Permit Application Status

B0500319


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500319
Building Permit - Residential
Certificate of Occupancy
WALLACE MICHAEL L & ANNE E
NEW SINGLE FAMILY
HOUSE
03/07/2005
03/10/2005
05/31/2008
03/24/2008
Locations
Contacts
BKS CONSTRUCTION, Address:PO BOX 291  
AFC HEATING & COOLING INC, Address:824 NW MAIN ST  
BRIGHT PLUMBING, Address:250 NW COMMERCE CT  
GREGORY ELECTRICAL SERVICES, Address:315 N RANDOLPH  
WALLACE MICHAEL L & ANNE E, Address:3361 SW JESSIE LN  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/04/2005 10/29/2010
Correction

Codes Administration- Bedrooms located in basements shall have at least one operable window or door approved for emergency escape which opens to the exterior. All escape or rescue windows shall have a minimum net clear openable area of 5.7 square feet. The net clear openable height shall be 24 inches. The minimum net clear openable width shall be 20 inches. The finished sill height shall not exceed 44 inches above the finished floor. (UBC Section 1204).
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The holder of this permit agrees and understands that the work authorized by this permit shall be performed in accordance with the 2000 International Residential Code as amended by Chapter 7 of the Lee's Summit Code of Ordinances.
Correction

CA - The holder of this permit agrees and understands that only persons authorized per LSCO 7-130 are permitted to perform electrical, plumbing or mechanical work authorized by this permit.
Correction

In a combined effort with both the R-4, and the R-7 School Districts the City of Lee's Summit is working together to educate the development community on a new program, the "Lee's Summit Voluntary Residential Development Surcharge". This is a program, which will help raise capital to build new schools for our community. Brochures are available at the front counter of both the Planning and Development and the Codes Administration departments. You can also find more information on the City of Lee's Summit web site at lees-summit.mo.us. (For more information please contact the Board of Education at 986-2400).
Correction

CA - 2000 IRC 401.3 - Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The grade away from foundation walls shall fall a minimum of 6 inches (152 mm) within the first 10 feet (3048 mm). 2000 IRC, Section 401.3
Correction

CA - 2000 IRC 403.1.6 - Foundation sills and exterior wall sole plates shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet on center. Anchor bolts shall be located within 12 inches from the end of each plate section. Anchor bolts shall be 1/2 inch in diameter and shall extend a minimum of 7 inches into the concrete. A nut and washer shall be tightened on each bolt to the plate. 2000 IRC, Section 403.1.6
Correction

CA - 2000 IRC 403.7.3 - The top of any exterior foundation shall extend above the elevation of the street curb or approved drainage device a minimum of 12" (twelve inches) plus 2%. Alternative elevations are permitted subject to approval of the building official, provided it can be demonstrated that required drainage to the point of discharge and away from the structure is provided at all locations on site. 2000 IRC, Section 403.7.3
Correction

CA - 2000 IRC 405.1 - Drains shall be provided around all concrete or masonry foundations that retain earth and enclose habitable or useable space. Drainage tiles, gravel drains or perforated pipe drainage systems shall be installed at or below the area to be protected and discharge by gravity or mechanical means. Perforated pipe shall be placed upon at least 2 inches of washed gravel or crushed rock and covered with not less than 6 inches of the same material. (2000 IRC, Section 405.1)
Correction

CA - 2000 IRC 703.9 - Foundation walls shall extend above the finished grade a minimum of 4 inches where masonry veneer is used and a minimum of 6 inches elsewhere. (2000 IRC, Section 404.1.6) Exterior Insulation Finish Systems, EFIS, shall terminate not less than 6 inches above finished grade. (2000 IRC, Section 703.9)
Correction

CA - 2000 IRC 314.3 - The minimum headroom in all parts of stairways shall not be less than 6 feet 8 inches measured vertically from the sloped plane adjoining the tread nosing or from the floor surface of the landing or platform.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-122 - Any excavation for foundations and/or footings of buildings and structures shall be backfilled within twenty-eight (28) days from the date of permit issuance unless otherwise approved by the building official.
Correction

