Permit Application Status

B0502003


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0502003
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW HANGER (REPLACEMENT)
11/07/2005
03/21/2006
10/13/2007
04/18/2007
Locations
Contacts
KOLCHINSKY ARCHITECTS INC, Address:110 N CHERRY SUITE 100  
CITY OF LEES SUMMIT, Address:2751 NE DOUGLAS ST  
J& M CONTRACTING INC, Address:1712 E 123RD ST  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/17/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1008.1.4 - Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit veritical in 12 units horizontal (2-percent slope).
Correction

Codes Administration - 2003 IBC 1008.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). When the landing serves an occupant load of 50 or more, doors in any position shall not reduce the landings to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm).
Correction

Codes Administration - 2003 IBC 1008.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater than 0.25 inch at doorways shall beveled with a slope not greater than one unit vertical in two units horizontal.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Fire Department- Clarify the use of the hangar. Will it be used for storage or maintenance?
Correction

Codes Administration - A complete site plan has not been provided.
Correction

Codes Administration - 2003 IBC 412.2.1 - Exterior walls. Exterior walls located less than 30 feet from property lines, lot lines or a public way shall have a fire-resistance rating not less than 2 hours.
Correction

Codes Administration - 2003 IBC 412.2.3 - Floor Surfaces. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump.
Correction

Codes Administration - Information has not been provided for the materials to be used and the method of installation of the plumbing and mechanical systems.
Correction

