Permit Application Status

B0501764


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0501764
Building Permit - Commercial
Final Completion
RAINTREE VILLAGE SHOPPING CENTER LLC
NEW SHELL BUILDING
NEW SPEC OFFICE/RETAIL/DINING STRIP BUILDING
09/30/2005
02/08/2006
08/07/2006
05/09/2007
Locations
Contacts
ARCHER ENGINEERS, Address:3731 NE TROON DR  
CAPITAL CONSTRUCTION SERVICES, LLC, Address:839 NE WOODS CHAPEL RD  
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
PROFESSIONAL SERVICES INDUSTRIES, Address:1211 W CAMBRIDGE CIRCLE DRIVE  
RAINTREE VILLAGE SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 400  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/19/2006 10/29/2010
Correction

Fire Department- Provide a complete code analysis for the project.
Correction

Road Improviements. The Developer shall design, engineer and construct the Road Improvements. The City shall issue no temporary or final Certificates of Occupancy for any of the Development until the City or MoDOT, as appropriate, has issued a Certificate of Substantial Completion for the Road Improvements (the "Certificate of Completion").
Correction

Codes Administration - A completed code analysis was not provided.
Correction

Codes Administration - The size and location of the domestic water service meter is not indicated on the plans.
Correction

Codes Administration - The project cost for this structure has not been provided.
Correction

Codes Administration - I am unable to locate information for the accessible curb ramps.
Correction

Codes Administration - Notes on the elevations found on Sheets A3.1 and A3.2 indicate that guards and curbs will be provided on the sloped sections of the sidewalks and that deails are located on the civil drawings. I am unable to locate the details on the civil drawings.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Codes Administration - The possible tenant finish address for this project are 837, 841, 845, 849, 853, 857, 861, 865, 869, 873, 877, 881, 885, 889, 891, 893, 895, 897, 899 SW Lemans Ln.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - 2003 IBC 1704.1.1 - Building permit requirements. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

