Summary
B0500162
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
BUILDING A INTERIOR FINISH
02/08/2005
04/14/2005
10/11/2005
05/17/2006
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
J E DUNN CONSTRUCTION, Address:929 HOLMES  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/07/2005 10/29/2010
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - 2003 IPC 301.3 - Connections to the sanitary drainage system. All plumbing fixtures, drains, appurtenances and appliances used to receive or discharge liquid wastes or sewage or sewage shall be directly connected to the sanitary drainage system of the building or premises, in accordance with the requirements of this code. This section shall not be construed to prevent the indirect waste systems required by Chapter 8.
Correction

Codes Administration - 2003 IBC 805.1 - General. In occupancies of Groups A, E, I, R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant in accordance with Section 805.2 and NFPA 701 or noncombustible. In Groups I-1 and I-2, combustible decorations shall be flame retardant unless the decorations, such as photographs and paintings, are of such limited quantities that a hazard of fire development or spread is not present. In Group I-3, combustible decorations are prohibited.
Correction

Code Administation - I am unable to locate dampers in the rated assemblies of the soil rooms and the suite separation.
Correction

Codes Administration - Soil room 1A083 is not idicated as having rated walls on Sheet A-2.
Correction

Codes Administration - Sheet A-2 shows area 1A079, Scheduler, as being inclosed by one-hour fire-resistive construction but the area is not inclosed on other sheets showing the area.
Correction

Codes Administration - Doors 1A043 and 1A056 are shown to be 20 minute rated in the door schedule. These doors are located in a one-hour fire-resistive wall and are required to be 45 minute rated.
Correction

Codes Administration - 2003 IBC 407.4.1 - Refuge area. At least 30 net square feet per patient shall be provided within the aggregate area of corridors, patient rooms, treatment rooms, lounge or dining areas and othe low-hazard areas on each side of each smoke barrier. On floors not housing patients confined to a bed or litter, at least 6 net square feet per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments.
Correction

Codes Administration - An exiting plan showing the occupant load at each exit device is not provided.
Correction

Codes Administration - The electrical system must be reviewed by the approved third party.
Correction

Fire Department- 703.2.1 Signs. Where required by the code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR-DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR-KEEP CLOSED.
Correction

