Permit Application Status

B0500947


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500947
Building Permit - Commercial
Certificate of Occupancy
UMB BANK NA
ADDITION COMMERCIAL
BUILDING ADDITION
06/06/2005
06/30/2005
12/27/2005
04/06/2006
Locations
Contacts
THE KONRATH GROUP, Address:801 WALNUT ST STE 402  
GLPM ARCHITECTS INC, Address:1001 NEW HAMPSHIRE  
UMB BANK NA, Address:1010 GRAND BLVD  
T & J REAL ESTATE LLC, Address:11000 S FRONTAGE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/03/2005 10/29/2010
Correction

Codes Administration - Specifications are not provided for the electrical installation.
Correction

Codes Administration - 2003 IBC 1008.1.4 - Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit veritical in 12 units horizontal (2-percent slope).
Correction

Codes Administration - 2003 IBC 1008.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater than 0.25 inch at doorways shall beveled with a slope not greater than one unit vertical in two units horizontal.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 302.1.1 - Incidental use areas. Spaces which are incidental to the main occupancy shall be separated or protected, or both, in accordance with Table 302.1.1 or the building shall be classified as a mixed occupancy and comply with Section 302.3. Areas that are incidental to the main occupancy shall be classified in accordance with the main occupancy of the portion of the building in which the incidental use area is located.
Correction

Codes Administration - Copies of the engineered steel building package were not provided at the time of permit application.
Correction

Codes Administration - Information on the protection of the pentrations of the existing fire-resistive assembly has not been provided.
Correction

Codes Administration - The structural calculations for this project have not been provided.
Correction

Codes Administration - The design loads for this project have not been provided.
Correction

