Summary
B0500709
Building Permit - Commercial
Certificate of Occupancy
SRI REAL ESTATE PROPERTIES LLC
NEW COMMERCIAL
SONIC RESTAURANT
05/02/2005
08/25/2005
02/21/2006
09/02/2008
Locations
Contacts
W C CONSTRUCTION LLC, Address:PO BOX 29009  
SRI REAL ESTATE PROPERTIES LLC, Address:300 JOHNNY BENCH DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/06/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1008.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater than 0.25 inch at doorways shall beveled with a slope not greater than one unit vertical in two units horizontal.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Fire Department- Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - ( As ammended) A 6-foot vinyl fence with masonry pilasters spaced 50 feet on center shall be provided for this development and a low impact screen per the UDO requirements shall be provided on the west side of the fence. The wall and berm system as described shall be constructed for the entire length of the property and completed prior to any occupancies being given for any of the five buildings shown on the plan.
Correction

Codes Administration - The plans must be approved by the Health Department prior to permit approval. Contact Steve Hutchens with the Jackson Count Public Works Department at 816-881-4471.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet of all portions of the facility or any portion of the exterior wall of the first story of the building as measured by an approved route around the exterior of the building or facility.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 608.1 - General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.9.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,352.00 $1,352.00 Paid 08/25/2005
24 BLDG Plan Check Fees $42.50 $42.50 Paid 08/25/2005
25 Electrical Permit Fee $133.41 $133.41 Paid 08/25/2005
25 Mechanical Permit Fees $70.00 $70.00 Paid 08/25/2005
25 Plumbing Permit Fees $83.00 $83.00 Paid 08/25/2005
84 Water Meters $400.00 $400.00 Paid 08/25/2005
85 Water Taps $10,936.00 $10,936.00 Paid 08/25/2005
89 Sewer Tap Fees $270.00 $270.00 Paid 08/25/2005
Right of Way Permit $35.00 $35.00 Paid 08/25/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 09/20/2005
Correction
Resolved
09/20/2005
PERIMETER GRADE BEAM 9/19/05 ENGR LTR.ENSURE RE-BAR COVERAGE >=3" AT BOTTOMS AND BANKS. OK TO POUR WHEN READY PER DRAWINGS CLARIFIED BY
Electrical Service Inspection Partial 09/21/2005
Correction
Partial Correction
09/21/2005
TEMPORARY ELECTRICAL SERVICE INSTALLATION 100 AMP RELEASE SERVICE
Underslab Plumbing Inspection - Commercial Passed 09/22/2005
Correction
Resolved
09/22/2005
None APPROVED TO POUR. NOTE: BELOW GRADE PLUMBING INSPECTION REQUIRED FOR GREASE TRAP AND ASSOCIATED PIPING.