CA - LSCO 7-128 (a)1 - Retaining walls which are over 4 feet in height measured from the bottom of the footing to the top of the wall of the wall shall be designed and sealed by a professional engineer or architect registered in the State of Missouri. In addition, the building official may waive the requirements for a permit or engineered drawings for walls over 4 feet in height if it is deemed unnecessary to require such submittals due to the location and type of wall to be installed.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-168 A - Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place before inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C 94; the concrete need not be on the job.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-930 - All dwellings shall have a controlled method of water disposal from the roofs that will collect and discharge all roof drainage to the ground at least 3 feet from the foundation walls or to an approved drainage system.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $482.00 $482.00 Paid 03/10/2005
25 Electrical Permit Fee $117.13 $117.13 Paid 03/10/2005
25 Mechanical Permit Fees $53.00 $53.00 Paid 03/10/2005
25 Plumbing Permit Fees $61.00 $61.00 Paid 03/10/2005
84 Water Meters $125.00 $125.00 Paid 03/10/2005
85 Water Taps $2,734.00 $2,734.00 Paid 03/10/2005
89 Sewer Tap Fees $450.00 $450.00 Paid 03/10/2005
Right of Way Permit $35.00 $35.00 Paid 03/10/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Failed 03/11/2005
Correction
Corrective Action Required
03/11/2005
R325 Premises Identification (IRC) PROVIDE ADDRESS
Footing Inspection - Residential Passed 03/11/2005
Water Service Inspection - R Passed 03/28/2005
Correction
Resolved
03/28/2005
NONE None TO METER SITE
Sewer Service Inspection - R Passed 03/28/2005
Sewer Service Inspection - Residential Request Complete 3/28/2005 3/28/2005 03/28/2005
Sewer Service Inspection - Residential Request Complete 3/28/2005 3/28/2005 03/28/2005
Water Service Inspection - R Passed 03/30/2005
Correction
Resolved
03/30/2005
NONE None APPROVED
Erosion Control Inspection Residential Failed 03/30/2005
Correction
Corrective Action Required
03/30/2005
LSCO 5029 XX Erosion Control EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Erosion Control Inspection Residential Failed 03/31/2005
Correction
Corrective Action Required
03/31/2005
LSCO 5029 XX Erosion Control EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underground Plumbing Inspection - Residential Passed 03/31/2005
Underground Plumbing Inspection - Residential Request Complete 3/30/2005 3/31/2005 03/31/2005
Underground Plumbing Inspection - Residential Request Complete 3/30/2005 3/31/2005 03/31/2005
Electrical Service Inspection Failed 06/08/2005
Correction
Corrective Action Required
06/08/2005
NONE None NOT READY. INSTALL SE CABLE
Driveway Inspection Passed 06/08/2005
Gas Service Inspection - Residential Failed 06/08/2005
Correction
Corrective Action Required
06/08/2005
M2416.4.1 Gas Test Pressure (IRC) PROVIDE MIN 10 PSI PRESSURE FOR TESTING
Gas Piping Inspection - Residential Passed 06/08/2005
All Rough Inspection - Residential Failed 06/08/2005
Correction
Corrective Action Required
06/08/2005
E3304.9 Prevent Physical Damage (IRC) ELECTRICAL NAIL PLATE REQUIRED AT STUD PENETRATION-GARAGE WHERE RED MARKED
Correction
Corrective Action Required
06/08/2005
MISC TIE WALL TOP PLATE AT I-BEAM GARAGE. LOOK AT TOP PLATE ABOVE I BEAM THAT WAS CUT
