Summary
B0500321
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
ADDITION COMMERCIAL
DINNING FACILITY BUILDING ADDITION
03/08/2005
04/11/2005
10/08/2005
11/15/2006
Locations
Contacts
SHAFER KLINE & WARREN, Address:2940 MAIN ST  
GASTINGER WALKER HARDEN ARCHITECTS, Address:817 WYANDOTTE  
THE WEITZ COMPANY, Address:9900 W 109TH ST  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/03/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2003 IBC 1009.11 - Handrails. Stairways shall have handrails on each side. Handrails shall be adequate in strength and attachment in accordance with Section 1607.7. Handrails for ramps, where required by Section 1010.8, shall comply with this section.
Correction

Codes Administration - 2003 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches (178 mm) maximum and 4 inches (102 mm) minimum. Stair tread depths shall be 11 inches (279 mm) minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 0.375 inch 99.5 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm). Winder treads shall have a minimum tread depth of 11 inches (279 mm) measured at a right angle to the tread's leading edge at a point 12 inches (305 mm) fron the side where the treads are narrower and a minimum tread depth of 10 inches (254 mm). The greatest winder tread depth at the 12 inch (305 mm) walk line within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm).
Correction

Codes Administration - 2003 IBC 705.2 - Structural stability. Fire walls shall have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall for the duration of time indicated by the required fire -resistance rating.
Correction

Codes Administration - 2003 IBC 705.4 - Fire-resistance rating. Fire walls shall have a fire-resistance rating of not less than that required by Table 705.4.
Correction

Codes Administration - 2003 IBC 705.5.1 - Exterior walls. Where the fire wall intersects the exterior walls, the fire-resistance rating for the exterior walls on both sides of the fire wall shall have a 1-hour fire-resistance rating with 3/4-hour opeingin protection where opening protection is required. The fire-resistance rating of the exterior wall shall extend a minimum of 4 feet )1220 mm) on each side of the intersection of the fire wall to exterior wall. Exterior wall intersections at fire walls that form an angle equal to or greater than 180 degrees (3.14 rad) do not need exterior wall protection.
Correction

Codes Administration - 2003 IBC 705.6.1 - Stepped buildings. Where a fire wall serves as an exterior wall for a building and separates buildings having different roof levels, such wall shall terminate at a point not less than 30 inches (762 mm) above the lower roof level, provided the exterior wall for a height of 15 feet (4572 mm) above the lower roof is not less than 1-hour fire-resistance-rated construction from both sides with opeinings protected by assemblies having a 3/4-hour fire protection rating.
Correction

Codes Administration - The electrical plans indicate an exit sign from the dining addition to the existing building. This cased opening is to now have coiling fire door.
Correction

Codes Administration - The electrical plans show an exit sign at door 112-1 which leads to the patio. The outer edge of the patio has an 18 inch high retaining wall.
Correction

Codes Administration - The plans indicate that Structural Insulated Panels are to be used.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Codes Administration - Lee's Summit Code of Ordinance Ordinance 17-6 - Smoke-free establishment (Existing and New). Food service establishments that elect to be smoke-free, including all existing and new fast food establishments which are required to be smoke-free, shall post the following signage: "THIS IS A SMOKE-FREE ESTABLISHMENT. Smoking is not permitted within this establishment. (Pursuant to LSCO Sec. 17-6.)
Correction

