Summary
B0500645
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
CHANGE OF TENANT
JOHN KNOX VILLAGE SPECIAL CARE SUITE RENOVATION
04/25/2005
09/30/2005
03/29/2006
02/07/2007
Locations
Contacts
THE WEITZ COMPANY, Address:9900 W 109TH ST SUITE 230  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/22/2006 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - The plans must be approved by the Jackson County Public Works, Environmental Services, prior to permit issuance.
Correction

Codes Administration - 2003 IMC 504.6.1 - Maximum length. The maximum length of a clothes dryer exhaust shall not exceed 25 ft from the dryer location to the outlet terminal. The maximum lenth of duct shall be reduced 2.5 feet for each 45-degree bend and 5 feet for each 90-degree bend. The maximum length of the exhaust duct does not include the transition duct.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requies a Type I hood, A Type I hood shall be installed. Where a Type II hood is required, a Type I or Typed II hood shall be installed.
Correction

Codes Administration - 2003 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

A note should be provided indicating a Reduce Pressure Zone (RPZ) principal backflow prevention device will be placed inside the building on the domestic water service line prior to any point of use.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,802.00 $1,802.00 Paid 09/30/2005
24 BLDG Plan Check Fees $50.00 $50.00 Paid 09/30/2005
25 Electrical Permit Fee $463.95 $463.95 Paid 09/30/2005
25 Mechanical Permit Fees $225.50 $225.50 Paid 09/30/2005
25 Plumbing Permit Fees $333.50 $333.50 Paid 09/30/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 10/26/2005
Correction
Partial Correction
10/26/2005
BUILDING DRAIN TRUNK LINE IN CORRIDORS FROM UNIT 01 TO 07; OK TO COVER WHEN READY SECTIONS LISTED BELOW:
Correction
Partial Correction
10/26/2005
UNDER-SLAB DWV PIPING IN ROOMS UNITS 01; 03; 05; 07; OK TO COVER WHEN READY AT SPACES LISTED BELOW:
Underslab Plumbing Inspection - Commercial Partial 10/28/2005
Correction
Partial Correction
10/28/2005
BUILDING DRAIN TRUNK LINE IN CORRIDORS THROUGH CORRIDORS 21 & 43 EXCEPT CONNECTIONS TO EXSTG @ N&S ENDS; OK TO COVER WHEN READY SECTIONS LISTED BELOW:
Underground Plumbing Inspection - Commercial Request Complete 10/27/2005 10/28/2005 10/28/2005
Underslab Plumbing Inspection - Commercial Partial 10/31/2005
Correction
Partial Correction
10/31/2005
UNDER-SLAB DWV PIPING IN ROOMS SPACES 01; 03; 05; 07; 9; 11; 12; 13; 14; 15; 16; 17; 18; 19; 41; 42; VISUAL + PRESSURE TEST OK TO COVER WHEN READY
Underground Plumbing Inspection - Commercial Request Complete 10/28/2005 10/31/2005 10/31/2005
Underslab Plumbing Inspection - Commercial Partial 11/03/2005
Correction
Partial Correction
11/03/2005
UNDER-SLAB DWV PIPING IN ROOMS SPACES 01; 03; 05; 07; 9; 11; 12; 13; 14; 15; 16; 17; 18; 19; 41; 42; 02; 04; 06; 08; 10; 29; 32; 33; 34; 35; 39; 40; 45; 46; E 20' OF LATERAL TOWARD 33; VISUAL + PRESSURE TEST OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Partial 11/04/2005
