B0500797


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500797
Building Permit - Commercial
Certificate of Occupancy
PREMIERLIFE REAL ESTATE HOLDING
NEW TENANT FINISH
BUSHNELL PERFORMANCE OPTICS LLC
05/13/2005
06/06/2005
12/03/2005
07/27/2005
Locations
Contacts
A L HUBER, Address:10770 EL MONTE  
PREMIERLIFE REAL ESTATE HOLDING, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/09/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- The plans indicate the building is sprinklered and it is not.
Correction

Codes Administration - Sheet T1 indicates that this building is provided with a sprinkler system. Our records do not indicate that this building has a sprinkler system.
Correction

Codes Administration - This permit does not include mechanical, electrical or plumbing work. Work in these areas will be added to the permit as plans are provided.
Correction

Codes Administration - The address assigned to this tenant space is 445 NW Murray Rd.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

Codes Administration - 2003 IPC 403.6 - Public facilities. Customers, patrons and visitors shall be provided with public toilet facilites in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilities and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $278.00 $278.00 Paid 06/06/2005
24 BLDG Plan Check Fees $19.20 $19.20 Paid 06/06/2005
25 Electrical Permit Fee $92.17 $92.17 Paid 06/06/2005
25 Mechanical Permit Fees $24.00 $24.00 Paid 06/06/2005
25 Plumbing Permit Fees $31.00 $31.00 Paid 06/06/2005
89 Sewer Tap Fees $150.00 $150.00 Paid 06/06/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 06/09/2005
Correction
Partial Correction
06/09/2005
None WALLS ONLY
Erosion Control Inspection Residential Passed 06/09/2005
Underslab Plumbing Inspection - Commercial Passed 06/09/2005
Underslab Electrical Inspection - Commercial Passed 06/09/2005
Rough Framing Inspection - Commercial Failed 06/09/2005
Correction
Partial Correction
06/09/2005
None WALL FRAMING NOT COMPLETED C.5 LINE 3.5 TO 5. CALL FOR NSPECTION WHEN COMPLETED. OK TO ROCK INSPECTED WALLS.
Rough Framing Inspection - Commercial Request Complete 6/8/2005 6/9/2005 06/09/2005
Rough Framing Inspection - Commercial Passed 06/14/2005
Correction
Resolved
06/14/2005
None
Rough Plumbing Inspection - Commercial Passed 06/14/2005
Correction
Resolved
06/14/2005
PROTECT COPPER PIPE FROM STEEL EDGES AT TOP TRACK PENETRATIONS GROMMETS OR SPRAY FOAM
Correction
Resolved
06/14/2005
SHIELD-PLATE PVC PIPE @ PENETRATIONS THEN OK TO COVER OF STUDS/PLATES WHERE < 1-1/2" FROM FACE
Underslab Electrical Inspection - Commercial Passed 06/14/2005
Correction
Resolved
06/14/2005
PVC CONDUIT + BOX FOR FLOOR RECEPTACLE
Rough Electrical Inspection - Commercial Passed 06/14/2005
Correction
Resolved
06/14/2005
None
Electrical Service Inspection Passed 06/14/2005
Correction
Resolved
06/14/2005
ELECTRICAL SERVICE INSTALLATION 200 AMP RELEASE SERVICE
All Rough Inspection - Commercial Passed 06/14/2005
Rough Framing Inspection - Commercial Request Complete 6/13/2005 6/14/2005 06/14/2005
Above Ceiling Inspection Passed 06/29/2005
Correction
Resolved
06/29/2005
ABOVE-CEILING SYSTEMS ROUGH THEN OK TO COVER WHEN READY EXCEPT AT RR106 WHERE MC CABLE IS COILED UNTERMINATED. CLOSE UNUSED JB KNOCKOUT SEE AT B.9/1.3
Gas Service Inspection - Commercial Failed 07/13/2005
Correction
Corrective Action Required
07/13/2005
GAS LINE PRESSURE TEST REQUIRED PRIOR TO RELEASE OF SERVICE METER INSTALL
Occupancy Inspection - Codes Commercial Failed 07/13/2005
Correction
Partial Correction
07/13/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Corrective Action Required
07/13/2005
LABELING OF NATURAL GAS METER WHEN METER IS INSTALLED APPLY PERMANENT LABEL DISPLAYING SPACE SERVED
Correction
Corrective Action Required
07/13/2005
GRADING AT NORTH END OF BUILDING WATER PONDING
Correction
Resolved
07/13/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
07/13/2005
Receive Fire Department approval PER CPT ULLERY 7/13/05
Occupancy Inspection - Codes Commercial Failed 07/14/2005
Correction
Corrective Action Required
07/14/2005
LIGHTED SIGN INSTALLED ON BUILDING NEC 600-3 NO LISTING LABELS FOUND
Gas Service Inspection - Commercial Passed 07/15/2005
Correction
Resolved
07/15/2005
GAS LINE PRESSURE TEST RELEASE SERVICE HELD STEADY @>10PSI FOR >30 MIN
Gas Piping Inspection - Commercial Passed 07/15/2005
Occupancy Inspection - Codes Commercial Passed 07/26/2005
Correction
Resolved
07/26/2005
LIGHTED SIGN INSTALLED ON BUILDING
Correction
Resolved
07/26/2005
OCCUPANCY APPROVAL STATUS
Correction
Resolved
07/26/2005
LABELING OF NATURAL GAS METER WHEN METER IS INSTALLED APPLY PERMANENT LABEL DISPLAYING SPACE SERVED
Correction
Resolved
07/26/2005
GRADING AT NORTH END OF BUILDING WATER PONDING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home