Codes Administration - The cost of this portion of the project has not been provided.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $3,461.00 $3,461.00 Paid 04/11/2005
24 BLDG Plan Check Fees $77.65 $77.65 Paid 04/11/2005
25 Electrical Permit Fee $199.36 $199.36 Paid 04/11/2005
25 Mechanical Permit Fees $37.00 $37.00 Paid 04/11/2005
25 Plumbing Permit Fees $11.00 $11.00 Paid 04/11/2005
84 Water Meters $625.00 $625.00 Paid 08/18/2005
85 Water Taps $13,670.00 $13,670.00 Paid 08/18/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/14/2005
Correction
Resolved
07/14/2005
UNDER-SLAB DWV & WATER PIPING WITH U/G PIPE INSULATION BEFORE BACKFILL OK TO COVER WHEN READY HW PIPE TO BE ENCASED
Footing Inspection - Commercial Passed 07/14/2005
Correction
Resolved
07/14/2005
INTERIOR COLUMN FOOTING POUR PREP APPROVED 7/12/05
Correction
Resolved
07/14/2005
PERIMETER GRADE BEAM + INTEGRAL COLUMN FOOTINGS APPROVED 7/12/05
Sewer Service Inspection - Commercial Request Complete 7/15/2005 7/15/2005 07/15/2005
Underslab Electrical Inspection - Commercial Passed 07/19/2005
Correction
Resolved
07/19/2005
UNDER-FLOOR ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP OK TO COVER WHEN READY
Underground Plumbing Inspection - Commercial Partial 07/21/2005
Correction
Partial Correction
07/21/2005
STORM WATER APPROVED TO COVER 10' SHORT OF TEE ON WEST SIDE TO ELBOW AT AIR INLET. COURTYARD
Sewer Service Inspection - Commercial Request Complete 7/21/2005 7/21/2005 07/21/2005
Underground Plumbing Inspection - Commercial Partial 07/22/2005
Correction
Resolved
07/22/2005
TEXT LINE SOUTH OF NEW BUILDING: APPROVED TO COVER ALL EXCEPT TEE AT MAIN. NOTE: SLOPES ADJUSTED UNDER DIRECTION OF ENGINEER.
Sewer Service Inspection - Commercial Request Complete 7/22/2005 7/22/2005 07/22/2005
Rough Electrical Inspection - Commercial Passed 11/07/2005
Correction
Resolved
11/07/2005
CONDUIT + BOXES FOR STEP LIGHTS IN RETAINING WALL @ N PATIO OK TO COVER WHEN READY
Rough Plumbing Inspection - Commercial Partial 11/22/2005
Correction
Partial Correction
11/22/2005
COPPER WATER PIPING H&C PIPING IN CLOSET @ DOOR 113/4 + TO ROOF HYDRANT ABOVE; OK TO INSULATE WHEN READY PORTIONS LISTED BELOW:
Rough Electrical Inspection - Commercial Passed 11/28/2005
Correction
Resolved
11/28/2005
CONDUIT + BOXES FOR STEP LIGHTS IN RETAINING WALL @ S PATIO OK TO COVER WHEN READY
Gas Service Inspection - Commercial Passed 11/28/2005
Correction
Resolved
11/28/2005
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 60 PSI FOR >=30 MIN
Gas Piping Inspection - Commercial Passed 11/28/2005
Correction
Resolved
11/28/2005
1-1/2" PIPING TO RTU-1 + RTU-2
All Rough Inspection - Commercial Partial 12/07/2005
Correction
Partial Correction
12/07/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 115 S WALL; 115 N WALL OK TO ONE-SIDE AT RISK; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 12/14/2005
Correction
Partial Correction
12/14/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 115 S WALL; 115 N WALL OK TO ONE-SIDE AT RISK; 112 AFTER SILL PLATE ANCHORED PER DRAWING; 113/114 NORTH & SOUTH WALLS; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Passed 12/14/2005
Correction
Resolved
12/14/2005
CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH OK TO COVER WHEN READY THREE SOFFITS ACROSS WIDTH OF 113/114
Gas Piping Inspection - Commercial Passed 12/14/2005
Correction
Resolved
12/14/2005
1-1/2" PIPING TO RTU-1 + RTU-2
Correction
Resolved
12/14/2005
GAS PIPING TO FIREPLACE @ NORTH WALL AT >= 10 PSI FOR >=10 MIN TEST PRESSURE LEVEL HELD STEADY
Above Ceiling Inspection Partial 12/22/2005
Correction
Partial Correction
12/22/2005
CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH THREE SOFFIT BANDS ACROSS WIDTH OF 113/114; 115; FASCIA/SOFFIT @ 112 WEST; OK TO COVER WHEN READY AREAS LISTED BELOW:
Miscellaneous Inspection Passed 12/28/2005
Correction
Resolved
12/28/2005
ANCHOR BOLT INSPECTION 113, 114 - ANCHOR BOLT INSTALLATION APPROVED OK TO COVER COMMON AREA
