Permit Application Status

B0500412


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500412
Building Permit - Commercial
Certificate of Occupancy
ERIC DEAN ENTERPRISES INC
ADDITION COMMERCIAL
BUILDING ADDITION
03/17/2005
06/23/2005
12/20/2005
07/27/2006
Locations
Contacts
NEARING STAATS PRELOGAR & JONES, Address:BILL PRELOGAR  
EXCEL CONSTRUCTORS INC, Address:8041 W 47TH ST SUITE 200  
ERIC DEAN ENTERPRISES INC, Address:255 NW BLUE PKWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/05/2005 10/29/2010
Correction

Codes Administration - ANSI A117.1-1998 804.1 - General. Accessible kitchens shall comply with Section 804.
Correction

CA - ASME A17.1-2000 2.2.4.2 - There shall be installed In the pit of each elevator, where the pit extends more than 900 mm (35 in.) below the sill of the pit access door, a fixed vertical ladder of noncumbustible material, located within reach of the access door. The ladder shall extend not less than 1,200 mm (48 in.) above the sill of the access door, or handgrips shall be provided to the same height. The rungs, cleats, or steps shall be a minimum of 300 mm (12 in.) wide. When unavoidable obstructions are encountered, the width shall be permitted to be decreased to less than 300 mm (12 in.). The reduced width shall be as wide as the availaable space permits, bot not less than 225 mm (9 in.). The rungs, cleats, or steps shall be spaced 300 mm (12 in.) on center. A clear distance of not less than 115 mm (4.5 in.) from the centerline of the rungs, cleats, or steps to the nearest permanent obfect in back of the ladder shall be provided. Handgips, of provided, shall have a clear distance of not less than 115 mm (4.5 in.) from their centerline to the nearest permanent object. The nearest point of the ladder shall be within 1,000 mm (39 in.), measured horizontally from the means to unlock the egress door from the pit.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1704.1.1 - Building permit requirements. The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

Codes Administration - 2003 IBC 1704.1.2 - Report Requirement. Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon by the permit applicant and the building official prior to the start of work.
Correction

Codes Administration - 2003 IBC 715.3 - Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any materials or assembly of component materials that conforms to the test requirements of Section 715.3.1, 715.3.2 or 715.3.3 and the fire protection rating indicated in Table 715.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.
Correction

Fire Department- Rm 417 shows an exit sign over door 415. It is not clear what this room is, and a stair way is not shown from this area to the first floor.
Correction

Fire Department- A Code Analysis for the building is not provided.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Codes Administration - The size of the existing water service to be abandoned is not provided on the plans.
Correction

Codes Administration - The wall types shown on Sheet A2.1 has two different D wall types. I believe the one to the far left is to be wall type F.
Correction

Codes Administration - A plumbing fixture schedule has not been provided.
Correction

Codes Administration - Electrical panel schedules have not been provided.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative.
Correction

CA - Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection.
Correction

NOTE: The contractor must contact the Missouri Department of Natural Resources at 1-800-361-4827 prior to starting the demolition.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start wth a number representing the floor on which the unit is located.
Correction