Codes Administration - 2003 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Permanent ladders installed to provide the required access shall comply with the followin minimum design criteria: 1. The side railings shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. 3. Ladders shall have a toe spacing not less tha 6 inches (152 mm) deep. 4. Ther shall be a minimum of 18 inches 9457 mm) between rails. 5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load. 6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $4,802.00 $4,802.00 Paid 02/08/2006
24 BLDG Plan Check Fees $100.00 $100.00 Paid 02/08/2006
25 Electrical Permit Fee $215.00 $215.00 Paid 02/08/2006
25 Mechanical Permit Fees $186.00 $186.00 Paid 02/08/2006
25 Plumbing Permit Fees $42.50 $42.50 Paid 02/08/2006
84 Water Meters $625.00 $625.00 Paid 02/08/2006
85 Water Taps $13,670.00 $13,670.00 Paid 02/08/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Partial 02/09/2006
Correction
Partial Correction
02/09/2006
JOB SITE TEMP OK TO RELEASE JOB SITE TEMP METER ONLY
Underslab Plumbing Inspection - Commercial Passed 03/24/2006
Correction
Resolved
03/24/2006
SHELL BUILDING 10 UNITS
Erosion Control Inspection Residential Failed 03/24/2006
Correction
Corrective Action Required
03/24/2006
Erosion Control REINSTALL FENCE AT SOUTHWEST CORNER ASAP
Sewer Service Inspection Passed 03/24/2006
Correction
Resolved
03/24/2006
None APPROVED FROM BUILDING TO STUB
Underslab Electrical Inspection - Commercial Failed 03/24/2006
Correction
Partial Correction
03/24/2006
SERVICE PANELS RECALL FOR WEST UNITS EAST PORTION
Piers/Caissons Inspection - Commercial Passed 03/24/2006
Correction
Resolved
03/24/2006
None 2 NORTH PIERS OK
Underslab Electrical Inspection - Commercial Passed 03/31/2006
Correction
Resolved
03/31/2006
SERVICE PANELS UNDER SLAB ELECTRICAL APPROVED
Electrical Service Inspection Partial 04/04/2006
Correction
Corrective Action Required
04/04/2006
Grounding Electrode Installation (IRC) FOOTING GROUND APPROVED WATERLINE UNDERSLAB APPROVED CHECK CONNECTION LATER DATE
Water Service Inspection Passed 04/06/2006
Correction
Resolved
04/06/2006
None
Water Service Inspection - Commercial Request Complete 4/6/2006 4/6/2006 04/06/2006
Footing Inspection - Commercial Failed 05/24/2006
Correction
Partial Correction
05/24/2006
None SOUTHEAST TRASH BIN OK
Retaining Wall Inspection Failed 05/24/2006
Correction
Partial Correction
05/24/2006
FOOTING SOUTH EAST WALL
Retaining Wall Inspection Request Complete 5/23/2006 5/24/2006 05/24/2006
Footing Inspection - Commercial Failed 05/26/2006
Correction
Partial Correction
05/26/2006
None SOUTHEAST TRASH BIN OK NORTHEAST TRASH BIN FOOTING APPROVED
Retaining Wall Inspection Passed 06/21/2006
Correction
Resolved
06/21/2006
FOOTING ALL PORTIONS OF FOOTING APPROVED// 6/21/06 SOUTH EAST WALL
Correction
Resolved
06/21/2006
None FROM TRASH BEN TO WEST - APPROVED FROM TRASH BEN SOUTH TO PRIOR FOOTING- APPROVED NORTH WEST CORNER
Footing Inspection - Commercial Failed 06/29/2006
Correction
Partial Correction
06/29/2006
None SOUTHEAST TRASH BIN OK. NORTHEAST TRASH BIN FOOTING APPROVED. NORTHWEST TRASH BIN FOOTING- APPROVED
Retaining Wall Inspection Passed 08/01/2006
Correction
Resolved
08/01/2006
None SOUTHWEST SIDE- APPROVED SOUTHSIDE - APPROVED
Underground Electrical Inspection - Commercial Failed 08/01/2006
Correction
Partial Correction
08/01/2006
LIGHT POLES CENTER 6 LOT LIGHTS TRENCH - APPROVED
Underground Electrical Inspection - Commercial Request Complete 7/31/2006 8/1/2006 08/01/2006
Sidewalk Inspection Passed 08/10/2006
Sidewalk Inspection Passed 08/11/2006
Piers/Caissons Inspection - Commercial Failed 08/17/2006
Correction
Corrective Action Required
08/17/2006
EAST LIGHT POLE PIERS INSTALL AS PER PLANS OR REVISE PLANS ( E3) 6 EAST LIGHT POLE BASE
Underground Electrical Inspection - Commercial Passed 08/17/2006
Correction
Resolved
08/17/2006
LIGHT POLES CENTER 6 LOT LIGHTS TRENCH - APPROVED ALL TRENCH FOR POLES APPROVED