Codes Administration - As no mechanical plans have been submitted, this permit does not include any hvac work.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department;A site plan depicting proposed fire apparatus access, location of fire lanes and parking areas and for fire hydrant locations shall be submitted to the fire department for review and approval prior to construction.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Fire Department- IFC 903.3.7 The location of fire department connections shall be approved by the fire code official. Connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $825.80 $825.80 Paid 03/21/2006
0120 Building Permit Fee ($3.00) ($3.00) $0.00 N/A
0122 Permit Reinspection Fees $30.00 $30.00 Paid 10/11/2006
84 Water Meters $125.00 $125.00 Paid 10/11/2006
85 Water Taps $3,418.00 $3,418.00 Paid 10/11/2006
Right of Way Permit $35.00 $35.00 Paid 10/11/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Not Ready 04/05/2006
Correction
Corrective Action Required
04/05/2006
NOT READY FOR INSPECTION
Footing Inspection - Commercial Partial 04/06/2006
Correction
Partial Correction
04/06/2006
TEXT APPROVED TO POUR ALL FOOTINGS AND COLUMN PIERS NOTE: TOP 2 BARS WRAPPING COLUMN VERTS TO BE VERIFIED AT SLAB INSPECTION.
Correction
Resolved
04/06/2006
NOT READY FOR INSPECTION
Footing Inspection - Commercial Partial 08/17/2006
Correction
Partial Correction
08/17/2006
TEXT APPROVED TO POUR ALL FOOTINGS AND COLUMN PIERS NOTE: TOP 2 BARS WRAPPING COLUMN VERTS TO BE VERIFIED AT SLAB INSPECTION.
Underslab Plumbing Inspection - Commercial Not Ready 08/17/2006
Correction
Corrective Action Required
08/17/2006
REQUIRED DRAWINGS APPROVED DRAWINGS MUST BE ON SITE FOR ALL INSPECTIONS. DRAWING MUST SHOW ALL PLUMBING INCLUDING TRENCH DRAINS AND SAND/OIL SEPARATOR. NOTE: SLAB INSPECTION REQUIRED PRIOR TO POUR.
Underslab Plumbing Inspection - Commercial Passed 08/24/2006
Correction
Resolved
08/24/2006
REQUIRED DRAWINGS
Underground Plumbing Inspection - Commercial Partial 08/24/2006
Correction
Partial Correction
08/24/2006
TEXT NORTH 60' OF WASTE PIPE ON WEST SIDE OF BUILDING APPROVED TO COVER. PROVIDE CLEANOUT IN WASTE LINE MAX. 100' SPACING. INTERCEPTOR AND HOLDING TANK NOT INSTALLED YET.
Footing Inspection - Commercial Not Ready 09/05/2006
Correction
Corrective Action Required
09/05/2006
COMMENTS CLEAR GRAVEL AWAY FROM PIERS AND REMOVE PAPER.
Footing Inspection - Commercial Passed 09/06/2006
Correction
Resolved
09/06/2006
TEXT
Correction
Resolved
09/06/2006
COMMENTS
Water Service Inspection Passed 10/11/2006
Water Service Inspection - Commercial Request Complete 10/11/2006 10/11/2006 10/11/2006
Electrical Service Inspection Passed 10/16/2006
Correction
Resolved
10/16/2006
None 200 AMP PANEL
Rough Plumbing Inspection - Commercial Partial 10/18/2006
Correction
Partial Correction
10/18/2006
None BATH AND MECH. RM. IN-WALL PLUMBING ROUGHIN APPROVED OK TO ROCK WHEN READY
Rough Electrical Inspection - Commercial Partial 10/18/2006
Correction
Partial Correction
10/18/2006
None BATH AND MECH. RM. IN-WALL ELECTRICAL ROUGHIN APPROVED OK TO ROCK WHEN READY
Underground Plumbing Inspection - Commercial Partial 11/09/2006
Correction
Partial Correction
11/09/2006
TEXT NORTH 60' OF WASTE PIPE ON WEST SIDE OF BUILDING APPROVED TO COVER. PROVIDE CLEANOUT IN WASTE LINE MAX. 100' SPACING. INTERCEPTOR AND HOLDING TANK NOT INSTALLED YET.
Rough Mechanical Inspection - Commercial Failed 11/09/2006
Correction
Corrective Action Required
11/09/2006
COMBUSTION AIR PROVIDE (2) COMBUSTION AIR VENTS. 1 WITHIN 12" OF FLOOR & 1 WITHIN 12" OF CEILING. EACH VENT TO BE MINIMUM 350 SQUARE INCHES. (VENT CURRENTLY INSTALLED ONLY PROVIDES 285 SQ. INCHES) NOTE: METAL GRILLE OPEN AREA = 75% OF FACE AREA.
Correction
Corrective Action Required
11/09/2006
Appliance Clearance to Unprotected Combustible Construction (IRC) PROVIDE MINIMUM 6" CLEARANCE AT FLUE PIPING THRU CEILING & ROOF.
Gas Piping Inspection - Commercial Passed 11/09/2006
Gas Service Inspection - Commercial Passed 11/09/2006
Correction
Resolved
11/09/2006
None 1 APPLIANCE
Occupancy Inspection - Codes Commercial Failed 12/21/2006
Correction
Corrective Action Required
12/21/2006
REQUIRED LIGHTING ALL EXIT DOORS MUST BE LIT
Correction
Corrective Action Required
12/21/2006
ADA RESTROOM VIOLATIONS 1- LABEL RESTROOM AS UNISEX & ACCESSIBLE. 2- GRAB BARS TO BE CAPABLE OF WITHSTANDING 250# OF PRESSURE. Restroom
Correction
Corrective Action Required
12/21/2006
Panel Circuit Identification (IRC) CIRCUIT LABELS MUST BE IN INK
Correction
Corrective Action Required
12/21/2006
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/21/2006
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/21/2006
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/21/2006
Receive Fire Department approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/21/2006
TEXT ALL PREVIOUS INSPECTIONS ITEMS MUST BE PASSED PRIOR TO OCCUPANCY
Rough Plumbing Inspection - Commercial Passed 12/21/2006
Correction
Resolved
12/21/2006
None
Rough Mechanical Inspection - Commercial Failed 12/21/2006
Underground Plumbing Inspection - Commercial Failed 12/21/2006
Correction
Partial Correction
12/21/2006
TEXT PROVIDE LETTER OF AFFIDAVIT FROM RESPONSIBLE PLUMBING CONTRACTOR DESCRIBING ALL METHODS AND MATERIALS INVOLVED IN HOLDING TANK AND OIL SEPARATOR. (NOT INSPECTED)
Occupancy Inspection - Codes Commercial Failed 12/22/2006
Underground Plumbing Inspection - Commercial Failed 12/22/2006
Correction
Partial Correction
12/22/2006
TEXT PROVIDE LETTER OF AFFIDAVIT FROM RESPONSIBLE PLUMBING CONTRACTOR DESCRIBING ALL METHODS AND MATERIALS INVOLVED IN HOLDING TANK AND OIL SEPARATOR. (NOT INSPECTED)
Rough Mechanical Inspection - Commercial Failed 12/22/2006
Rough Electrical Inspection - Commercial Passed 12/22/2006
Correction
Resolved
12/22/2006
None
Occupancy Inspection - Codes Commercial Failed 01/02/2007
Correction
Resolved
01/02/2007
30 DAY TCO
Correction
Resolved
01/02/2007
ADA RESTROOM VIOLATIONS
Correction
Resolved
01/02/2007
REQUIRED LIGHTING
Correction
Resolved
01/02/2007
Panel Circuit Identification (IRC)
Correction
Resolved
01/02/2007
Receive Fire Department approval
Correction
Resolved
01/02/2007
TEXT
Underground Plumbing Inspection - Commercial Passed 01/02/2007
Correction
Resolved
01/02/2007
TEXT
Rough Mechanical Inspection - Commercial Passed 01/02/2007
Correction
Resolved
01/02/2007
Appliance Clearance to Unprotected Combustible Construction (IRC)
Correction
Resolved
01/02/2007
COMBUSTION AIR
Occupancy Inspection - Codes Commercial Passed 04/17/2007
Correction
Resolved
04/17/2007
Receive Planning & Development Approval
Correction
Resolved
04/17/2007
Receive Public Works Approval
Correction
Resolved
04/17/2007
Receive Water Utilities Approval
Occupancy Inspection - Codes Commercial Passed 04/18/2007
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home