Permit Application Status

B0501822


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0501822
Building Permit - Commercial
Certificate of Occupancy
RAINTREE VILLAGE SHOPPING CENTER LLC
NEW COMMERCIAL
NEW BUILDING
10/10/2005
03/14/2006
11/27/2007
06/06/2007
Locations
Contacts
ARCHER ENGINEERS, Address:3731 NE TROON DR  
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
CAPITAL CONSTRUCTION SERVICES, LLC, Address:2642 NE HAGEN RD  
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
RAINTREE VILLAGE SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/19/2006 10/29/2010
Correction

Codes Administration - The size of the water tap and meter setup is not indicated on the plans.
Correction

Fire Department- Building to be addressed off of Lemans .
Correction

Codes Administration - For the Health Department approval permit approval contact Steve Hutchens with the Jackson County Public Works Department at 816-881-4471. Permit approval is required by the City of Lee's Summit prior to issuance of the full building permit.
Correction

Codes Administration - A project cost has not been provided for this project.
Correction

Road Improviements. The Developer shall design, engineer and construct the Road Improvements. The City shall issue no temporary or final Certificates of Occupancy for any of the Development until the City or MoDOT, as appropriate, has issued a Certificate of Substantial Completion for the Road Improvements (the "Certificate of Completion").
Correction

Fire Department- The occupant load shall be posted in a conspicuous location near the front door.
Correction

Fire Department- When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Fire Department- Provide a complete code analysis for the project.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - Smoke-free establishment (existing and new). Food service establishments that elect to be smoke-free, including all existing and new fast food establishments which are required to be smoke-free, shall post the following signage: "THIS IS A SMOKE-FREE ESTABLISHMENT. Smoking is not permitted within this establishment. (Pursuant to LSCO Sec. 17-6.)"
Correction

Codes Adminsitration - 2003 IBC 303.1.1 - Nonaccessory assembly use. A building or tenant space used for assembly purposes by less than 50 persons shall be considered a Group B occupancy.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Tale 403.1 shall be considered individually by the code official. The number of occupants shall be deetermined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $541.50 $541.50 Paid 03/14/2006
84 Water Meters $200.00 $200.00 Paid 03/14/2006
85 Water Taps $5,468.00 $5,468.00 Paid 03/14/2006
89 Sewer Tap Fees $240.00 $240.00 Paid 03/14/2006
Middle Big Creek Watershed $267.84 $267.84 Paid 03/14/2006
Right of Way Permit $35.00 $35.00 Paid 03/14/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 03/16/2006
Correction
Resolved
03/16/2006
None STEEL AS PER PLANS
Erosion Control Inspection Residential Passed 03/16/2006
Correction
Resolved
03/16/2006
Erosion Control
Underslab Plumbing Inspection - Commercial Failed 03/29/2006
Correction
Corrective Action Required
03/29/2006
PARTIAL OK TO COVER , RECALL WHEN GREASE TRAP IS INSTALLLED
Sewer Service Inspection Passed 03/29/2006
Correction
Resolved
03/29/2006
None
Sewer Service Inspection - Commercial Request Complete 3/29/2006 3/29/2006 03/29/2006
Underslab Electrical Inspection - Commercial Passed 04/04/2006
Correction
Resolved
04/04/2006
None
Underslab Plumbing Inspection - Commercial Passed 04/04/2006
Correction
Resolved
04/04/2006
PARTIAL
Correction
Resolved
04/04/2006
None grease trap approved
Water Service Inspection Passed 04/06/2006
Correction
Resolved
04/06/2006
None
Water Service Inspection - Commercial Request Complete 4/6/2006 4/6/2006 04/06/2006
Rough Framing Inspection - Commercial Failed 05/19/2006
Correction
Corrective Action Required
05/19/2006
TRUSS BEARING PROVIDE DBL STUD UNDER WEST DBL GIRTER TRUSS EACH END.
Correction
Corrective Action Required
05/19/2006
TOP PLATE CONNECTION PROVIDE REQUIRED TIES AT EACH DBL STUD OVER EACH HEADER TO TOP PLATES.
Correction
Corrective Action Required
05/19/2006
JACK STUDS PROVIDE CLARIFICATION ON JACK AND FULL LENGTH STUDS ON ALL HEADERS.
Correction
Corrective Action Required
05/19/2006
SIMPSON TIES PROVIDE REVISED PLANS OR INSTALL LTP4 TIES ON REQUIRED HEADERS.
Correction
Corrective Action Required
05/19/2006
Foundation Anchor Bolts (IRC) INSTALL HOLD DOWN PER PLANS 24" O.C. WALL SECTION \32" O.C WALL SECTION INSTALL PER PLANS
Rough Framing Inspection - Commercial Request Complete 5/18/2006 5/19/2006 05/19/2006
Driveway Inspection Passed 02/28/2007
Electrical Service Inspection Passed 04/12/2007
Correction
Resolved
04/12/2007
None
Rough Framing Inspection - Commercial Failed 04/12/2007
Correction
Corrective Action Required
04/12/2007
Foundation Anchor Bolts (IRC) INSTALL HOLD DOWN PER PLANS INSTALL PER PLANS
Correction
Resolved
04/12/2007
SIMPSON TIES
Correction
Resolved
04/12/2007
JACK STUDS
Correction
Resolved
04/12/2007
TOP PLATE CONNECTION
Correction
Resolved
04/12/2007
TRUSS BEARING
Rough Framing Inspection - Commercial Failed 04/24/2007
Correction
Resolved
04/24/2007
Foundation Anchor Bolts (IRC)
Correction
Partial Correction
04/24/2007
PLANS SUBMIT REVISED PLANS FOR APPROVAL. OK TO INSULATE AND ROCK . PENDING APPROVED PLANS.
Above Ceiling Inspection Passed 05/21/2007
Correction
Resolved
05/21/2007
None
Occupancy Inspection - Codes Commercial Failed 05/21/2007
Correction
Corrective Action Required
05/21/2007
None LOWER SINKS TO NO MORE THAN 34" LOWER MIRRORS TO 40" OFF OF FLOOR TO REFLECTIVE EDGE. PRE FINAL
Rough Framing Inspection - Commercial Passed 05/25/2007
Correction
Resolved
05/25/2007
PLANS
Rough Plumbing Inspection - Commercial Passed 05/25/2007
Correction
Resolved
05/25/2007
None
Occupancy Inspection - Codes Commercial Failed 05/25/2007
Correction
Resolved
05/25/2007
None TCO 10 DAY
Correction
Resolved
05/25/2007
Receive Fire Department approval
Correction
Corrective Action Required
05/25/2007
Receive Water Utilities Approval
Gas Piping Inspection - Commercial Passed 05/30/2007
Correction
Resolved
05/30/2007
None
Gas Service Inspection - Commercial Passed 05/30/2007
Correction
Resolved
05/30/2007
None
Occupancy Inspection - Codes Commercial Failed 06/01/2007
Correction
Resolved
06/01/2007
None
Occupancy Inspection - Codes Commercial Passed 06/05/2007
Correction
Resolved
06/05/2007
Receive Water Utilities Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home