Correction
Resolved
11/04/2005
BUILDING DRAIN TRUNK LINE IN CORRIDORS THROUGH CORRIDORS 21 & 43 EXCEPT CONNECTIONS TO EXSTG @ N&S ENDS; TIE-IN TO EXISTING LINES @ CORR 21 S + CORR 43 N OK TO COVER WHEN READY SECTIONS LISTED BELOW:
Correction
Partial Correction
11/04/2005
UNDER-SLAB DWV PIPING IN ROOMS SPACES 01; 03; 05; 07; 9; 11; 12; 13; 14; 15; 16; 17; 18; 19; 41; 42; 02; 04; 06; 08; 10; 29; 30; 31; 32; 33; 34; 35; 39; 40; 45; 46; E 30' OF LATERAL TOWARD 30; VISUAL + PRESSURE TEST OK TO COVER WHEN READY
Underground Plumbing Inspection - Commercial Request Complete 11/3/2005 11/4/2005 11/04/2005
Footing Inspection - Commercial Not Ready 01/06/2006
Correction
Corrective Action Required
01/06/2006
SPREAD FOOTING @ NEW MENS ROOM ALREADY POURED @ 13:30 INSPECTOR ARRIVAL READY TIME 12:30
All Rough Inspection - Commercial Failed 02/15/2006
Correction
Corrective Action Required
02/15/2006
EXTERIOR WALLS @ NORTH + SOUTH WINGS + OBTAIN CONCURRENCE OF JKV IF NUMEROUS EXISTING NOTCHED STUDS ARE TO BE COVERED WITHOUT REPAIR/REINFORCEMENT. REPAIR HOLES IN SHEATHING DO NOT COVER
Occupancy Inspection - Codes Commercial Not Ready 02/24/2006
Correction
Corrective Action Required
02/24/2006
Receive Fire Department approval
Correction
Corrective Action Required
02/24/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
02/24/2006
Receive Water Utilities Approval
Correction
Resolved
02/24/2006
Receive Public Works Approval PER LSPW COFC 1/27/06
Underslab Plumbing Inspection - Commercial Passed 03/14/2006
Correction
Resolved
03/14/2006
BUILDING DRAIN TRUNK LINE IN CORRIDORS
Correction
Resolved
03/14/2006
UNDER-SLAB DWV PIPING IN ROOMS SPACES 01; 03; 05; 07; 9; 11; 12; 13; 14; 15; 16; 17; 18; 19; 41; 42; 02; 04; 06; 08; 10; 29; 30; 31; 32; 33; 34; 35; 39; 40; 45; 46; E 30' OF LATERAL TOWARD 30; REMAINDER @ 30, 36, 38; TOILET @ 20 VISUAL + PRESSURE TEST OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 04/06/2006
Correction
Partial Correction
04/06/2006
EXTERIOR WALLS @ NORTH + SOUTH WINGS APPROVED TO COVER EXTERIOR WALLS CONTINGENT UPON FIRE BLOCKING ALL TOP PLATE PENETRATIONS. PROVIDE PHOTOS AS VERIFICATION AT NEXT INSPECTION.
Miscellaneous Inspection Failed 04/06/2006
Correction
Corrective Action Required
04/06/2006
Premises Identification (IRC) PROPERTY TO BE IDENTIFIABLE FROM STREET.
All Rough Inspection - Commercial Failed 04/14/2006
Correction
Corrective Action Required
04/14/2006
INTERIOR OF CORRIDOR WALLS NORTH & SOUTH REPAIR DAMAGED STUDS AT SHOWERS & AT ABANDONED PLUMBING AT FAR SOUTH & AT OVERDRILLS AT FAR SOUTHWEST. NOTE: THIS COMMENT ASSUMES A LOAD BEARING WALL. A SEALED LETTER FROM ENGINEER VERIFYING THAT ROOF STRUCTURE IS A FREE SPAN CAN NEGATE THIS COMMENT.
Above Ceiling Inspection Partial 04/14/2006
Correction
Partial Correction
04/14/2006
NORTH & SOUTH CORRIDORS APPROVED TO INSULATE DOMESTIC WATER PIPING. DO NOT COVER CEILING.
