Permit Application Status

B0502036


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0502036
Building Permit - Commercial
Certificate of Occupancy
GRANDLAND DEVELOPMENT LC
CHANGE OF TENANT
TENANT FINISH
11/14/2005
12/16/2005
06/14/2006
03/23/2006
Locations
Contacts
THOLEN WOLFE CONTRACTORS, Address:1929 INDIAN AV  
GRANDLAND DEVELOPMENT LC, Address:PO BOX 10076  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/13/2006 10/29/2010
Correction

Codes Administration - Information is not provided for the installation of the plumbing, electrical and mechanical systems.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 501.2 - Outdoor discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $122.55 $122.55 Paid 12/16/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/16/2005
All Rough Inspection - Commercial Partial 12/21/2005
Correction
Partial Correction
12/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH RESTROOM; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 12/21/2005
Correction
Partial Correction
12/21/2005
1-HR RATED WALL W WALL OF RESTROOM E FACE ONE LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Rated Assembly Inspection Partial 01/05/2006
Correction
Partial Correction
01/05/2006
1-HR RATED WALL W WALL OF RESTROOM E FACE ONE LAYER 5/8" TYPE X GWB; REMAINDER OF WALL E FACE ONE LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY PORTIONS LISTED BELOW:
All Rough Inspection - Commercial Passed 01/18/2006
Correction
Resolved
01/18/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH RESTROOM; N-S DEMISING WALL + CENTER E-W WALL AT REAR OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Passed 01/20/2006
Correction
Resolved
01/20/2006
1-HR RATED WALL W WALL OF RESTROOM E FACE ONE LAYER 5/8" TYPE X GWB; REMAINDER OF WALL E FACE ONE LAYER 5/8" TYPE X GWB; W FACE ONE LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Above Ceiling Inspection Passed 02/02/2006
Correction
Resolved
02/02/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 02/10/2006
Correction
Partial Correction
02/10/2006
OCCUPANCY APPROVAL STATUS OK TO SET UP FOR BUSINESS NO PUBLIC UNTIL APPROVED
Correction
Corrective Action Required
02/10/2006
LIGHTED SIGN @ BUILDING FASCIA INSTALLATION BY LICENSED ELECTRICIAN WHEN INSTALLED. REQUIRES P&D PERMIT + LISTING LABEL +
Correction
Corrective Action Required
02/10/2006
DOOR# 02 NOT PER DRAWING RATED ASSEMBLY REQUIRED
Correction
Corrective Action Required
02/10/2006
Receive Water Utilities Approval CONTACT BEN HASKAMP @ LSWU 969-7636 BUILDING BACKFLOW TEST REPORT NOT ON RECORD
Correction
Corrective Action Required
02/10/2006
Receive Fire Department approval SEE REPORT PROVIDED
Occupancy Inspection - Codes Commercial Failed 02/14/2006
Correction
Partial Correction
02/14/2006
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Corrective Action Required
02/14/2006
LIGHTED SIGN @ BUILDING FASCIA INSTALLATION BY LICENSED ELECTRICIAN WHEN INSTALLED. REQUIRES P&D PERMIT + LISTING LABEL +
Correction
Resolved
02/14/2006
DOOR# 02
Correction
Corrective Action Required
02/14/2006
Receive Water Utilities Approval CONTACT BEN HASKAMP @ LSWU 969-7636 BUILDING BACKFLOW TEST REPORT NOT ON RECORD
Correction
Resolved
02/14/2006
Receive Fire Department approval PER JOE DIR 2/14/06
Occupancy Inspection - Codes Commercial Failed 02/15/2006
Correction
Resolved
02/15/2006
Receive Water Utilities Approval PER BEN HASKAMP 2/15/06
Occupancy Inspection - Codes Commercial Failed 03/21/2006
Correction
Corrective Action Required
03/21/2006
OCCUPANCY APPROVAL STATUS TEMPORARY OCCUPANCY AUTHORIZATION HAS EXPIRED
Correction
Corrective Action Required
03/21/2006
LIGHTED SIGN @ BUILDING FASCIA PER NEC 600.3 NO UL LABEL FOUND AS INDICATION OF LISTING
Occupancy Inspection - Codes Commercial Passed 03/23/2006
Correction
Resolved
03/23/2006
OCCUPANCY APPROVAL STATUS
Correction
Resolved
03/23/2006
LIGHTED SIGN @ BUILDING FASCIA PER NEC 600.3 UL LABELS AFFIXED AS INDICATION OF LISTING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home