Codes Administration - 2003 IBC 302.1.1.1 - Separation. Where Table 302.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separated fron the remainder of the building with a fire barrier. Where Table 302.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidential use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend fron the floor to the underside of the fire-resistance-rated floor/ceiling assembly or fire-resistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - Lee's Summit Code of Ordinance 17-6.D - Regulated smoking environments classified. No person with ownership, management, or control of a "Food Service Establishment" shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, with primary lettering of not less than one inch in height according to one of the following classifications of food service establishements: 1. Smoke -free establishement 2. Smoking restricted establishement.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $47,780.00 $47,780.00 Paid 04/14/2005
24 BLDG Plan Check Fees $816.30 $816.30 Paid 04/14/2005
25 Electrical Permit Fee $2,008.00 $2,008.00 Paid 04/14/2005
25 Mechanical Permit Fees $346.50 $346.50 Paid 04/14/2005
25 Plumbing Permit Fees $2,097.00 $2,097.00 Paid 04/14/2005
89 Sewer Tap Fees $2,550.00 $2,550.00 Paid 04/14/2005
Inspection Overtime $300.00 $300.00 Paid 02/03/2006
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Partial 03/31/2005
Correction
Partial Correction
03/31/2005
ROOF DRAIN SYSTEM - 2ND FLOOR LEVEL @ LOCATIONS: TWO @ A'.2/7.7; TWO @ A.6/7.6; ONE @ A.1/5.6; A.1/6.6; C.9/6.6; C.9/5.6; C.9/4.6; C.9/3.6; PRESSURE TEST OK PIPING/STACKS FROM R.D.'S
Rough Plumbing Inspection - Commercial Partial 04/05/2005
Correction
Partial Correction
04/05/2005
ROOF DRAIN SYSTEM - 2ND FLOOR LEVEL @ LOCATIONS: TWO @ A'.2/7.7; TWO @ A.6/7.6; ONE @ A.1/5.6; A.1/6.6; C.9/6.6; C.9/5.6; C.9/4.6; C.9/3.6; C.7/2; C.7/3; C.7/4; A.1/1.5; A.1/2.5; A.1/3.5; A.1/4.5; C.9/1.5; C.9/2.6; PRESSURE TEST OK PIPING/STACKS FROM R.D.'S
Correction
Partial Correction
04/05/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH VTR @: C.7/2; C.7/3; C.7/4; VISUAL INSPECTION + WATER PRESSURE TEST
Rough Plumbing Inspection - Commercial Partial 05/11/2005
Correction
Partial Correction
05/11/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; VISUAL INSPECTION + WATER PRESSURE TEST
Rough Plumbing Inspection - Commercial Partial 05/12/2005
Correction
Partial Correction
05/12/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; C.7/14.05; C.7/15.05; C.7/16.05; C.7/17.05; VISUAL INSPECTION + WATER PRESSURE TEST
Rough Plumbing Inspection - Commercial Partial 05/13/2005
Correction
Partial Correction
05/13/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; C.7/14.05; C.7/15.05; C.7/16.05; C.7/17.05; C.6/18.05; C.6/18.9; VISUAL INSPECTION + WATER PRESSURE TEST
Rough Framing Inspection - Commercial Partial 05/17/2005
Correction
Partial Correction
05/17/2005
LIGHT-GUAGE STEEL FRAMING @ EXT WALLS ON (A) FROM (1) TO (7); ON (D) FROM (1) TO (6.7); OK TO COVER WHEN READY WALL SECTIONS BELOW:
Rough Plumbing Inspection - Commercial Partial 05/17/2005
Correction
Partial Correction
05/17/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; C.7/14.05; C.7/15.05; C.7/16.05; C.7/17.05; C.6/18.05; C.6/18.9; A.4/13.05; A.4/14.05; A.4/16.05; W STACK DOWN @ B.45/17.95; VISUAL INSPECTION + WATER PRESSURE TEST
Rough Plumbing Inspection - Commercial Partial 05/19/2005
Correction
Partial Correction
05/19/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; C.7/14.05; C.7/15.05; C.7/16.05; C.7/17.05; C.6/18.05; C.6/18.9; A.4/13.05; A.4/14.05; A.4/16.05; W STACK DOWN @ B.45/17.95; A.4/14.95; A.4/15.05; B.3/17.95; B.8/12.05; VISUAL INSPECTION + WATER PRESSURE TEST
Hood/Duct Inspection Partial 05/19/2005
Correction
Partial Correction
05/19/2005
DUCTWORK FROM 2ND FLOOR LEVEL TO ROOF 2 PINHOLES IDENTIFIED + ONE SLIP JOINT TO BE BETTER CLOSED REPAIR THREE ITEMS THEN OK TO COVER
All Rough Inspection - Commercial Partial 05/19/2005
Correction
Partial Correction
05/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH EXCEPT FOR SPANDRELS 09 - 20; 75; 76; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 05/26/2005
Correction
Partial Correction
05/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 09 - 20; 75; 76; 066 SOUTH WALL; OK TO COVER WHEN READY SPACES LISTED BELOW:
Hood/Duct Inspection Partial 05/26/2005
Correction
Partial Correction
05/26/2005
DUCTWORK FROM 2ND FLOOR LEVEL TO ROOF OK TO COVER DUCTS/SHAFTS AT THIS LEVEL
Rough Plumbing Inspection - Commercial Partial 05/31/2005
Correction
Partial Correction
05/31/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Correction