Correction
Corrective Action Required
06/08/2005
MISC NAIL CORNERS PER CODE NAIL 16D EVERY 24" ALONG WALL CORNER STUD TO TIE WALLS TOGETHER-THROUGHOUT
Correction
Corrective Action Required
06/08/2005
R602.8 Fireblocking (IRC) -FIREBLOCK ALL FLOOR/CEILING PENETRATIONS, IE PLUMBING TRAPS, HVAC, OPENINGS, ETC. -FIREBLOCK WALL AND VERTICAL SPACE FROM FLOOR JOIST AND FUR-DOWN SPACE-BASEMENT -FIREBLOCK B-VENT AND DUCT CHASE AND FIREPLACE FROM ATTIC
Correction
Corrective Action Required
06/08/2005
MISC ROOF COVERED PORCH PIER INSPECTION REQUIRED WHEN READY
Correction
Corrective Action Required
06/08/2005
MISC SUPPORT FRAME ABOVE FIREPLACE
Correction
Corrective Action Required
06/08/2005
MISC NAIL PLATE REQUIRED FOR DVW-THROUGHOUT NAILGUARD PLATES REQUIRED FOR DVW AND WATER ALSO
Correction
Corrective Action Required
06/08/2005
MISC INSTALL DUCT TO BATHFAN-MASTER BATH
Correction
Corrective Action Required
06/08/2005
E3801.2 Convenience Receptacle Spacing (Walls & Floors) (IRC) INSTALL FLOOR RECEPTICLE AT 2ND FL. NEAR GUARD RAIL
Correction
Corrective Action Required
06/08/2005
R502.6 Bearing (Joist/Beam Girder) (IRC) PROVIDE MIN 1.5" BEARING OF 2-2X10 BEAM ABOVE 1ST FL STAIR LANDING. INSTALL PROPER BRACKET TO ATTACH BEAM TO STRUCTURE
Correction
Corrective Action Required
06/08/2005
R502.6 Bearing (Joist/Beam Girder) (IRC) GROUT UNDER ALL I-BEAMS IN BASEMENT
Correction
Corrective Action Required
06/08/2005
MISC SECURE ALL COLUMNS TO FLOOR
Correction
Corrective Action Required
06/08/2005
E3804.7 Electrical in Air Handling Spaces (IRC) ELECTRICAL WIRING INSIDE RETURN SPACE FROM MASTER BEDROOM. PUT THE WIRE INSIDE FLEXIBLE METALLIC CONDUIT IS ACCEPTIBLE
Correction
Corrective Action Required
06/08/2005
MISC PLUMBING CLEANOUT REQUIRED TO BE ACCESSIBLE IN BASEMENT BATH FUR-OUT
Correction
Corrective Action Required
06/08/2005
MISC TEXT OKAY TO INSULATE, DO NOT ROCK
Piers/Caissons Inspection - Residential Failed 06/24/2005
Correction
Corrective Action Required
06/24/2005
NONE None NO PIER
All Rough Inspection - Residential Failed 06/24/2005
Correction
Resolved
06/24/2005
E3304.9 Prevent Physical Damage (IRC)
Correction
Corrective Action Required
06/24/2005
MISC TIE WALL TOP PLATE AT I-BEAM GARAGE. LOOK AT TOP PLATE ABOVE I BEAM THAT WAS CUT
Correction
Resolved
06/24/2005
MISC NAIL CORNERS PER CODE
Correction
Corrective Action Required
06/24/2005
R602.8 Fireblocking (IRC) -FIREBLOCK B-VENT AND DUCT CHASE FROM ATTIC
Correction
Resolved
06/24/2005
MISC ROOF COVERED PORCH PIER INSPECTION REQUIRED WHEN READY
Correction
Resolved
06/24/2005
MISC SUPPORT FRAME ABOVE FIREPLACE
Correction
Resolved
06/24/2005
MISC NAIL PLATE REQUIRED FOR DVW-THROUGHOUT
Correction
Resolved
06/24/2005
MISC INSTALL DUCT TO BATHFAN-MASTER BATH
Correction
Resolved
06/24/2005
E3801.2 Convenience Receptacle Spacing (Walls & Floors) (IRC)
Correction
Resolved
06/24/2005
R502.6 Bearing (Joist/Beam Girder) (IRC)
Correction
Resolved
06/24/2005
R502.6 Bearing (Joist/Beam Girder) (IRC)
Correction
Resolved
06/24/2005
MISC SECURE ALL COLUMNS TO FLOOR
Correction
Resolved
06/24/2005
E3804.7 Electrical in Air Handling Spaces (IRC)
Correction
Resolved
06/24/2005
MISC PLUMBING CLEANOUT REQUIRED TO BE ACCESSIBLE
Gas Service Inspection - Residential Failed 06/24/2005
Correction
Corrective Action Required
06/24/2005
M2416.4.1 Gas Test Pressure (IRC) PROVIDE MIN 10 PSI PRESSURE FOR TESTING