Fire Department; Egress from a room or space shall not pass through adjoining or interven-ing rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass though a room which can be locked to prevent egress. IFC 1004.2.3
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Fire Department; Buildings other than one- and two-family dwellings. The minimum fire flow and flow duration for buildings otherthan one- and two-family dwellings shall be as specified in Table B105.1.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $7,262.00 $7,262.00 Paid 06/23/2005
24 BLDG Plan Check Fees $141.00 $141.00 Paid 06/23/2005
25 Electrical Permit Fee $590.00 $590.00 Paid 06/23/2005
25 Mechanical Permit Fees $181.00 $181.00 Paid 06/23/2005
25 Plumbing Permit Fees $170.00 $170.00 Paid 06/23/2005
84 Water Meters $625.00 $625.00 Paid 06/23/2005
85 Water Taps $8,202.00 $8,202.00 Paid 06/23/2005
89 Sewer Tap Fees $570.00 $570.00 Paid 06/23/2005
Right of Way Permit $35.00 $35.00 Paid 06/23/2005
85 Water Taps $5,468.00 $5,468.00 Paid 06/09/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 07/26/2005
Correction
Partial Correction
07/26/2005
PERIMETER SPREAD FOOTING + INTEGRAL COLUMN FOOTINGS ON (A.1) FROM (10) TO (15); OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Foundation Inspection - Commercial Partial 07/27/2005
Correction
Partial Correction
07/27/2005
FOUNDATION WALL POUR PREP ON (A.1) FROM (10) TO (15) PREP IN PROGRESS; OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Footing Inspection - Commercial Passed 08/01/2005
Correction
Resolved
08/01/2005
PERIMETER SPREAD FOOTING + INTEGRAL COLUMN FOOTINGS ON (A.1) FROM (10) TO (15); REMAINDER OF PERIMETER ON (A.1), (17) AND (F) OK TO POUR WHEN READY COMPONENTS LISTED BELOW:
Correction
Resolved
08/01/2005
ISOLATED COLUMN FOOTINGS ON (B.1) OK TO POUR WHEN READY
Sewer Service Inspection Partial 08/18/2005
Correction
Partial Correction
08/18/2005
SEWER SERVICE INSTALLATION FROM EAST OF BLDG @ (10) NORTH TO CONNECT TO EXSTG SAN @ (3); CONNECTION LOCATION REVISED PER LSPW OK TO COVER WHEN READY SEGMENTS LISTED BELOW:
Water Service Inspection Partial 08/18/2005
Correction
Partial Correction
08/18/2005
WATER SERVICE INSTALLATION FROM EAST OF BLDG @ (10) NORTH TO (3); OK TO COVER WHEN READY SEGMENTS LISTED BELOW:
Sewer Service Inspection - Commercial Request Complete 8/18/2005 8/18/2005 08/18/2005
Water Service Inspection - Commercial Request Complete 8/18/2005 8/18/2005 08/18/2005
Underground Plumbing Inspection - Commercial Request Complete 8/18/2005 8/19/2005 08/19/2005
Water Service Inspection - Commercial Request Complete 8/18/2005 8/19/2005 08/19/2005
Underground Plumbing Inspection - Commercial Partial 08/30/2005
Correction
Partial Correction
08/30/2005
FIRE PROTECTION WATER LINE FROM CONNECTION S OF VAULT TO NEAR FIRE HYDRANT LOCATION @ NW PROPERTY CORNER; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Water Service Inspection - Commercial Request Complete 8/30/2005 8/30/2005 08/30/2005
Erosion Control Inspection Residential Passed 09/01/2005
Footing Inspection - Commercial Passed 09/01/2005
Correction
Resolved
09/01/2005
None FOOTING FOR RETAINING WALL APPROVED PER PLANS.
Underslab Electrical Inspection - Commercial Passed 09/01/2005
Underslab Plumbing Inspection - Commercial Partial 09/01/2005
Correction
Partial Correction
09/01/2005
None UNDER SLAB PLUMBING APPROVED FOR ROOM 103
Retaining Wall Inspection Passed 09/13/2005
Correction
Resolved
09/13/2005