Underslab Electrical Inspection - Commercial Passed 09/27/2005
Underground Electrical Inspection - Commercial Request Complete 9/26/2005 9/27/2005 09/27/2005
All Rough Inspection - Commercial Failed 10/10/2005
Correction
Corrective Action Required
10/10/2005
FRAMING ONLY COMPLETE ANCHOR BOLTS AT WEST ENTRANCE
All Rough Inspection - Commercial Failed 10/18/2005
Correction
Resolved
10/18/2005
FRAMING ONLY
Correction
Corrective Action Required
10/18/2005
SUPPORT OF IN-WALL ELECTRICAL BOXES SECURE ALL BOXES 4" STAND-OFFS INEFFECTIVE EXCEPT IN 4" WALLS
Correction
Corrective Action Required
10/18/2005
PROTECTION OF COPPER & PVC PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES AT STUDS & PLATES. < 1-1/2" FROM FACE OF STUD / PLATE / TRACK
All Rough Inspection - Commercial Passed 10/19/2005
Correction
Resolved
10/19/2005
SUPPORT OF IN-WALL ELECTRICAL BOXES
Correction
Resolved
10/19/2005
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
10/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH OK TO COVER WHEN READY
Water Service Inspection Partial 11/01/2005
Correction
Partial Correction
11/01/2005
WATER SERVICE INSTALLATION OK TO COVER WHEN READY FROM BUILDING ENTRY TO NEAR METER LOCATION
Rough Framing Inspection - Commercial Passed 11/01/2005
Correction
Resolved
11/01/2005
STEEL FRAME FOR CANOPY NOTE: NO INSPECTION REQUESTED ON CANOPY PIERS. NO OTHER ISSUES NOTED. VISUAL INSPECTION FABRICATION/ERECTION
Water Service Inspection - Commercial Request Complete 11/1/2005 11/1/2005 11/01/2005
Underground Plumbing Inspection - Commercial Failed 11/02/2005
Correction
Corrective Action Required
11/02/2005
GREASE INTERCEPTOR CONFIGURATION NOT PER PERMIT DRWGS OBTAIN A/E APPROVAL
Sewer Service Inspection Partial 11/02/2005
Correction
Partial Correction
11/02/2005
SEWER SERVICE INSTALLATION THEN FROM GREASE INTERCEPTOR CONNECTION AT MAIN (APPROVED BY LSPW). OK TO COVER PIPE WHEN READY. NOTE VARIATION IN GREASE INTERCEPTION DESIGN. FROM BUILDING ENTRY TO GREASE INTERCEPTOR
Sewer Service Inspection - Commercial Request Complete 11/2/2005 11/2/2005 11/02/2005
Water Service Inspection Passed 11/03/2005
Correction
Resolved
11/03/2005
WATER SERVICE INSTALLATION APPROVED EXTERIOR
Water Service Inspection - Commercial Request Complete 11/3/2005 11/3/2005 11/03/2005
Underground Electrical Inspection - Commercial Partial 11/04/2005
Correction
Partial Correction
11/04/2005
EXTERIOR UNDERGROUND ELECTRICAL CONDUIT ONE 2" + ONE 1" FROM BLDG NW FOR CONTROL + CANOPY SPEAKERS; TWO 3/4" FROM BLDG N FOR CANOPY LIGHTING; OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Underground Electrical Inspection - Commercial Request Complete 11/4/2005 11/4/2005 11/04/2005
Underground Electrical Inspection - Commercial Partial 11/08/2005
Correction
Partial Correction
11/08/2005
EXTERIOR UNDERGROUND ELECTRICAL CONDUIT ONE 2" + ONE 1" FROM BLDG NW FOR CONTROL + CANOPY SPEAKERS; TWO 3/4" FROM BLDG N FOR CANOPY LIGHTING; REMAINDER OF SITE U/G CONDUIT EXCEPT TO MONUMENT SIGN *LIGHT POLE BASES TO BE REQUESTED FOR INSPECTION WHEN READY FOR POUR* OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Underground Electrical Inspection - Commercial Request Complete 11/7/2005 11/8/2005 11/08/2005
Underground Electrical Inspection - Commercial Partial 11/11/2005
