Permit Application Status

B0500933


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500933
Building Permit - Commercial
Certificate of Occupancy
DAHMER REALTY LP
ALTERATION COMMERCIAL
UPPER FLOOR OFFICE ADDITION
06/01/2005
06/24/2005
12/21/2005
09/27/2005
Locations
Contacts
DAHMER CONSTRUCTION, INC., Address:18707 E. 191ST ST  
DAHMER REALTY LP, Address:2301 NE INDEPENDENCE AVE  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/28/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2003 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches (178 mm) maximum and 4 inches (102 mm) minimum. Stair tread depths shall be 11 inches (279 mm) minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 0.375 inch 99.5 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm). Winder treads shall have a minimum tread depth of 11 inches (279 mm) measured at a right angle to the tread's leading edge at a point 12 inches (305 mm) fron the side where the treads are narrower and a minimum tread depth of 10 inches (254 mm). The greatest winder tread depth at the 12 inch (305 mm) walk line within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm).
Correction

Codes Administration - 2003 IBC 1012.1 - Where required. Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 30 inches (762 mm) above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with Section 1607.7. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 30 inches (762 mm) above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in Section 1607.7. In addition, guards are required at retaining walls over 30" above grade when walking surfaces are within ten (10) feet of the high side of the retaining wall. (As amended by the City of Lee's Summit)
Correction

Fire Department- Provide emergency lighting per Codes Administration comments.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 304.9 - Clearance from grade. Equipment and appliances in stalled at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches above adjoining grade.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $212.00 $212.00 Paid 06/24/2005
24 BLDG Plan Check Fees $17.00 $17.00 Paid 06/24/2005
25 Electrical Permit Fee $77.58 $77.58 Paid 06/24/2005
25 Mechanical Permit Fees $30.50 $30.50 Paid 06/24/2005
25 Plumbing Permit Fees $7.00 $7.00 Paid 06/24/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 07/26/2005
Correction
Corrective Action Required
07/26/2005
COMPLETE NAILING OF METAL STUDS
Correction
Corrective Action Required
07/26/2005
Fireblocking (IRC) PROVIDE FIRE BLOCKING MATERIAL AT ALL FLOOR TO FLOOR PENETRATIONS.
Correction
Partial Correction
07/26/2005
None DO NOT ROCK. OK TO INSULATE CONTIGENT UPON LEAVING AREAS OF VIOLATION EXPOSED.
All Rough Inspection - Commercial Passed 07/28/2005
Correction
Resolved
07/28/2005
COMPLETE NAILING OF METAL STUDS
Correction
Resolved
07/28/2005
Fireblocking (IRC)
Correction
Resolved
07/28/2005
None OK TO INSULATE OK TO ROCK
Above Ceiling Inspection Failed 08/31/2005
Correction
Corrective Action Required
08/31/2005
DUCT SUPPORTS FLEXIBLE DUCTWORK TO BE SUPPORTED WITH MINIMUM 1-1/2" STRAPS AT MAXIMUM 5'-0" INTERVALS PER: SMACNA, AIR DIFFUSION COUNCIL AND MANUFACTURER'S INSTRUCTIONS. THROUGHOUT
Correction
Corrective Action Required
08/31/2005
LIGHT FIXTURE SUPPORT SUPPORT LIGHT FIXTURES FROM STRUCTURE. DO NOT SUPPORT FROM PIPES. EAST CLOSET
Correction
Corrective Action Required
08/31/2005
ENGINEERED DOCUMENTS APPROVED ENGINEER'S PLANS TO BE ON SITE FOR ALL INSPECTIONS.
Correction
Corrective Action Required
08/31/2005
None DO NOT INSTALL CEILING TILES
Above Ceiling Inspection Passed 09/01/2005
Correction
Resolved
09/01/2005
DUCT SUPPORTS THROUGHOUT
Correction
Resolved
09/01/2005
LIGHT FIXTURE SUPPORT EAST CLOSET
Correction
Resolved
09/01/2005
ENGINEERED DOCUMENTS
Correction
Resolved
09/01/2005
None OK TO COVER
Gas Piping Inspection - Commercial Passed 09/09/2005
Gas Service Inspection - Commercial Failed 09/09/2005
Correction
Corrective Action Required
09/09/2005
Gas Test Pressure (IRC) PROVIDE GAUGE FOR GAS PRESSURE TEST. MIN. 15PSI FOR 10 MIN.
Occupancy Inspection - Codes Commercial Failed 09/09/2005
Correction
Resolved
09/09/2005
None APPROVED BY NEIL ULLERY
Correction
Corrective Action Required
09/09/2005
Receive Planning & Development Approval NOTE: EXTERIOR A/C UNIT SHALL BE SCREENED FROM VIEW PER P&D REQUIREMENTS. UNDER SEPARATE COVER
Correction
Corrective Action Required
09/09/2005
GAS PIPING GAS PRESSURE TEST MUST BE COMPLETED AND APPROVED PRIOR TO OCCUPANCY
Correction
Corrective Action Required
09/09/2005
Through Penetrations (IRC) 1- CAULK TOP OF A/C DISCONNECT SWITCH. 2- CAULK REFRIGERANT PIPING PENETRATION EXTERIOR
Correction
Corrective Action Required
09/09/2005
SECURE A/C DISC. SWITCH CONDUIT TO STRUCTURE EXTERIOR
Correction
Corrective Action Required
09/09/2005
Panel Circuit Identification (IRC) 1- LABEL PANEL COVER TO MATCH DISCONNECT DEVICE (IN OTHER PANEL?) 2- LABEL CIRCUITS IN PERMANENT MANNER. NO PENCIL MEZZANINE
Correction
Corrective Action Required
09/09/2005
None DO NOT OCCUPY. OK TO STORE FURNITURE AND OFFICE EQUIPMENT.
Gas Service Inspection - Commercial Passed 09/13/2005
Correction
Resolved
09/13/2005
Gas Test Pressure (IRC)
Occupancy Inspection - Codes Commercial Failed 09/13/2005
Correction
Resolved
09/13/2005
GAS PIPING
Correction
Resolved
09/13/2005
Through Penetrations (IRC) EXTERIOR
Correction
Resolved
09/13/2005
SECURE A/C DISC. SWITCH CONDUIT TO STRUCTURE EXTERIOR
Correction
Resolved
09/13/2005
Panel Circuit Identification (IRC) MEZZANINE
Correction
Resolved
09/13/2005
None 30 DAY TCO
Occupancy Inspection - Codes Commercial Passed 09/26/2005
Correction
Resolved
09/26/2005
Receive Planning & Development Approval
Documents & Images

No documents are currently available for viewing.

Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home