Summary
B0500526
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
NEW TENANT FINISH
DAVE ORSON OPTOMETRISTS OFFICE
04/04/2005
05/02/2005
10/29/2005
01/04/2006
Locations
Contacts
HIRST AND ASSOCIATES PC, Address:621 NE WOODS CHAPEL RD  
HOBBS CONSTRUCTION, Address:PO BOX 2026  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/01/2005 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.4.1 - Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.4.1.
Correction

Codes Administration - 2003 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $152.00 $152.00 Paid 05/02/2005
24 BLDG Plan Check Fees $14.50 $14.50 Paid 05/02/2005
25 Electrical Permit Fee $42.81 $42.81 Paid 05/02/2005
25 Mechanical Permit Fees $15.00 $15.00 Paid 05/02/2005
25 Plumbing Permit Fees $19.00 $19.00 Paid 05/02/2005
89 Sewer Tap Fees $120.00 $120.00 Paid 05/02/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 05/10/2005
Correction
Resolved
05/10/2005
None UNDERSLAB PLUMBING APPROVED.
Miscellaneous Inspection Failed 05/18/2005
Correction
Corrective Action Required
05/18/2005
WALL CONCEALED PRIOR TO INSPECTION ELECTRICAL ROUGH-IN FOR WALL HAS NOT BEEN APPROVED FOR SHEETROCKING. BOTH SIDES HAS BEEN COVERED WITH SHEETROCK.
Rough Plumbing Inspection - Commercial Passed 05/18/2005
Correction
Resolved
05/18/2005
None PLUMBING ROUGHIN APPROVED
Rough Electrical Inspection - Commercial Passed 05/26/2005
Correction
Resolved
05/26/2005
None ELECTRICAL IN-WALL ROUHGIN APPROVED
Miscellaneous Inspection Passed 05/26/2005
Correction
Resolved
05/26/2005
WALL CONCEALED PRIOR TO INSPECTION
Rough Mechanical Inspection - Commercial Failed 06/16/2005
Correction
Corrective Action Required
06/16/2005
SUPPORT FLEX DUCT WITH MIN 1.5" STRAP NOT WITH SUPPORT WIRE-MIDDLE OF SPACE
Above Ceiling Inspection Failed 06/16/2005
Correction
Corrective Action Required
06/16/2005
SEE BELOW -SUPPORT WATER LINE 6 FT OC -SUPPORT WIRE -CLOSE OUT ELECTRICAL BOXES -DRAFTSTOP PARTITION IN ATTIC -SUPPORT FLEX DUCT WITH 1.5" STRAPS
Rough Mechanical Inspection - Commercial Passed 06/17/2005
Correction
Resolved
06/17/2005
SUPPORT FLEX DUCT WITH MIN 1.5" STRAP
Above Ceiling Inspection Passed 06/17/2005
Correction
Resolved
06/17/2005
SEE BELOW
Occupancy Inspection - Codes Commercial Failed 12/12/2005
Correction
Corrective Action Required
12/12/2005
TEXT -12/12/05: CALLED ABOUT SPACE BEING OCCUPIED WITHOUT ISSUE OF CERTIFICATE OF OCCUPANCY. CURRENTLY NO FINAL INSPECTION HAS BEEN CALLED
Occupancy Inspection - Codes Commercial Failed 12/15/2005
Correction
Corrective Action Required
12/15/2005
TEXT FIRE DEPT APPROVAL REQUIRED: 1. FIRE EXTINGUISHER REQUIRED 2. EGRESS EMERGENCY ILLUMINATION NOT WORKING
Occupancy Inspection - Codes Commercial Passed 01/03/2006
Correction
Resolved
01/03/2006
TEXT FULL OCCUPANCY APPROVED
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home