All Rough Inspection - Commercial Not Ready 04/19/2006
Correction
Corrective Action Required
04/19/2006
READINESS FOR INSPECTION WHEN REQUESTING INSPECTION INDICATE SPACES REQUESTED FOR INSPECTION OR BE PRESENT ON-SITE TO CLARIFY WORK REQUESTED FOR INSP AREA(S) NOT SPECIFIED
Rough Mechanical Inspection - Commercial Partial 04/20/2006
Correction
Partial Correction
04/20/2006
HVAC SA DUCTWORK FROM RTU'S 4, 5, 9 WALLPENETRATION FROM ROOF 90 FITTINGS DOWN TO 1STFL
All Rough Inspection - Commercial Not Ready 04/25/2006
Correction
Corrective Action Required
04/25/2006
READINESS FOR INSPECTION ABOVE-CEILING SYSTEMS WORK INCOMPLETE WORK REQUESTED FOR INSP NOT COMPLETED
All Rough Inspection - Commercial Failed 04/28/2006
Correction
Partial Correction
04/28/2006
READINESS FOR INSPECTION 4/28/06 INSPECTION NORTH & SOUTH WINGS ONLY
Correction
Corrective Action Required
04/28/2006
BATH VENT FANS NOT INSTALLED @ 18 & 19 WIRING NOT COMPLETED
Correction
Corrective Action Required
04/28/2006
CAN LIGHTS @ BATHROOMS NOT INSTALLED
Correction
Corrective Action Required
04/28/2006
BUILDING INSULATION ABOVE CEILING AREAS MISSING/DAMAGED VARIOUS LOCATIONS
Correction
Corrective Action Required
04/28/2006
INSTALLATION OF HVAC DUCTWORK SOME INCOMPLETE SOME NOT INSULATED
Correction
Corrective Action Required
04/28/2006
ROOF LEAK AT CORRIDOR 43 OUTSIDE ROOM 9
Correction
Corrective Action Required
04/28/2006
NM ELECTRICAL CABLE @ ROOM 7 ABOVE ELECTRICAL PANEL DAMAGED -- TAPE N.G.
Correction
Corrective Action Required
04/28/2006
INSULATION OF WATER PIPING INCOMPLETE
Correction
Corrective Action Required
04/28/2006
UNTERMINATED BARE ELECTRICAL CABLES ABOVE CEILING @ CORR 43 OUTSIDE RM 7
Correction
Corrective Action Required
04/28/2006
ELECTRICAL BOX HIGH ON CORRIDOR 43 EAST WALL EXCEEDS 1/4" MAX SETBACK S END OF CORRIDOR RECESSED IN WALL
Correction
Corrective Action Required
04/28/2006
ELECTRICAL BOX HIGH ON EAST WALL OF CORR 43 BETWEEN 13 & 15 DAMAGED/DISPLACED
Correction
Corrective Action Required
04/28/2006
TYPE AND RATING OF WALLS/PARTITIONS APPEAR NOT TO AGREE. SEE TYPES K1 & K2. OBTAIN WRITTEN CLARIFICATION FROM ARCHITECT/ENGINEER DRAWING SHEET A0.1 VERSUS SHEETS A1.1 & A6.1
Correction
Corrective Action Required
04/28/2006
INSTALLATION OF CEILING ELECTRICAL BOXES SOME CONFLICT WITH CHANNEL CEILING FRAMING
All Rough Inspection - Commercial Partial 05/04/2006
Correction
Resolved
05/04/2006
EXTERIOR WALLS @ NORTH + SOUTH WINGS
Correction
Resolved
05/04/2006
INTERIOR OF CORRIDOR WALLS NORTH & SOUTH
Correction
Partial Correction
05/04/2006
READINESS FOR INSPECTION 4/28/06 INSPECTION NORTH & SOUTH WINGS ONLY
Correction
Corrective Action Required
05/04/2006
BATH VENT FANS NOT INSTALLED @ 18 & 19 WIRING NOT COMPLETED
Correction
Partial Correction
05/04/2006
BUILDING INSULATION ABOVE CEILING REPAIR ONE AREA NEAR N END CORRIDOR 43
Correction
Resolved
05/04/2006
INSTALLATION OF HVAC DUCTWORK
Correction
Resolved
05/04/2006
ROOF LEAK AT CORRIDOR 43
Correction
Resolved
05/04/2006
NM ELECTRICAL CABLE @ ROOM 7
