Permit Application Status

B0500807


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500807
Building Permit - Commercial
Certificate of Occupancy
LBC INVESTMENTS LLC
CHANGE OF TENANT
OCONNER DISTRIBUTION TENANT FINISH
05/16/2005
06/23/2005
12/20/2005
03/22/2006
Locations
Contacts
HIRST AND ASSOCIATES PC, Address:621 NE WOODS CHAPEL RD  
RIVER OAK CONSTRUCTION, Address:621 NE WOODS CHAPEL RD  
LBC INVESTMENTS LLC, Address:PO BOX 7258  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/12/2005 10/29/2010
Correction

Codes Administration - The plans indicate that the north demising wall is existing. It is my understanding, and previous plans for the north tenant space show this as a chain link fence.
Correction

Codes Administration - The door schedule shows door 16 to be a 36 inch door but the plans indicate that it is smaller than that.
Correction

Codes Administration - The plans indicate that Door 13 is to swing into the retail area. The code requires the doors to swing in the direction of travel when the occupant load exceeds 50. The code also requires that a second exit be provided with 75 of common path of travel. The only way to meet both of these requirements is to reverse the swing of Door 13. The warehouse is not seen to be a more hazardous area and exiting through this space is allowed as long as a clear path of travel is provided.
Correction

Codes Administration - As there are no proposed alterations for the mezzanine, this space is not being reviewed under this permit. If the space is altered in the future, additional exiting systems may be required.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department- Provide information on the method of storage in the warehouse.
Correction

Fire Department- If dividing the space affects the smoke ventilation system for the building. The panel in the fire control room needs to be relabeled.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- The use of lift trucks shall be in accordance with IFC Section 309.
Correction

Codes Administration - Occupancy type S-2 does not allow for storage of any type of combustible materials.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