Miscellaneous Inspection Passed 01/02/2006
Correction
Resolved
01/02/2006
ANCHOR BOLT INSPECTION
All Rough Inspection - Commercial Partial 01/02/2006
Correction
Partial Correction
01/02/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 115 S WALL; 115 N WALL OK TO ONE-SIDE AT RISK; 112; 113/114 N & S WALLS; 113, 114 E & W WALLS; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 01/06/2006
Correction
Partial Correction
01/06/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 115 S WALL; 115 N WALL OK TO ONE-SIDE AT RISK; 112; 113/114 N & S WALLS; 113, 114 E & W WALLS; WALL BUMP-OUT FRAMING & M/E/P @ 112 SOUTHEAST + 113 NORTH; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Underground Electrical Inspection - Commercial Passed 01/25/2006
Correction
Resolved
01/25/2006
PVC CONDUIT CONCRETE ENCASE CONDUIT WHERE < 18" DEEP AT TRANSITIONS W & SW OF BLDG FOR LIGHTS + TO WATER B/F ENCLOSURE
Occupancy Inspection - Codes Commercial Failed 04/12/2006
Correction
Corrective Action Required
04/12/2006
None THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS APPROVED TO INSTALL/STORE FURNITURE DO NOT OCCUPY
Correction
Corrective Action Required
04/12/2006
Through Penetrations (IRC) SEAL NATURAL GAS PIPE ENTRY EXTERIOR
Correction
Corrective Action Required
04/12/2006
SIGNAGE POST MAXIMUM OCCUPANCY SIGNAGE
Correction
Corrective Action Required
04/12/2006
Handrails (IRC) HANDRAILS TO BE 34-38" HIGH AS MEASURED AT PLANE OF TOES
Correction
Corrective Action Required
04/12/2006
TEXT RESOLVE PENDING INSPECTION ITEMS FROM: ALL-ROUGH UNDERGROUND PLUMBING ABOVE CEILING
Correction
Corrective Action Required
04/12/2006
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
Receive Fire Department approval UNDER SEPARATE COVER
Occupancy Inspection - Codes Commercial Failed 04/14/2006
Correction
Partial Correction
04/14/2006
None THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS 30 DAY TCO
Correction
Resolved
04/14/2006
Through Penetrations (IRC)
Correction
Resolved
04/14/2006
SIGNAGE
Correction
Corrective Action Required
04/14/2006
Handrails (IRC) HANDRAILS TO BE 34-38" HIGH AS MEASURED AT PLANE OF TOES
Occupancy Inspection - Codes Commercial Failed 05/12/2006
Correction
Resolved
05/12/2006
Receive Fire Department approval APPROVED ON SITE BY CPTN. JOE DIRR
Correction
Resolved
05/12/2006
Handrails (IRC)
Underslab Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
UNDER-SLAB DWV & WATER PIPING
Underground Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
STORM WATER
Correction
Resolved
05/16/2006
TEXT
Rough Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
COPPER WATER PIPING
Above Ceiling Inspection Passed 05/16/2006
Correction
Resolved
05/16/2006
CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH
All Rough Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Occupancy Inspection - Codes Commercial Failed 05/16/2006
Correction
Resolved
05/16/2006
TEXT
Correction
Resolved
05/16/2006
Handrails (IRC)
Correction
Resolved
05/16/2006
SIGNAGE
Correction
Resolved
05/16/2006
Through Penetrations (IRC)
Correction
Resolved
05/16/2006
None
Occupancy Inspection - Codes Commercial Passed 05/17/2006
Correction
Resolved
05/17/2006
Receive Fire Department approval PER CPT JOE DIR
Correction
Resolved
05/17/2006
Receive Public Works Approval NO REMAINING ISSUES
Correction
Resolved
05/17/2006
Receive Planning & Development Approval NO REMAINING ISSUES
Correction
Resolved
05/17/2006
TEXT
Correction
Resolved
05/17/2006
Handrails (IRC)
Correction
Resolved
05/17/2006
SIGNAGE
Correction
Resolved
05/17/2006
Through Penetrations (IRC)
Correction
Resolved
05/17/2006
None
Correction
Resolved
05/17/2006
OCCUPANCY APPROVAL STATUS CHAPTER 353 CERTIFICATE OF COMPLIANCE NO ISSUES REMAINING OK FOR PROCESSING OF
Occupancy Inspection - Codes Commercial Passed 11/13/2006
Correction
Resolved
11/13/2006
OCCUPANCY APPROVAL STATUS CHAPTER 353 CERTIFICATE OK PER M DUNNING 11/13/06
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home