Correction
Resolved
05/04/2006
INSULATION OF WATER PIPING
Correction
Resolved
05/04/2006
UNTERMINATED BARE ELECTRICAL CABLES
Correction
Resolved
05/04/2006
ELECTRICAL BOX HIGH ON CORRIDOR 43 EAST WALL
Correction
Resolved
05/04/2006
ELECTRICAL BOX HIGH ON EAST WALL OF CORR 43
Correction
Corrective Action Required
05/04/2006
TYPE AND RATING OF WALLS/PARTITIONS APPEAR NOT TO AGREE. SEE TYPES K1 & K2. OBTAIN WRITTEN CLARIFICATION FROM ARCHITECT/ENGINEER DRAWING SHEET A0.1 VERSUS SHEETS A1.1 & A6.1
Correction
Resolved
05/04/2006
INSTALLATION OF CEILING ELECTRICAL BOXES
Correction
Partial Correction
05/04/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS NORTH + SOUTH WINGS EXCEPT CEILINGS @ BATHROOMS & SHOWERS AND ROOM 7 SOUTH WALL OK TO COVER WHEN READY SPACES LISTED BELOW:
Gas Piping Inspection - Commercial Passed 05/17/2006
Correction
Resolved
05/17/2006
EXTENSION OF EXISTING PIPING SYSTEM TO SERVE FACILITY HELD STEADY AT >16 PSI FOR >30 MIN VISUAL INSPECTION OK TEST PRESSURE LEVEL
All Rough Inspection - Commercial Partial 05/30/2006
Correction
Partial Correction
05/30/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS NORTH + SOUTH WINGS EXCEPT CEILINGS @ BATHROOMS & SHOWERS AND ROOM 7 SOUTH WALL; BATHROOMS & SHOWERS @ 2-18 (SEAL FLEX HVAC DUCT JOINT @ 10 & 16); FRAMING TO ELIMINATE DOORS @ S & N ENDS OF MAIN CORRIDOR OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Failed 06/05/2006
Correction
Partial Correction
06/05/2006
READINESS FOR INSPECTION 24-26; 29-34; 37-39; SPACES NOT READY FOR INSPECTION: 27-28; 35-36 SPACES UNDER INSPECTION AS OF 6/5/06:
Correction
Resolved
06/05/2006
BATH VENT FANS
Correction
Resolved
06/05/2006
CAN LIGHTS @ BATHROOMS
Correction
Resolved
06/05/2006
BUILDING INSULATION ABOVE CEILING
Correction
Partial Correction
06/05/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY NORTH & SOUTH WINGS
Correction
Corrective Action Required
06/05/2006
WALL OPENING IN BEARING WALL BETWEEN SPACES 30 & 38 NO LINTEL FOUND
Correction
Corrective Action Required
06/05/2006
CONDITION OF ROOF INSULATION NOT SECURED TO STRUCTURE JOINTS NOT CLOSED/ADHERED
Correction
Corrective Action Required
06/05/2006
STATUS OF DEMOLITION/REMOVALS REMOVAL NOT COMPLETE NOT PER DRWG A0.2 PIPING, CONDUIT, BOXES
Correction
Corrective Action Required
06/05/2006
WIRING OF VENT FAN AT 31 NOT TERMINATED
Correction
Corrective Action Required
06/05/2006
PROTECTION OF COPPER & PVC PIPING IPC 305.8: INSTALL SHIELD PLATES AT STUDS / PLATES / TRACKS < 1-1/2" FROM FACE OF STUD / PLATE / TRACK
Correction
Corrective Action Required
06/05/2006
FIRE-BLOCKING OF LEVEL-TO-LEVEL OPENINGS NOT COMPLETED VARIOUS LOCATIONS
Correction
Corrective Action Required
06/05/2006
EXISTING CONDENSATE PIPING VERIFY CONDITION OF ALL + CLOSE UNUSED OPENINGS
Correction
Corrective Action Required
06/05/2006
BEARING WALL DAMAGE @ DOOR S1 CMU WALL FRACTURED REQUIRES REPAIR
Miscellaneous Inspection Passed 06/09/2006
Correction
Resolved
06/09/2006
Premises Identification (IRC)