Electrical Service Inspection Passed 06/24/2005
Correction
Resolved
06/24/2005
NONE None -APPROVED FOR 1-200 AMP SERVICE RELEASE
All Rough Inspection - Residential Passed 06/27/2005
Correction
Resolved
06/27/2005
MISC TIE WALL TOP PLATE AT I-BEAM GARAGE. LOOK AT TOP PLATE ABOVE I BEAM THAT WAS CUT
Correction
Resolved
06/27/2005
R602.8 Fireblocking (IRC) -FIREBLOCK B-VENT AND DUCT CHASE FROM ATTIC
Correction
Resolved
06/27/2005
MISC TEXT OKAY TO INSULATE OK TO ROCK
Piers/Caissons Inspection - Residential Passed 06/27/2005
Correction
Resolved
06/27/2005
NONE None
Erosion Control Inspection Residential Passed 06/27/2005
Correction
Resolved
06/27/2005
LSCO 5029 XX Erosion Control EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Sidewalk Inspection Passed 09/14/2005
Gas Service Inspection - Residential Passed 09/15/2005
Correction
Resolved
09/15/2005
M2416.4.1 Gas Test Pressure (IRC)
Correction
Resolved
09/15/2005
NONE None GAS APPROVED TEST PRESSURE 20 PSI RELEASE GAS
Lawn Sprinkler Final Passed 11/26/2007
Correction
Resolved
11/26/2007
NONE None BACKFLOW PREVENTER INSTALLED
Occupancy Inspection - Codes Residential Failed 12/03/2007
Correction
Corrective Action Required
12/03/2007
MISC EXPOSE STORM WATER OUTLETS
Correction
Corrective Action Required
12/03/2007
MISC CIRCUIT TO LIGHT POLE 1. INSTALL CONDUCTOR RATED FOR WET LOCATION. NM CABLE NOT ALLOWED 2. INSTALL WIRE NUT AT EQUIPMENT GROUNDING CONDUCTORS TERMINAL-INSIDE METAL J-BOX 3. BOND METAL J-BOX
Correction
Corrective Action Required
12/03/2007
MISC ELECTRICAL IN BACKYARD -PLEASE CORRECT ALL THAT NEEDS TO BE CORRECTED TO MAKE THIS CODE-COMPLIANT. TOO MANY CODE VIOLATIONS HERE
Correction
Corrective Action Required
12/03/2007
E3802.3 Outdoor GFCI Receptacles (IRC) NOT TRIPPING REAR PATIO
Correction
Corrective Action Required
12/03/2007
MISC CONNECT FRONT DOWNSPOUT TO STORM WATER DRAINAGE SYSTEM
Correction
Corrective Action Required
12/03/2007
MISC GARAGE INCOMPLETED
Correction
Corrective Action Required
12/03/2007
MISC KITCHEN COOKTOP 1. J-BOX IS OVERFILLED. 7 CONDUCTOR FILLS OF #8 2. SECURE FLEXIBLE CONDUIT WITHIN 12" OF J-BOX 3. BOND BOX IF METAL J-BOX IS INSTALLED (SEE #1 ABOVE)
Correction
Corrective Action Required
12/03/2007
MISC INSTALLED ELECTRICAL BOX EXTENSIONS AT FOLLOWING 1. ALL DINING RM REAR WALL RECEPTACLE BOXES 2. LOFT FLOOR RECEPTACLE BOX
Correction
Corrective Action Required
12/03/2007
MISC ALL EGRESS DOOR HARDWARE REPLACE ALL EGRESS DOOR HARDWARE WITH HARDWARE THAT DO NOT REQUIRE KEY OR SPECIAL EFFORT TO OPEN. FRONT ENTRANCE DOOR AND REAR DOORS
Correction
Corrective Action Required
12/03/2007
E3903.11 Fixtures in Clothes Closets INSTALL FLOURESCENT LIGHT FIXTURE. CURRENT INCANDESCENT FIXTURE HAS LESS THAN 12" CLEARANCE FROM SHELF MASTER BATH
Correction
Corrective Action Required
12/03/2007
E4109.4 Hydromassage Bathtub Bonding (IRC) MASTER BATH
Correction
Corrective Action Required
12/03/2007
MISC FIREBLOCK FLOOR AT HYDROTUB TRAP MASTER BATH
Correction
Corrective Action Required
12/03/2007
MISC FRONT ENTRANCE LIGHT-BURN OUT BULB
Correction
Corrective Action Required
12/03/2007
MISC PROVIDE PERMANENT STEPS AT BASEMENT BEDROOM WINDOW DISTANCE FROM WINDOW SILL TO FINISH FLOOR IS MORE THAN 44" BASEMENT BEDROOM
Correction
Corrective Action Required
12/03/2007
MISC WET BAR PLUMBING -SECURE ALL DRAINAGE AND VENT LINES BASEMENT
Correction
Corrective Action Required
12/03/2007