905.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section and as required by the Code Offical. Fire hose threads used in connection with standpipe systems shall comply with NFPA 1963 or as otherwise approved and shall be compatible with fire department hose threads. The location of fire department hose connections shall be approved. In build-ings used for high-piled combustible storage, fire protection shall be in accordance with Chapter 23.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $227.00 $227.00 Paid 06/23/2005
24 BLDG Plan Check Fees $17.50 $17.50 Paid 06/23/2005
25 Electrical Permit Fee $164.94 $164.94 Paid 06/23/2005
25 Mechanical Permit Fees $59.50 $59.50 Paid 06/23/2005
25 Plumbing Permit Fees $35.00 $35.00 Paid 06/23/2005
89 Sewer Tap Fees $150.00 $150.00 Paid 06/23/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/12/2005
All Rough Inspection - Commercial Failed 07/12/2005
Correction
Partial Correction
07/12/2005
SEE TEXT IN-WALL INSPECTION COVERS EAST AREA ONLY. WAREHOUSE AND NW RR NOT INSPECTED. OK TO COVER WALLS IN EAST AREA EXCEPT WEST DEMISING WALL (WAITING ON DWV NAIL GUARDS.)
Correction
Corrective Action Required
07/12/2005
Water/DWV Preotection Against Physical Damage (IRC) PROVIDE NAIL GUARDS AT DWV PIPING. DEMISING WALL
Foundation Inspection - Commercial Passed 07/13/2005
Footing Inspection - Commercial Failed 07/13/2005
Correction
Corrective Action Required
07/13/2005
COMMENTS FOOTING POURED PRIOR TO INSPECTION. ARCHITECT HAS DIGITAL PICTURES.
All Rough Inspection - Commercial Partial 07/15/2005
Correction
Partial Correction
07/15/2005
SEE TEXT IN-WALL INSPECTION COVERS EAST AREA ONLY. WAREHOUSE AND NW RR NOT INSPECTED. OK TO COVER WALLS IN EAST AREA.
Correction
Resolved
07/15/2005
Water/DWV Preotection Against Physical Damage (IRC) NOTE: PROVIDE NAIL GUARDS AT NW RESTROOM DWV THRU TOP PLATE. (TO BE INSPECTED AT LATER DATE) DEMISING WALL
Rough Electrical Inspection - Commercial Failed 07/20/2005
Correction
Corrective Action Required
07/20/2005
Grounding Conductor Continuity (IRC) REPLACE WIRE NUT CONNECTING GROUND WIRES WITH APPROVED GREEN WIRE NUT OR BUCHANNAN CRIMP. WOMEN'S RR #111
All Rough Inspection - Commercial Partial 07/20/2005
Correction
Partial Correction
07/20/2005
SEE TEXT IN-WALL INSPECTION COVERS EAST AREA ONLY. WAREHOUSE NOT INSPECTED. OK TO COVER WALLS IN EAST AREA INCLUDING WOMEN'S RR #111.
Electrical Service Inspection Partial 08/04/2005
Correction
Partial Correction
08/04/2005
COMMENTS 1- INSTALLATION OF GROUND CONDUCTORS AT DISC. SW. CONFLICTS WITH APPROVED ENGINEER'S DOCUMENTS. PROVIDED LETTER FROM ENGINEER. 2- SERVICE PANELS AND TRANSFORMER APPROVED.
Above Ceiling Inspection Failed 08/24/2005
Correction
Corrective Action Required
08/24/2005
SEE COMMENTS REMOVE ALL CEILING TILES AND RESCHEDULE INSPECTION.
All Rough Inspection - Commercial Passed 08/25/2005
Correction
Resolved
08/25/2005
SEE TEXT
Above Ceiling Inspection Passed 08/25/2005
Correction
Resolved
08/25/2005
SEE COMMENTS OK TO COVER
Occupancy Inspection - Codes Commercial Failed 09/01/2005
Correction
Resolved
09/01/2005
FIRE DEPARTMENT APPROVAL REPORT PER NEIL ULLERY
Correction
Corrective Action Required
09/01/2005
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Resolved
09/01/2005
None 30 DAY TCO OK TO STORE FURNITURE AND EQUIPMENT
Correction
Resolved
09/01/2005
PROVIDE ADDRESS NUMBERS ON FRONT DOOR
Correction
Corrective Action Required
09/01/2005
MECHANICAL 1- EXHAUST FAN IN RR #111 TO BE DUCTED TO EXTERIOR OR INTO EXISTING EXHAUST OF ADEQUATE SIZE. 2- CALL FOR INSPECTION OF WAREHOUSE HVAC CURRENTLY ON BACKORDER.
Correction
Resolved
09/01/2005
ELECTRICAL
Rough Electrical Inspection - Commercial Passed 09/01/2005
Correction
Resolved
09/01/2005
Grounding Conductor Continuity (IRC) WOMEN'S RR #111
Gas Service Inspection - Commercial Failed 09/08/2005
Correction
Corrective Action Required
09/08/2005
Gas Test Pressure (IRC) INSUFFICIENT PRESSURE AT GAUGE. MINIMUM 15 PSI FOR 10 MIN. NOTE: METER WILL BE REQUIRED TO BE LABELED TO MATCH SUITE PRIOR TO ISSUING FINAL OCCUPANCY.
Gas Service Inspection - Commercial Partial 09/13/2005
Correction
Partial Correction
09/13/2005
Gas Test Pressure (IRC) NOTE: METER WILL BE REQUIRED TO BE LABELED TO MATCH SUITE PRIOR TO ISSUING FINAL OCCUPANCY.
Occupancy Inspection - Codes Commercial Failed 10/13/2005
Correction
Corrective Action Required
10/13/2005
MECHANICAL 1- EXHAUST FAN IN RR #111 TO BE DUCTED TO EXTERIOR OR INTO EXISTING EXHAUST OF ADEQUATE SIZE. 2- WAREHOUSE UNIT INSTALLED WITHOUT FLUE. PROVIDE INSTALLATION MANUAL FOR NEXT INSPECTION. DO NOT RUN UNIT.
Occupancy Inspection - Codes Commercial Failed 02/27/2006
Correction
Corrective Action Required
02/27/2006
MECHANICAL 1- EXHAUST FAN IN RR #111 TO BE DUCTED TO EXTERIOR OR INTO EXISTING EXHAUST OF ADEQUATE SIZE.
Gas Service Inspection - Commercial Passed 03/22/2006
Correction
Resolved
03/22/2006
Gas Test Pressure (IRC)
Footing Inspection - Commercial Passed 03/22/2006
Correction
Resolved
03/22/2006
COMMENTS
Occupancy Inspection - Codes Commercial Passed 03/22/2006
Correction
Resolved
03/22/2006
MECHANICAL
Correction
Resolved
03/22/2006
Receive Planning & Development Approval
Electrical Service Inspection Passed 03/22/2006
Correction
Resolved
03/22/2006
COMMENTS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home