RETAINING WALL POUR PREPARATION OK TO POUR WHEN READY SE BUILDING CORNER PER WALL SECTION 15/S2.2
Retaining Wall Inspection Request Complete 9/12/2005 9/13/2005 09/13/2005
Electrical Service Inspection Partial 09/21/2005
Correction
Partial Correction
09/21/2005
TEMPORARY ELECTRICAL SERVICE INSTALLATION 400 AMP SERVICE TEMPORARY MODULAR BLDG FOR BLDG OWNER TEMP USE
Underslab Plumbing Inspection - Commercial Passed 10/03/2005
Correction
Resolved
10/03/2005
None UNDER SLAB PLUMBING ROOM 103
Correction
Resolved
10/03/2005
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY RR'S 203 & 204
All Rough Inspection - Commercial Failed 10/18/2005
Correction
Corrective Action Required
10/18/2005
PROTECTION OF COPPER & PVC PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES AT STUDS & TRACKS. < 1-1/2" FROM FACE OF STUD / TRACK
Correction
Corrective Action Required
10/18/2005
FASTENING OF LIGHT GUAGE STEEL STUDS TO TRACKS IBC 2205; AISI SCREW BOTH FLANGES EXCEPT TO SLIP TRACKS
Correction
Partial Correction
10/18/2005
INSTALLATION OF ELECTRICAL RECEPTACLE/SWITCH BOXES ENSURE WITHIN 1/4" OF NON-COM WALL SURFACE
Above Ceiling Inspection Not Ready 10/18/2005
Correction
Corrective Action Required
10/18/2005
PVC PLUMBING PIPE ABOVE CEILING IF RETURN AIR PLENUM PVC NOT ALLOWED
All Rough Inspection - Commercial Failed 10/18/2005
All Rough Inspection - Commercial Passed 10/19/2005
Correction
Resolved
10/19/2005
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
10/19/2005
FASTENING OF LIGHT GUAGE STEEL STUDS TO TRACKS
Correction
Resolved
10/19/2005
INSTALLATION OF ELECTRICAL RECEPTACLE/SWITCH BOXES CAUTION TO ELECTRICAL CONTRACTOR ENSURE WITHIN 1/4" OF NON-COM WALL SURFACE
Rough Framing Inspection - Commercial Partial 12/02/2005
Correction
Partial Correction
12/02/2005
L.G. STEEL FRAMING FOR BRICK FACADE ABOVE WINDOW-WALL C/1-A1/1-A1/3-A/3-A/11-A1/11-A1/17; PER STRUCTURAL DRAWINGS OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Rough Framing Inspection - Commercial Not Ready 12/06/2005
Correction
Corrective Action Required
12/06/2005
READINESS FOR INSPECTION IBC 109.1 NO LADDER TO ROOF FOR INSP OF L.G. FRAMING
Rough Framing Inspection - Commercial Request Complete 12/5/2005 12/6/2005 12/06/2005
Rough Framing Inspection - Commercial Partial 12/15/2005
Correction
Partial Correction
12/15/2005
L.G. STEEL FRAMING FOR BRICK FACADE ABOVE WINDOW-WALL C/1-A1/1-A1/3-A/3-A/11-A1/11-A1/17; REMAINDER OF PERIMETER @ S END + WEST SIDE PER STRUCTURAL DRAWINGS OK TO COVER WHEN READY PORTIONS LISTED BELOW:
Correction
Resolved
12/15/2005
READINESS FOR INSPECTION
Rough Framing Inspection - Commercial Request Complete 12/14/2005 12/15/2005 12/15/2005
Rated Assembly Inspection Partial 01/12/2006
Correction
Partial Correction
01/12/2006
RATED WALLS @ STAIRWELL FRAMING + 1" LINER BOARD; OK TO COVER WHEN READY FULL HEIGHT
Correction
Partial Correction
01/12/2006
MECHANICAL SHAFT SOUTH OF STAIRWELL FRAMING + 1" LINER BOARD @ 2ND FLOOR OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Not Ready 02/06/2006
Correction
Corrective Action Required
02/06/2006
READINESS FOR INSPECTION NOT READY FOR INSPECTION OFFICE TRAILER LOCKED NOACCESS TO PERMIT PRINTS
Rough Framing Inspection - Commercial Request Complete 2/3/2006 2/6/2006 02/06/2006
Foundation Inspection - Commercial Passed 02/28/2006
Correction
Resolved
02/28/2006
FOUNDATION WALL POUR PREP
All Rough Inspection - Commercial Failed 02/28/2006
Correction
Resolved
02/28/2006