Codes Administration - A bath fan is not shown in the new restroom.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $977.00 $977.00 Paid 06/30/2005
24 BLDG Plan Check Fees $36.25 $36.25 Paid 06/30/2005
25 Electrical Permit Fee $75.00 $75.00 Paid 06/30/2005
25 Mechanical Permit Fees $31.50 $31.50 Paid 06/30/2005
25 Plumbing Permit Fees $29.00 $29.00 Paid 06/30/2005
89 Sewer Tap Fees $60.00 $60.00 Paid 06/30/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Passed 07/12/2005
Water Service Inspection - Commercial Request Complete 7/12/2005 7/12/2005 07/12/2005
Footing Inspection - Commercial Passed 07/14/2005
Correction
Resolved
07/14/2005
None INSTALLED PER PLAN
Underground Electrical Inspection - Commercial Partial 07/22/2005
Correction
Partial Correction
07/22/2005
TEXT APPROVED TO COVER ELECTRIC SERVICE TO TRANSFORMER. REPAIR BROKEN CONDUIT SERVING EXISTING LIGHT POLE. LEAVE REPAIR EXPOSED FOR INSPECTION.
Underground Electrical Inspection - Commercial Request Complete 7/21/2005 7/22/2005 07/22/2005
Underground Electrical Inspection - Commercial Partial 08/02/2005
Correction
Partial Correction
08/02/2005
TEXT APPROVED TO COVER ELECTRIC SERVICE TO TRANSFORMER. REPAIR TO BROKEN CONDUIT REPAIRED AND APPROVED. NOTE: CONCRETE ENCASEMENT REQUIRED FOR MAIN SERVICE CONDUIT. VIDEO TAPE OR PICTURES OF PROCESS WILL BE ACCEPTIBLE.
Rough Framing Inspection - Commercial Request Complete 8/1/2005 8/2/2005 08/02/2005
Underground Electrical Inspection - Commercial Request Complete 8/1/2005 8/2/2005 08/02/2005
Underslab Plumbing Inspection - Commercial Passed 08/26/2005
Rough Framing Inspection - Commercial Passed 09/02/2005
Correction
Resolved
09/02/2005
COMMENTS APPROVED FOR ROCK CONTINGENT UPON PROVIDE (2) NAIL GUARDS AS DISCUSSED ON SITE AND PROTECTING WATER PIPE FROM DISSIMILAR METAL CONTACT THROUGH TOP PLATE
Rough Framing Inspection - Commercial Request Complete 9/1/2005 9/2/2005 09/02/2005
Occupancy Inspection - Codes Commercial Failed 10/28/2005
Correction
Corrective Action Required
10/28/2005
Panel Circuit Identification (IRC) LABEL NEW ELECTRICAL PANEL TO MATCH CIRCUIT IDENTIFICATION AT EXISTING PANEL.
Correction
Corrective Action Required
10/28/2005
ADA RESTROOM INSULATE ALL PIPING BENEATH ADA LAVATORY. ADA RESTROOM
Correction
Corrective Action Required
10/28/2005
FIRE SEPARATION WALL BETWEEN SHOP & SHOW ROOM IS TO BE 2 HR RATED. 1- DOOR AND FRAME TO HAVE APPROPRIATE FIRE RATING. 2- FIRE CAULK ALL PENETRATIONS.
Correction
Corrective Action Required
10/28/2005
Through Penetrations (IRC) SEAL NG PIPING ENTRY EXTERIOR
Correction
Corrective Action Required
10/28/2005
UNDERGROUND ELECTRICAL CARRIED OVER FROM PREVIOUS INSPECTION: PROVIDE VERIFICATION OF ENCASEMENT OF TRANSFORMER FEEDS. CONCRETE ENCASEMENT REQUIRED FOR MAIN SERVICE CONDUIT. VIDEO TAPE OR PICTURES OF PROCESS WILL BE ACCEPTIBLE.
Correction
Corrective Action Required
10/28/2005
Grading (IRC) 1- PROVIDE FINAL GRADE AND PERMANENT EROSION CONTROL. 2- ROOF DRAIN DISCHARGE TO EXTEND MIN. 36" AWAY FROM FOUNDATION EXTERIOR
Correction
Corrective Action Required
10/28/2005
REQUIRED PAYMENT OF TAXES PAYMENT OF ALL TAXES REQUIRED PRIOR TO ISSUANCE OF TEMPORARY OR FINAL OCCUPANCY. DO NOT OCCUPY. DO NOT STORE EQUIPMENT, VEHICLES, FURNITURE, WARES, ETC.
Correction
Resolved
10/28/2005
None
Correction
Corrective Action Required
10/28/2005
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
10/28/2005
Receive Fire Department approval UNDER SEPARATE COVER
Underground Electrical Inspection - Commercial Passed 10/28/2005
Correction
Resolved
10/28/2005
TEXT MOVED TO OCCUPANCY
Occupancy Inspection - Codes Commercial Failed 11/01/2005
Correction
Resolved
11/01/2005
30 DAY TCO
Correction
Resolved
11/01/2005
Panel Circuit Identification (IRC)
Correction
Corrective Action Required
11/01/2005
ADA RESTROOM INSULATE ALL PIPING BENEATH ADA LAVATORY. ADA RESTROOM
Correction
Resolved
11/01/2005
FIRE SEPARATION
Correction
Resolved
11/01/2005
Through Penetrations (IRC) EXTERIOR
Correction
Corrective Action Required
11/01/2005
Grading (IRC) 1- PROVIDE FINAL GRADE AND PERMANENT EROSION CONTROL. 2- ROOF DRAIN DISCHARGE TO EXTEND MIN. 36" AWAY FROM FOUNDATION EXTERIOR
Correction
Resolved
11/01/2005
REQUIRED PAYMENT OF TAXES
Correction
Corrective Action Required
11/01/2005
Receive Planning & Development Approval 11/1/05 - ISSUES PENDING UNDER SEPARATE COVER
Occupancy Inspection - Codes Commercial Failed 12/12/2005
Correction
Resolved
12/12/2005
Grading (IRC) EXTERIOR
Correction
Resolved
12/12/2005
UNDERGROUND ELECTRICAL
Correction
Resolved
12/12/2005
ADA RESTROOM ADA RESTROOM
Occupancy Inspection - Codes Commercial Passed 04/05/2006
Correction
Resolved
04/05/2006
Receive Fire Department approval VERBAL APPROVAL FROM CHIEF EDEN - 4/5/06 - 11:50
Correction
Resolved
04/05/2006
Receive Planning & Development Approval APPROVED VIA LETTER DATED 3/17/06
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home