Underground Electrical Inspection - Commercial Request Complete 8/16/2006 8/17/2006 08/17/2006
Footing Inspection - Commercial Passed 08/21/2006
Correction
Resolved
08/21/2006
None SOUTHEAST ENCLOSER OK. NORTHEAST TRASH ENCLOSER APPROVED. NORTHWEST TRASH ENCLOSER- APPROVED SOUTHWEST TRANSH ENCLOSER- APPROVED
Piers/Caissons Inspection - Commercial Passed 08/21/2006
Correction
Resolved
08/21/2006
EAST LIGHT POLE PIERS OK, 8 POLE BASES 8 EAST LIGHT POLE BASE
Rough Framing Inspection - Commercial Failed 09/05/2006
Correction
Corrective Action Required
09/05/2006
Roof Truss Bracing (IRC) 1. CLARIFY LOCATION OF 2X4'S AT END TRUSS. 2. TRUSS TIES. 3. INSTALL WALL TIES ALSO. EAST END CANOPY
Correction
Corrective Action Required
09/05/2006
Roof Truss Bracing (IRC) 1. SCREW PATTERN SHEER WALL. 2. TRUSS TIES 3. BOTTOM CORD BRACING. 4. FRONT WALL NAIL PATTERN ON PLYWOOD. CENTER TOP ROOF
Rough Framing Inspection - Commercial Request Complete 9/1/2006 9/5/2006 09/05/2006
Piers/Caissons Inspection - Commercial Passed 09/06/2006
Correction
Resolved
09/06/2006
LIGHT POLE PIERS 5 SOUTH LIGHT POLES 2 NORTH OF 813 COFFEE HOUSE SOUTH POLES
Electrical Service Inspection Passed 09/07/2006
Correction
Resolved
09/07/2006
Grounding Electrode Installation (IRC) HOUSE PANEL APPROVED
Correction
Resolved
09/07/2006
JOB SITE TEMP
Piers/Caissons Inspection - Commercial Passed 09/07/2006
Correction
Resolved
09/07/2006
LIGHT POLE BASE 4 NORTH PIERS
Rough Framing Inspection - Commercial Passed 09/21/2006
Correction
Resolved
09/21/2006
Roof Truss Bracing (IRC)
Correction
Resolved
09/21/2006
Roof Truss Bracing (IRC)
Rough Framing Inspection - Commercial Request Complete 9/20/2006 9/21/2006 09/21/2006
Driveway Inspection Passed 10/02/2006
All Rough Inspection - Commercial Passed 10/09/2006
Correction
Resolved
10/09/2006
OK TO ROCK OK TO ROCK WALL
Rough Electrical Inspection - Commercial Failed 10/09/2006
Correction
Corrective Action Required
10/09/2006
Wiring Installation and Support (IRC) -SECURE CABLE EVERY 6FT ALONG CEILING TRUSS LATERAL BRACE ALONG REAR WALL AND WITHIN 12" OF BOXES AND FIXTURES
Driveway Inspection Passed 10/24/2006
Gas Piping Inspection - Commercial Failed 11/01/2006
Correction
Corrective Action Required
11/01/2006
ROOF TOP EAST 8 GAS LINES NO TEST MIDDLE 8 APPROVED WEST 3 UNITS NO TEST
Gas Service Inspection - Commercial Partial 11/01/2006
Correction
Partial Correction
11/01/2006
Gas Test Pressure (IRC) EAST 8 NOT INSPECTED MIDDLE 8 APPROVED WEST 3 NOT INSPECTED
Gas Piping Inspection - Commercial Passed 11/02/2006
Correction
Resolved
11/02/2006
ROOF TOP EAST 8 GAS LINES APPROVED MIDDLE 8 APPROVED WILL INSPECT 3 WEST UNITS AT TENANT FINISH
Gas Service Inspection - Commercial Passed 11/02/2006
Correction
Resolved
11/02/2006
Gas Test Pressure (IRC) EAST 8 APPROVED MIDDLE 8 APPROVED WEST 3 NOT INSTALLED , WILL INSPECT AT TENANT FINISH
Final Inspection - Commercial Failed 12/01/2006
Correction
Corrective Action Required
12/01/2006
TYPE YOUR OWN TEXT TERMINATE ELECTRICAL OVER DRIVE THROUGH EAST EXTERIOR WALL ELECTRICAL
Correction
Corrective Action Required
12/01/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
12/01/2006
Receive Water Utilities Approval
Correction
Corrective Action Required
12/01/2006
Receive Public Works Approval
Correction
Corrective Action Required
12/01/2006
Receive Fire Department approval
Final Inspection - Commercial Failed 12/12/2006
Correction
Corrective Action Required
12/12/2006
Receive Planning & Development Approval OK FOR TCO 12-8-06
Correction
Resolved
12/12/2006
Receive Water Utilities Approval
Final Inspection - Commercial Passed 04/24/2007
Correction
Resolved
04/24/2007
Receive Fire Department approval
Correction
Resolved
04/24/2007
Receive Public Works Approval
Correction
Resolved
04/24/2007
Receive Planning & Development Approval
Correction
Resolved
04/24/2007
TYPE YOUR OWN TEXT
Rough Electrical Inspection - Commercial Passed 05/08/2007
Correction
Resolved
05/08/2007
Wiring Installation and Support (IRC)
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home