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
02/28/2006
INSTALLATION OF ELECTRICAL RECEPTACLE/SWITCH BOXES
Correction
Resolved
02/28/2006
READINESS FOR INSPECTION
Correction
Corrective Action Required
02/28/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 1) SHIELD PLATE PVC PIPE < 1-1/2" FROM FACE OF STUD/TRACK 2) ISOLATE COPPER PIPING FROM STEEL STUDS 3) SCREW ALL STUD FLANGES AT FRAMED OPENINGS 4) ROOF DRAIN CLEANOUTS MUST BE ACCESSIBLE NORTH OF C/L 10 ISSUES LISTED BELOW:
All Rough Inspection - Commercial Failed 03/02/2006
Correction
Corrective Action Required
03/02/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 3) STUD FLANGES NOT FULLY SCREWED AT FRAMED OPENINGS A/E NOTE: ROOF DRAIN CLEANOUTS MAY NOT BE ACCESSIBLE NORTH OF C/L 10 ISSUES LISTED BELOW:
All Rough Inspection - Commercial Partial 03/03/2006
Correction
Partial Correction
03/03/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 1ST FLOOR NORTH OF C/L 10; 1ST FLR 103-107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Failed 03/16/2006
Correction
Corrective Action Required
03/16/2006
PVC PLUMBING PIPE ABOVE CEILING SUBJECT TO APPROVAL
Correction
Corrective Action Required
03/16/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS CORRIDOR 202 FIRE-SEALING OK EXCEPT ROOF DECK FLUTES NOT FILLED WITH MINERAL WOOL SAFING OR EQUIVALENT; SPACES LISTED BELOW
Electrical Service Inspection Passed 03/16/2006
Correction
Resolved
03/16/2006
TEMPORARY ELECTRICAL SERVICE INSTALLATION
Correction
Resolved
03/16/2006
ELECTRICAL SERVICE INSTALLATION 1200 AMP RELEASE SERVICE
Above Ceiling Inspection Partial 03/20/2006
Correction
Resolved
03/20/2006
PVC PLUMBING PIPE ABOVE CEILING
Correction
Partial Correction
03/20/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS CORRIDOR 202; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Not Ready 04/19/2006
Correction
Corrective Action Required
04/19/2006
READINESS FOR INSPECTION ABOVE-CEILING INSP @ TENANT FINISH AREA WORK REQUESTED FOR INSP NOT COMPLETED
Above Ceiling Inspection Partial 04/26/2006
Correction
Partial Correction
04/26/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS CORRIDOR 202; ALL SPACES NORTH OF CORRIDOR 202, BUT CORRIDOR NORTH WALL TO BE LEFT EXPOSED UNTIL FIRE-SEALING IS APPROVED OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Resolved
04/26/2006
READINESS FOR INSPECTION
Above Ceiling Inspection Passed 05/23/2006
Correction
Resolved
05/23/2006
PVC PLUMBING PIPE ABOVE CEILING
Correction
Resolved
05/23/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS FIRE-SEAL AS DISCUSSED OK TO COVER WHEN READY
Correction
Resolved
05/23/2006
READINESS FOR INSPECTION
Occupancy Inspection - Codes Commercial Failed 06/06/2006
Correction
Corrective Action Required
06/06/2006
Receive Fire Department approval
Correction
Corrective Action Required
06/06/2006
Receive Planning & Development Approval
Correction
Corrective Action Required
06/06/2006
Receive Public Works Approval
Correction
Corrective Action Required
06/06/2006
Receive Water Utilities Approval
Correction
Corrective Action Required
06/06/2006
ROOFTOP CLEAN-UP REMOVE ALL DEBRIS AND UNUSED MATERIAL
Correction
Corrective Action Required
06/06/2006
REQUIRED ELECTRICAL RECEPTACLE OUTLETS NEC 210.63: REQUIRED WITHIN 7.5 METERS HVAC AND/OR REFRIG EQPMT AT ROOFTOP
Correction
Corrective Action Required
06/06/2006
PASSENGER ELEVATOR INSTALLATION PROVIDE COPY OF CERTIFICATE WHEN APPROVED NOT CERTIFIED APPROVED BY STATE OF MO INSPECTOR
