete 4/25/2007 4/26/2007 04/26/2007
Occupancy Inspection - Codes Commercial Failed 05/01/2007
Correction
Resolved
05/01/2007
APT.418 APT. 418
Occupancy Inspection - Codes Commercial Failed 09/13/2007
Correction
Resolved
09/13/2007
Handrails (IRC) BREEZWAYS EXTERIOR STEPS
Correction
Partial Correction
09/13/2007
Receive Planning & Development Approval
Erosion Control Inspection Residential Passed 10/19/2007
Occupancy Inspection - Codes Commercial Passed 10/19/2007
Correction
Resolved
10/19/2007
Receive Public Works Approval
Correction
Resolved
10/19/2007
Receive Planning & Development Approval
Correction
Resolved
10/19/2007
None occupancy approved close permit c. o.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home