Above Ceiling Inspection Partial 06/09/2006
Correction
Partial Correction
06/09/2006
NORTH & SOUTH CORRIDORS
All Rough Inspection - Commercial Partial 06/09/2006
Correction
Partial Correction
06/09/2006
READINESS FOR INSPECTION 24-26; 29-34; 37-39; SPACES NOT READY FOR INSPECTION: 27-28; 35-36 SPACES UNDER INSPECTION AS OF 6/9/06:
Correction
Partial Correction
06/09/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS 24-26; 29-34; 37-39; OK TO COVER WHEN READY NORTH & SOUTH WINGS +
Correction
Resolved
06/09/2006
WALL OPENING IN BEARING WALL BETWEEN SPACES 30 & 38
Correction
Resolved
06/09/2006
CONDITION OF ROOF INSULATION
Correction
Resolved
06/09/2006
STATUS OF DEMOLITION/REMOVALS JKV LETTER DTD 6/8/06 INDICATES ACCEPTANCE
Correction
Resolved
06/09/2006
WIRING OF VENT FAN AT 31
Correction
Resolved
06/09/2006
PROTECTION OF COPPER & PVC PIPING IPC 305.8: INSTALL SHIELD PLATES AT STUDS / PLATES / TRACKS < 1-1/2" FROM FACE OF STUD / PLATE / TRACK
Correction
Resolved
06/09/2006
FIRE-BLOCKING OF LEVEL-TO-LEVEL OPENINGS
Correction
Resolved
06/09/2006
EXISTING CONDENSATE PIPING VERIFY CONDITION OF ALL
Correction
Resolved
06/09/2006
BEARING WALL DAMAGE @ DOOR S1
Footing Inspection - Commercial Passed 06/09/2006
Correction
Resolved
06/09/2006
SPREAD FOOTING @ NEW MENS ROOM
Rough Mechanical Inspection - Commercial Passed 06/09/2006
Correction
Resolved
06/09/2006
HVAC SA DUCTWORK FROM RTU'S 4, 5, 9
All Rough Inspection - Commercial Partial 06/12/2006
Correction
Resolved
06/12/2006
READINESS FOR INSPECTION
Correction
Partial Correction
06/12/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS 24-26; 29-34; 36; 37-39; SPACES NOT READY FOR INSPECTION: 27-28; 35 OK TO COVER WHEN READY NORTH & SOUTH WINGS +
Correction
Resolved
06/12/2006
STATUS OF DEMOLITION/REMOVALS
Correction
Resolved
06/12/2006
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
06/12/2006
EXISTING CONDENSATE PIPING
All Rough Inspection - Commercial Partial 06/15/2006
Correction
Partial Correction
06/15/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS 24-26; 29-34; 36; 37-39; 27-28; 35 OK TO COVER WHEN READY NORTH & SOUTH WINGS +
Above Ceiling Inspection Partial 06/15/2006
Correction
Partial Correction
06/15/2006
NORTH & SOUTH CORRIDORS CEILING APPROVED AT CORRIDOR 35
Occupancy Inspection - Codes Commercial Not Ready 06/30/2006
Correction
Corrective Action Required
06/30/2006
READINESS FOR INSPECTION CALL FOR INSPECTION AFTER PREPARATION IS COMPLETE WORK REQUESTED FOR INSP NOT COMPLETED 6/30/06
Above Ceiling Inspection Passed 07/03/2006
Correction
Resolved
07/03/2006
NORTH & SOUTH CORRIDORS
All Rough Inspection - Commercial Passed 07/03/2006
Correction
Resolved
07/03/2006
TYPE AND RATING OF WALLS/PARTITIONS SEE FINAL INSPECTION
Correction
Resolved
07/03/2006
WALL FRAMING & IN-WALL + ABOVE-CEILING SYSTEMS
Occupancy Inspection - Codes Commercial Not Ready 07/03/2006
Correction
Corrective Action Required
07/03/2006
ROOFTOP INSPECTION SUBJECT TO APPROVAL
Occupancy Inspection - Codes Commercial Failed 07/06/2006