Correction
Corrective Action Required
06/06/2006
LABELING OF ELECTRICAL SWITCHES & CIRCUIT BREAKERS NEC 408.4 LABEL ALL CB'S & SWITCHES IDENTIFY ALL CB POSITIONS
Correction
Corrective Action Required
06/06/2006
PVC DRAIN PIPING @ 107 NOT SUPPORTED/SECURED
Correction
Corrective Action Required
06/06/2006
UNTERMINATED MC CABLE AT N WALL OF NCORR 102 & 202 EQUIPMENT TO BE WIRED
Correction
Corrective Action Required
06/06/2006
HVAC DUCT INSULATION @ 111 & 206 SEAL ALL JOINTS
Correction
Corrective Action Required
06/06/2006
ROOF DRAIN PIPING @ 111 EAST WALL HANGER NOT SECURED
Correction
Corrective Action Required
06/06/2006
ACCESSIBILITY OF ROOF DRAIN CLEANOUTS DEMONSTRATE ACCESS TO ALL LOCATIONS
Correction
Corrective Action Required
06/06/2006
LOW VOLTAGE ELECTRICAL CABLE @ 111 NEAR WEST WALL SECURE TO STRUCTURE @ 4.5' INTERVALS
Correction
Corrective Action Required
06/06/2006
PLUMBING FIXTURES @ 412 NOT INSTALLED
Correction
Corrective Action Required
06/06/2006
SERVER ROOM LEAVE CEILING TILE OUT, INCLUDING AT ADJOINING ROOM, UNTIL APPROVED. ABOVE-CEILING WORK NOT READY FOR INSPECTION
Correction
Corrective Action Required
06/06/2006
INCANDESCENT LUMINAIRE @ FURNACE ROOM LAMP NOT PROTECTED
Correction
Corrective Action Required
06/06/2006
ELECTRICAL RECEPTACLE AT 422 SOUTH WALL BOX NOT ACCESSIBLE COVERED BY KV CARRIER
Correction
Corrective Action Required
06/06/2006
CONDENSATE DRAIN LINES @ FURNACE ROOM SUPPORT/SECURE ALL LINES
Correction
Corrective Action Required
06/06/2006
OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FURNITURE NO BUSINESS OPERATIONS
All Rough Inspection - Commercial Passed 06/06/2006
Correction
Resolved
06/06/2006
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
06/06/2006
FASTENING OF LIGHT GUAGE STEEL STUDS TO TRACKS
Correction
Resolved
06/06/2006
INSTALLATION OF ELECTRICAL RECEPTACLE/SWITCH BOXES
Correction
Resolved
06/06/2006
READINESS FOR INSPECTION
Correction
Resolved
06/06/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Water Service Inspection Passed 06/06/2006
Correction
Resolved
06/06/2006
WATER SERVICE INSTALLATION
Rated Assembly Inspection Passed 06/06/2006
Correction
Resolved
06/06/2006
RATED WALLS @ STAIRWELL
Correction
Resolved
06/06/2006
MECHANICAL SHAFT SOUTH OF STAIRWELL
Sewer Service Inspection Passed 06/06/2006
Correction
Resolved
06/06/2006
SEWER SERVICE INSTALLATION
Underground Plumbing Inspection - Commercial Passed 06/06/2006
Correction
Resolved
06/06/2006
FIRE PROTECTION WATER LINE
Rough Framing Inspection - Commercial Passed 06/06/2006
Correction
Resolved
06/06/2006
L.G. STEEL FRAMING FOR BRICK FACADE ABOVE WINDOW-WALL
Correction
Resolved
06/06/2006
READINESS FOR INSPECTION
Occupancy Inspection - Codes Commercial Failed 06/08/2006
Correction
Corrective Action Required
06/08/2006
Receive Planning & Development Approval NO ISSUES PRESENTED TO DATE
Correction
Corrective Action Required
06/08/2006
Receive Public Works Approval COORDINATE W/ BILL LYON
Correction
Corrective Action Required
06/08/2006
Receive Water Utilities Approval COORDINATE W/ BEN HASKAMP
Correction
Resolved
06/08/2006
ROOFTOP CLEAN-UP
Correction
Resolved
06/08/2006
REQUIRED ELECTRICAL RECEPTACLE OUTLETS
Correction
Partial Correction
06/08/2006
LABELING OF ELECTRICAL SWITCHES & CIRCUIT BREAKERS NEC 408.4 LABELELING OF PANELS TO BE COMPLETED
Correction
Resolved
06/08/2006
PVC DRAIN PIPING @ 107
Correction
Resolved
06/08/2006
UNTERMINATED MC CABLE AT N WALL OF NCORR 102 & 202 TEMPORARY PROTECTION IN PLACE