Resolved
05/31/2005
DWV SYSTEM -- 2ND FLOOR LEVEL SUBSYSTEMS WITH STACK OR VTR @: C.7/2; C.7/3; C.7/4; A.4/6.05; C.7/13.15; C.7/14.05; C.7/15.05; C.7/16.05; C.7/17.05; C.6/18.05; C.6/18.9; A.4/13.05; A.4/14.05; A.4/16.05; W STACK DOWN @ B.45/17.95; A.4/14.95; A.4/15.05; B.3/17.95; B.8/12.05; VISUAL INSPECTION + WATER PRESSURE TEST
Correction
Resolved
05/31/2005
ROOF DRAIN SYSTEM - 2ND FLOOR LEVEL @ LOCATIONS: TWO @ A'.2/7.7; TWO @ A.6/7.6; ONE @ A.1/5.6; A.1/6.6; C.9/6.6; C.9/5.6; C.9/4.6; C.9/3.6; C.7/2; C.7/3; C.7/4; A.1/1.5; A.1/2.5; A.1/3.5; A.1/4.5; C.9/1.5; C.9/2.6; PRESSURE TEST OK PIPING/STACKS FROM R.D.'S
All Rough Inspection - Commercial Partial 05/31/2005
Correction
Partial Correction
05/31/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 006 - 008; 009 - 020; 021 - 026; 066 - 068; 075; 076; 081; 082; 083; 084; 088; CORRIDORS 065, 069, 086, 077, 074, 080, 085, 087; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 06/01/2005
Correction
Partial Correction
06/01/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 FRAMING + LINER BOARD; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Rough Plumbing Inspection - Commercial Partial 06/01/2005
Correction
Partial Correction
06/01/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Partial 06/01/2005
Correction
Partial Correction
06/01/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Rated Assembly Inspection Partial 06/02/2005
Correction
Partial Correction
06/02/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 FRAMING + LINER BOARD; 1ST LAYER GWB; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 06/06/2005
Correction
Resolved
06/06/2005
BULKHEAD @ 2A073 SOUTH SOFFIT + VERTICAL FACES OK TO COVER WHEN READY
Rated Assembly Inspection Partial 06/06/2005
Correction
Partial Correction
06/06/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 06/07/2005
Correction
Resolved
06/07/2005
BULKHEAD @ 2A073 SOUTH SOFFIT + VERTICAL FACES
Correction
Partial Correction
06/07/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A006 - 008; 009 - 020; 021 - 026; 066 - 068; 075; 076; 081; 082; 083; 084; 088; CORRIDORS 065, 069, 086, 074, 077, 080, 085, 087; 070-073; 078; OK TO COVER WHEN READY SPACES LISTED BELOW:
Occupancy Inspection - Codes Commercial Partial 06/08/2005
Correction
Partial Correction
06/08/2005
ADVANCE USE OF STORAGE ROOM A038 APPROVED BY FD & CA
All Rough Inspection - Commercial Partial 06/13/2005
Correction
Partial Correction
06/13/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A006 - 026; 065 - 078; 080-088; 027-029; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 06/13/2005
Correction
Partial Correction
06/13/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 1ST LAYER GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
06/13/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Rough Plumbing Inspection - Commercial Passed 06/14/2005
Correction
Resolved
06/14/2005
ROOF DRAIN SYSTEM -- 1ST FLOOR LEVEL ALL APP'D BY MC 6/10/05
Correction
Resolved
06/14/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; REMAINDER @ 1ST FLOOR BY MC 6/10/05 VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Not Ready 06/14/2005
Correction
Partial Correction
06/14/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 1ST LAYER GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Resolved
06/14/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Gas Piping Inspection - Commercial Passed 06/15/2005
Correction
Resolved
06/15/2005
GAS PIPING TO ABOVE 1ST FLOOR @ C.7/2.2 HELD >60 PSI STEADY FOR >30 MIN FROM ENERGY CENTER BELOW VISUAL + PRESSURE TEST
Rated Assembly Inspection Partial 06/15/2005
Correction
Resolved
06/15/2005
SHAFT ENCLOSURE @ B.3/15.6 DUE TO COMPLEX CONFIGURATION OF MEP SYSTEMS. CONTINGENT ON FIRE DAMPERS AND FIRE-STOPPING AT FLOOR & ROOF LEVELS. CONSENSUS AGREEMENT AT JOBSITE AMONG JED, ACI BOLAND, CASSELL & ASSOCIATES, AND LSCA. NOT REQUIRED TO BE TYPE F THIS LOCATION ONLY
Correction
Partial Correction
06/15/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Resolved
06/15/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 FRAMING + SHAFT LINER BOARD; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Rough Plumbing Inspection - Commercial Partial 06/20/2005
Correction
Partial Correction
06/20/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; REMAINDER @ 1ST FLOOR BY MC 6/10/05; PRESS TEST @ KITCHEN B-D x 1-4; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Partial 06/20/2005
Correction
Resolved
06/20/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 1ST LAYER GWB; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Correction
Partial Correction