Correction
Partial Correction
11/11/2005
EXTERIOR UNDERGROUND ELECTRICAL CONDUIT ALL SITE U/G BRANCH CONDUIT EXCEPT TO MONUMENT SIGN; SECONDARY SERVICE CONDUIT OK TO ENCASE PER AQUILA & BACKFILL OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Underground Electrical Inspection - Commercial Request Complete 11/10/2005 11/11/2005 11/11/2005
Hood/Duct Inspection Failed 11/14/2005
Correction
Corrective Action Required
11/14/2005
COMMERCIAL KITCHEN GREASE DUCT GAPPED JOINTS IN DUCT, DUCT-TO-HOOD CONNECTION, DUCT-TO-EXHAUST FAN CONNECTION, IMC 506 ELIMINATE ALL LEDGES + PROTRUDING WELDS +
Hood/Duct Inspection Passed 11/17/2005
Correction
Resolved
11/17/2005
COMMERCIAL KITCHEN GREASE DUCT OK TO COVER EXTERIOR WHEN READY GRIND PROTRUDING WELDS ON DUCT INTERIOR T&B
Gas Service Inspection - Commercial Passed 11/17/2005
Correction
Resolved
11/17/2005
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Passed 11/17/2005
Underground Electrical Inspection - Commercial Partial 11/21/2005
Correction
Partial Correction
11/21/2005
EXTERIOR UNDERGROUND ELECTRICAL CONDUIT SECONDARY SERVICE CONDUIT; ALL SITE U/G BRANCH CONDUIT; LIGHT POLE BASES YET TO BE INSPECTED OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Underground Electrical Inspection - Commercial Request Complete 11/18/2005 11/21/2005 11/21/2005
Electrical Service Inspection Not Ready 12/05/2005
Correction
Corrective Action Required
12/05/2005
READINESS FOR INSPECTION CALL TO SCHEDULE INSPECTION AFTER PREPARATION IS COMPLETE WORK REQUESTED FOR INSP NOT COMPLETED
Electrical Service Inspection Passed 12/06/2005
Correction
Resolved
12/06/2005
TEMPORARY ELECTRICAL SERVICE INSTALLATION
Correction
Resolved
12/06/2005
READINESS FOR INSPECTION
Correction
Resolved
12/06/2005
PERMANENT ELECTRICAL SERVICE INSTALLATION ENSURE PANEL FRONTS ARE IN PLACE BEFORE REQUESTING SERVICE ACTIVATION. 400 AMP RELEASE SERVICE
Above Ceiling Inspection Failed 12/27/2005
Correction
Partial Correction
12/27/2005
RESTUARANT AREA PANEL RUNNING EXTERIOR SWITCHES WAS NOT BUTTONED UP - DO NOT COVER AREA OR BE ABLE TO BE MADE READILY AVAILABLE UPON REQUEST - CHECK AT OCCUPANCY OK TO COVER
Occupancy Inspection - Codes Commercial Failed 12/30/2005
Correction
Corrective Action Required
12/30/2005
COMMENTS OCCUPANCY INSPECTION NOT YET PERFORMED. OK TO STORE OWNER'S GOODS & WARES ON SHELVING CONTINGENT UPON STORAGE NOT OBSCURING ANY INSPECTION ITEMS. CONTRACTOR RESPONSIBLE FOR MOVING ANY/ALL STORED ITEMS AT TIME OF ACTUAL INSPECTION.
Correction
Corrective Action Required
12/30/2005
COMMENT SITE NOT APPROVED FOR ANY TYPE OF TRAINING OR "MOCK SERVICE."
Miscellaneous Inspection Failed 12/30/2005
Correction
Corrective Action Required
12/30/2005
LIGHT POLE BASES STEEL REINFORCEMENT NOT PER PLANS. DO NOT POUR
Miscellaneous Inspection Passed 01/02/2006
Correction
Resolved
01/02/2006
LIGHT POLE BASES SEE U/G ELECTRICAL
Underground Electrical Inspection - Commercial Partial 01/02/2006
Correction
Resolved
01/02/2006
EXTERIOR UNDERGROUND ELECTRICAL CONDUIT
Correction
Corrective Action Required
01/02/2006
LIGHT POLE BASES DO NOT POUR STEEL REINFORCEMENT NOT PER PLANS 12/30/05
Underground Plumbing Inspection - Commercial Passed 01/02/2006
Correction
Resolved
01/02/2006