Correction
Resolved
06/08/2006
HVAC DUCT INSULATION @ 111 & 206 JOINTS SEALED
Correction
Resolved
06/08/2006
ROOF DRAIN PIPING @ 111 EAST WALL HANGER SECURED
Correction
Resolved
06/08/2006
ACCESSIBILITY OF ROOF DRAIN CLEANOUTS RESOLVED DURING IN-WALL INSPECTIONS
Correction
Resolved
06/08/2006
LOW VOLTAGE ELECTRICAL CABLE @ 111 NEAR WEST WALL REMOVED
Correction
Resolved
06/08/2006
PLUMBING FIXTURES @ 412 CAULK W.C. TO FLOOR
Correction
Resolved
06/08/2006
SERVER ROOM ABOVE-CEILING WORK
Correction
Resolved
06/08/2006
INCANDESCENT LUMINAIRE @ FURNACE ROOM PROTECTED
Correction
Resolved
06/08/2006
ELECTRICAL RECEPTACLE AT 422 SOUTH WALL
Correction
Resolved
06/08/2006
CONDENSATE DRAIN LINES @ FURNACE ROOM SUPPORT/SECURE COPPER PIPE @ EAST WALL
Correction
Corrective Action Required
06/08/2006
OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FURNITURE NO BUSINESS OPERATIONS
Correction
Corrective Action Required
06/08/2006
LICENSE/EXISE TAX PAYMENT NOT FOUND RECEIVED
Correction
Corrective Action Required
06/08/2006
WATER TAP FEE PAYMENT NOT FOUND RECEIVED
Occupancy Inspection - Codes Commercial Failed 06/09/2006
Correction
Resolved
06/09/2006
Receive Fire Department approval PER CPT JOE DIR
Correction
Corrective Action Required
06/09/2006
Receive Planning & Development Approval SEE INSPECTION REPORT PROVIDED CONTACT HECTO SOTO PHONE 816-969-7317
Correction
Corrective Action Required
06/09/2006
Receive Public Works Approval COORDINATE W/ BILL LYON PHONE 816-969-1800
Correction
Resolved
06/09/2006
PASSENGER ELEVATOR INSTALLATION APPROVED INSPECTION DATED 6/9/06
Correction
Resolved
06/09/2006
LABELING OF ELECTRICAL SWITCHES & CIRCUIT BREAKERS NEC 408.4 LABELELING OF 2 PANELS TO BE COMPLETED
Correction
Partial Correction
06/09/2006
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
06/09/2006
LICENSE/EXISE TAX PAYMENT RECEIVED
Correction
Resolved
06/09/2006
WATER TAP FEE PAYMENT RECEIVED
Occupancy Inspection - Codes Commercial Failed 07/07/2006
Correction
Resolved
07/07/2006
Receive Public Works Approval PER BILL LYON 7/7/06
Correction
Resolved
07/07/2006
Receive Water Utilities Approval PER BEN HASKAMP 6/7/06
Occupancy Inspection - Codes Commercial Passed 07/26/2006
Correction
Resolved
07/26/2006
Receive Planning & Development Approval PER HECTO SOTO 7/26/06
Correction
Resolved
07/26/2006
REQUIRED ELECTRICAL RECEPTACLE OUTLETS
Correction
Resolved
07/26/2006
PASSENGER ELEVATOR INSTALLATION
Correction
Resolved
07/26/2006
LABELING OF ELECTRICAL SWITCHES & CIRCUIT BREAKERS
Correction
Resolved
07/26/2006
PVC DRAIN PIPING @ 107
Correction
Resolved
07/26/2006
UNTERMINATED MC CABLE AT N WALL OF NCORR 102 & 202
Correction
Resolved
07/26/2006
HVAC DUCT INSULATION @ 111 & 206
Correction
Resolved
07/26/2006
ROOF DRAIN PIPING @ 111 EAST WALL
Correction
Resolved
07/26/2006
ACCESSIBILITY OF ROOF DRAIN CLEANOUTS
Correction
Resolved
07/26/2006
LOW VOLTAGE ELECTRICAL CABLE @ 111 NEAR WEST WALL
Correction
Resolved
07/26/2006
PLUMBING FIXTURES @ 412
Correction
Resolved
07/26/2006
SERVER ROOM
Correction
Resolved
07/26/2006
INCANDESCENT LUMINAIRE @ FURNACE ROOM
Correction
Resolved
07/26/2006
ELECTRICAL RECEPTACLE AT 422 SOUTH WALL
Correction
Resolved
07/26/2006
CONDENSATE DRAIN LINES @ FURNACE ROOM
Correction
Resolved
07/26/2006
OCCUPANCY APPROVAL STATUS
Correction
Resolved
07/26/2006
LICENSE/EXISE TAX PAYMENT
Correction
Resolved
07/26/2006
WATER TAP FEE PAYMENT
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home