Correction
Corrective Action Required
07/06/2006
Receive Fire Department approval SEE REPORT PROVIDED
Correction
Corrective Action Required
07/06/2006
Receive Planning & Development Approval COORDINATE W/ HECTOR SOTO PHONE 816-969-7317
Correction
Corrective Action Required
07/06/2006
Receive Water Utilities Approval CONTACT BEN HASKAMP PHONE 816-969-1930
Correction
Resolved
07/06/2006
READINESS FOR INSPECTION
Correction
Corrective Action Required
07/06/2006
ROOFTOP INSPECTION >ELECTRICAL RECEPTACLES @ RTU'S NOT HOT FOR TEST >REMOVE ABANDONED CONDUIT AT S ROOF N END; PLUG OPENINGS CLEAN/CLEAR ALL MATERIAL AND DEBRIS FROM ROOF +
Correction
Corrective Action Required
07/06/2006
BACKFLOW PREVENTION DEVICES 1) ICE DISPENSER -- LISTED FOR PURPOSE 2) HOSE CONNECTIONS AT CLOSET UNDER STAIR 3) DISWASHER: DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED REQUIRED AT LOCATIONS LISTED BELOW
Correction
Corrective Action Required
07/06/2006
ELECTRICAL RECEPTACLE RIGHT OF DP8 SINK NOT GFCI PROTECTED
Correction
Partial Correction
07/06/2006
OCCUPANCY APPROVAL STATUS NO PATIENTS OR PUBLIC UNTIL APPROVED OK FOR STAFF SET-UP FOR BUSINESS
Occupancy Inspection - Codes Commercial Failed 07/11/2006
Correction
Corrective Action Required
07/11/2006
Receive Fire Department approval SEE REPORT PROVIDED
Correction
Corrective Action Required
07/11/2006
Receive Planning & Development Approval COORDINATE W/ HECTOR SOTO PHONE 816-969-7317
Correction
Corrective Action Required
07/11/2006
Receive Water Utilities Approval CONTACT BEN HASKAMP PHONE 816-969-1930
Correction
Resolved
07/11/2006
ROOFTOP INSPECTION CLEAN/CLEAR ALL MATERIAL AND DEBRIS FROM ROOF
Correction
Corrective Action Required
07/11/2006
BACKFLOW PREVENTION DEVICES 1) ICE DISPENSER -- MUST BE LISTED FOR PURPOSE 2) HOSE CONNECTIONS AT CLOSET UNDER STAIR REQUIRED AT LOCATIONS LISTED BELOW
Correction
Resolved
07/11/2006
ELECTRICAL RECEPTACLE RIGHT OF DP8 SINK
Correction
Partial Correction
07/11/2006
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Failed 08/04/2006
Correction
Resolved
08/04/2006
BACKFLOW PREVENTION DEVICES
Occupancy Inspection - Codes Commercial Failed 08/07/2006
Correction
Resolved
08/07/2006
Receive Fire Department approval PER JIM EDEN 8/7/06
Correction
Corrective Action Required
08/07/2006
Receive Planning & Development Approval COORDINATE W/ HECTOR SOTO PHONE 816-969-7314
Correction
Resolved
08/07/2006
Receive Water Utilities Approval PER BEN HASKAMP 8/7/06
Correction
Corrective Action Required
08/07/2006
GUARD @ ELEVATED SIDE OF RAMP AT COURTYARD SW TO BE INSTALLED
Occupancy Inspection - Codes Commercial Passed 02/06/2007
Correction
Resolved
02/06/2007
Receive Planning & Development Approval PER HECTOR SOTO 2/5/07 PHONE 816-969-7314
Correction
Resolved
02/06/2007
ROOFTOP INSPECTION
Correction
Resolved
02/06/2007
OCCUPANCY APPROVAL STATUS
Correction
Resolved
02/06/2007
GUARD @ ELEVATED SIDE OF RAMP AT COURTYARD SW INSTALLED
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home