GREASE INTERCEPTOR CONFIGURATION NOT PER PERMIT DRWGS APPROVED BY A/E
Sewer Service Inspection Passed 01/02/2006
Correction
Resolved
01/02/2006
SEWER SERVICE INSTALLATION THEN FROM GREASE INTERCEPTOR CONNECTION AT MAIN (APPROVED BY LSPW) FROM BUILDING ENTRY TO GREASE INTERCEPTOR
Underground Electrical Inspection - Commercial Passed 01/03/2006
Correction
Resolved
01/03/2006
LIGHT POLE BASES + TIGHTEN GROUND CONDUCTOR IN CLAMP @ NE POLE RE-SET ONE GROUND ROD @ NW NOT DRIVEN SOLID
Occupancy Inspection - Codes Commercial Failed 01/04/2006
Correction
Resolved
01/04/2006
COMMENTS
Correction
Resolved
01/04/2006
COMMENT
Correction
Corrective Action Required
01/04/2006
Receive Fire Department approval
Correction
Corrective Action Required
01/04/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
01/04/2006
Receive Public Works Approval
Correction
Corrective Action Required
01/04/2006
Receive Water Utilities Approval
Correction
Corrective Action Required
01/04/2006
KITCHEN HOOD VELOCITY TEST
Correction
Corrective Action Required
01/04/2006
KITCHEN HOOD SMOKE CAPTURE TEST
Correction
Corrective Action Required
01/04/2006
ROOFTOP GAS PIPING
Correction
Corrective Action Required
01/04/2006
ROOFTOP CONDENSATE PIPING
Correction
Corrective Action Required
01/04/2006
DEADBOLT LOCK @ SOUTH DOOR MUST HAVE THUMB LATCH FOR EMERGENCY EGRESS
Correction
Corrective Action Required
01/04/2006
LABELING OF ELECTRICAL CIRCUIT BREAKERS COMPLETE SCHEDULES AT SERVICE PANELS
Correction
Corrective Action Required
01/04/2006
EXTERIOR CEILING FANS PROVIDE LISTING INFO FOR USE IN DAMP CONDITIONS
Above Ceiling Inspection Passed 01/04/2006
Correction
Resolved
01/04/2006
RESTUARANT AREA
Occupancy Inspection - Codes Commercial Failed 01/05/2006
Correction
Resolved
01/05/2006
Receive Fire Department approval PER J DIR 1/4/06
Correction
Resolved
01/05/2006
Receive Water Utilities Approval PER B HASKAMP 1/3/06
Correction
Resolved
01/05/2006
KITCHEN HOOD SMOKE CAPTURE TEST WITNESSED 1/4/06
Correction
Resolved
01/05/2006
ROOFTOP GAS PIPING
Correction
Resolved
01/05/2006
EXTERIOR CEILING FANS LISTING INFO PROVIDED
Occupancy Inspection - Codes Commercial Failed 01/09/2006
Correction
Resolved
01/09/2006
KITCHEN HOOD VELOCITY TEST REPORT DATED 1/5/06
Correction
Resolved
01/09/2006
ROOFTOP CONDENSATE PIPING
Correction
Resolved
01/09/2006
DEADBOLT LOCK @ SOUTH DOOR
Correction
Resolved
01/09/2006
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
01/09/2006
EXTERIOR CEILING FANS LISTING INFO PROVIDED
Correction
Corrective Action Required
01/09/2006
LABELING OF ELECTRICAL PANELS DIFFERENTIATE PANELS B1 AND B2
Occupancy Inspection - Codes Commercial Failed 01/13/2006
Correction
Partial Correction
01/13/2006
Receive Planning & Development Approval CONTACT T SCANNELL FOR REINSPECTION WHEN ALL P&D ISSUES ARE RESOLVED OK FOR TEMP OCCUPANCY PER T SCANNELL 1/13/06
Correction
Resolved
01/13/2006
Receive Public Works Approval NO REMAINING ISSUES
Correction
Resolved
01/13/2006
EXTERIOR CEILING FANS
Correction
Resolved
01/13/2006
LABELING OF ELECTRICAL PANELS
Occupancy Inspection - Codes Commercial Passed 08/29/2008
Correction
Resolved
08/29/2008
Receive Planning & Development Approval PER BOB MCKAY 8/22/08
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home