Summary
B0500237
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
TENANT FINISH NW CORNER 3RD FLOOR
02/24/2005
03/10/2005
09/06/2005
10/24/2005
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
LYTLE CONSTRUCTION INC, Address:1051 SE BROADWAY DR  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/23/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - Specifications for this project have not been provided.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $566.00 $566.00 Paid 03/10/2005
24 BLDG Plan Check Fees $29.40 $29.40 Paid 03/10/2005
25 Electrical Permit Fee $82.36 $82.36 Paid 03/10/2005
25 Mechanical Permit Fees $41.00 $41.00 Paid 03/10/2005
25 Plumbing Permit Fees $21.00 $21.00 Paid 03/10/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 04/07/2005
Correction
Partial Correction
04/07/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH EXCEPT PLUMBING WALLS -- NOT READY; SCREW ALL STUD FLANGES OK TO COVER WHEN READY
Rough Framing Inspection - Commercial Request Complete 4/6/2005 4/7/2005 04/07/2005
Rough Plumbing Inspection - Commercial Passed 04/12/2005
Correction
Resolved
04/12/2005
CAST IRON DWV PIPING VISUAL INSPECTION + PRESSURE TEST
Above Ceiling Inspection Failed 05/12/2005
Correction
Corrective Action Required
05/12/2005
REMOVE TEMPORARY LIGHTING.
Correction
Corrective Action Required
05/12/2005
SEE TEXT THIS INSPECTION EXCLUDES INSTALLATION OF LAY-IN LIGHTING.
Correction
Partial Correction
05/12/2005
None APPROVED TO INSTALL PERIMETER/BORDER TILES EXCEPT WHERE NOTED.
Correction
Corrective Action Required
05/12/2005
PENETRATION OF SMOKE BARRIER PATCH WALL WHERE DUCT PENETRATES. CORRIDOR SOUTH OF FINISH
Correction
Corrective Action Required
05/12/2005
PIPE INSULATION 1- COMPLETE PIPE INSULATION AT HEATING HOT WATER SERVING FAN BOXES. 2- COMPLETE PIPE INSULATION IN CORRIDOR SOUTH OF FINISHED AREA. THROUGHOUT
Correction
Corrective Action Required
05/12/2005
PIPE SUPPORT SUPPORT DOMESTIC WATER PIPING FROM STRUCTURE AT ELBOWS. BREAK ROOM 211
Correction
Corrective Action Required
05/12/2005
CONDUIT SUPPORT CONDUITS SHALL BE SUPPORTED WITHIN 12" OF JUNCTION BOXES. THROUGHOUT
Correction
Corrective Action Required
05/12/2005
PLENUM RATED CABLE PROVIDE VERIFACTION THAT ALL EXPOSED CABLES ABOVE CEILING ARE PLENUM RATED.
Correction
Corrective Action Required
05/12/2005
J-BOX INSTALLATION COMPLETE CONNECTIONS AND INSTALLATION OF JUNCTION BOXES. LEAVE EXPOSED FOR INSPECTION STORAGE ROOM 205 NORTH & EAST WALL
Above Ceiling Inspection Passed 05/25/2005
Correction
Resolved
05/25/2005
REMOVE TEMPORARY LIGHTING.
Correction
Resolved
05/25/2005
SEE TEXT
Correction
Resolved
05/25/2005
None
Correction
Resolved
05/25/2005
PENETRATION OF SMOKE BARRIER
Correction
Resolved
05/25/2005
PIPE INSULATION
Correction
Resolved
05/25/2005
PIPE SUPPORT
Correction
Resolved
05/25/2005
CONDUIT SUPPORT
Correction
Resolved
05/25/2005
PLENUM RATED CABLE
Correction
Resolved
05/25/2005
J-BOX INSTALLATION
All Rough Inspection - Commercial Passed 05/25/2005
Correction
Resolved
05/25/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Occupancy Inspection - Codes Commercial Passed 05/27/2005
Correction
Resolved
05/27/2005
Receive Fire Department approval SMOKE DEVICE COVERS REMOVED.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home