M1306.1 Appliance Clearance to Unprotected Combustible Construction (IRC) SECURE NM ELECTRICAL CABLE MINIMUM 1" AWAY FROM B-VENT MECHANICAL RM
Correction
Corrective Action Required
12/03/2007
E3802.5 Unfinished Basement GFCI Receptacles (IRC) INSTALL ONE GFCI RECEPTACLE BASEMENT PORTION BY STAIR
Correction
Corrective Action Required
12/03/2007
MISC PROVIDE FULL BEARING UNDER I BEAM AT POCKETS BASEMENT PORTION BY STAIR
Miscellaneous Inspection Passed 12/03/2007
Correction
Resolved
12/03/2007
R325 Premises Identification (IRC)
Occupancy Inspection - Codes Residential Failed 12/13/2007
Correction
Corrective Action Required
12/13/2007
MISC EXPOSE STORM WATER OUTLETS ONE ON SOUTH SIDE EXPOSED. THE DRAIN OUTLET ON NORTH SIDE CANNOT BE VERIFIED
Correction
Corrective Action Required
12/13/2007
MISC CIRCUIT TO LIGHT POLE 1. INSTALL CONDUCTOR RATED FOR WET LOCATION. NM CABLE NOT ALLOWED 2. INSTALL WIRE NUT AT EQUIPMENT GROUNDING CONDUCTORS TERMINAL-INSIDE METAL J-BOX 3. BOND METAL J-BOX
Correction
Resolved
12/13/2007
MISC ELECTRICAL IN BACKYARD
Correction
Resolved
12/13/2007
E3802.3 Outdoor GFCI Receptacles (IRC)
Correction
Corrective Action Required
12/13/2007
MISC CONNECT FRONT DOWNSPOUT TO STORM WATER DRAINAGE SYSTEM
Correction
Corrective Action Required
12/13/2007
MISC GARAGE INCOMPLETED -CARPET MUST BE REMOVED FROM GARAGE -REPAIR/REPLACE ATTIC ACCESS PANEL **ALL RECEPTACLES ARE GFCI-PROTECTED
Correction
Corrective Action Required
12/13/2007
MISC KITCHEN COOKTOP YOU FORGOT INSTALLING THE CLAMP CONNECTOR TO SECURE THE FLEXIBLE CONDUIT TO THE BOX
Correction
Corrective Action Required
12/13/2007
MISC INSTALLED ELECTRICAL BOX EXTENSIONS AT FOLLOWING 1. REAR WALL RECEPTACLE @ LIVING RM
Correction
Resolved
12/13/2007
MISC ALL EGRESS DOOR HARDWARE
Correction
Corrective Action Required
12/13/2007
E3903.11 Fixtures in Clothes Closets INSTALL FLOURESCENT LIGHT FIXTURE. CURRENT INCANDESCENT FIXTURE HAS LESS THAN 12" CLEARANCE FROM SHELF **NOTE: FLOURESCENT LIGHT FIXTURES, NOT FLOURESCENT BULBS MASTER BATH
Correction
Resolved
12/13/2007
E4109.4 Hydromassage Bathtub Bonding (IRC)
Correction
Resolved
12/13/2007
MISC FIREBLOCK FLOOR AT HYDROTUB TRAP
Correction
Resolved
12/13/2007
MISC FRONT ENTRANCE LIGHT-BURN OUT BULB
Correction
Resolved
12/13/2007
MISC PROVIDE PERMANENT STEPS AT BASEMENT BEDROOM WINDOW
Correction
Resolved
12/13/2007
MISC WET BAR PLUMBING
Correction
Resolved
12/13/2007
M1306.1 Appliance Clearance to Unprotected Combustible Construction (IRC)
Correction
Resolved
12/13/2007
E3802.5 Unfinished Basement GFCI Receptacles (IRC)
Correction
Resolved
12/13/2007
MISC PROVIDE FULL BEARING UNDER I BEAM AT POCKETS I DON'T KNOW HOW THIS WAS DONE WITHOUT REMOVING THINGS. DID YOU PUT SOMETHING SOLID UNDERNEATH THE I BEAM?
Occupancy Inspection - Codes Residential Failed 12/21/2007
Correction
Resolved
12/21/2007
MISC CIRCUIT TO LIGHT POLE
Correction
Resolved
12/21/2007
MISC CONNECT FRONT DOWNSPOUT TO STORM WATER DRAINAGE SYSTEM
Correction
Resolved
12/21/2007
MISC GARAGE INCOMPLETED
Correction
Resolved
12/21/2007
MISC KITCHEN COOKTOP
Correction
Resolved
12/21/2007
MISC INSTALLED ELECTRICAL BOX EXTENSIONS AT FOLLOWING
Correction
Resolved
12/21/2007
E3903.11 Fixtures in Clothes Closets
Water Service Inspection - R Passed 03/21/2008
Occupancy Inspection - Codes Residential Passed 03/21/2008
Correction
Resolved
03/21/2008
MISC EXPOSE STORM WATER OUTLETS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home