06/20/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 1ST FLOOR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 2ND FLR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; OK TO COVER WHEN READY SURFACES LISTED BELOW:
All Rough Inspection - Commercial Partial 06/20/2005
Correction
Partial Correction
06/20/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A006 - 029; 065-078; 080-088; 031-034; 062-064; 091; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 06/21/2005
Correction
Resolved
06/21/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 2nd LAYER GWB; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 06/21/2005
Correction
Partial Correction
06/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-005; 006 - 029; 031-034; 062-078; 080-088; 091; 104-105; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 06/22/2005
Correction
Partial Correction
06/22/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-005; 006 - 029; 031-034; 058; 062-078; 080-088; 091; 102-103; 104-105; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 06/27/2005
Correction
Resolved
06/27/2005
SHAFT ENCLOSURE @ B.3/15.6 THIS LOCATION ONLY, DUE TO COMPLEX CONFIGURATION OF MEP SYSTEMS. CONTINGENT ON FIRE DAMPERS AND FIRE-STOPPING AT FLOOR & ROOF LEVELS. CONSENSUS AGREEMENT AT JOBSITE AMONG JED, ACI BOLAND, CASSELL & ASSOCIATES, AND LSCA. 2ND FLOOR LEVEL NOT REQUIRED TO BE TYPE F
Correction
Partial Correction
06/27/2005
SHAFT ENCLOSURE @ B.8/9.5 2ND FLOOR N, W, S SIDES FRAMING + LINER BOARD; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Correction
Partial Correction
06/27/2005
FIREBLOCKING OF FLOOR EXPANSION JOINT @ (13) FROM (A) TO (B); FROM (C) TO (D); OK TO COVER WHEN READY EXTENT LISTED BELOW:
All Rough Inspection - Commercial Partial 06/27/2005
Correction
Partial Correction
06/27/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-034; 035-036; 045-051; 058; 062-078; 080-088; 091; 102-105; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Hood/Duct Inspection Partial 06/27/2005
Correction
Partial Correction
06/27/2005
DUCTWORK AT 1ST FLOOR OK TO COVER HORIZONTAL DUCTWORK AT THIS LEVEL. DROPS TO BE INSPECTED WHEN READY. EXCLUDING VERTICAL DROPS TO HOODS/EQUIPMENT
Correction
Partial Correction
06/27/2005
DUCTWORK FROM 2ND FLOOR LEVEL TO ROOF OK TO COVER DUCTS/SHAFTS AT THIS LEVEL
All Rough Inspection - Commercial Partial 06/28/2005
Correction
Partial Correction
06/28/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-034; 035-036; 045-051; 058; 062-078; 080-088; 091; 102-105; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
06/28/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 066-068; 090 N,W,S WALLS; 090A; 091-094; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 06/28/2005
Correction
Partial Correction
06/28/2005
SHAFT ENCLOSURE @ B.8/9.5 2ND FLOOR N, W, S SIDES FRAMING + LINER BOARD; 1ST LAYER GWB EXCEPT S WALL WHERE TEMP ELECT PENETRATES; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Rated Assembly Inspection Partial 06/29/2005
Correction
Resolved
06/29/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 2nd LAYER GWB; CHASE HORIZONTAL EXTENSION @ B.2/13.3 1ST LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Correction
Partial Correction
06/29/2005
SHAFT ENCLOSURE @ B.8/9.5 2ND FLOOR N, W, S SIDES FRAMING + LINER BOARD; 1ST & 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 06/29/2005
Correction
Partial Correction
06/29/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-034; 035-036; 038; 045-051; 058; 062-078; 080-088; 091; 094; 102-105; 109-111A; 114/114A; 134-135; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 06/30/2005
Correction
Partial Correction
06/30/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-034; 035-036; 038; 039; 045-051; 058; 062-078; 080-088; 091; 094; 102-105; 109-111A; 114/114A; 134-135; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); WALL ADJACENT TO CHASE ALONG (13.3) FROM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 06/30/2005
Correction
Resolved
06/30/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 2nd LAYER GWB; CHASE HORIZONTAL EXTENSION @ B.2/13.3 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 07/01/2005
Correction
Partial Correction
07/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-034; 035-036; 038; 039; 045-051; 058; 062-078; 080-088; 091; 094; 102-105; 106-107; 109-111A; 114/114A; 134-135; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); WALL ADJACENT TO CHASE ALONG (13.3) FROM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 066-068; 090 N,W,S WALLS; 090A; 091-094; 098; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/05/2005
Correction
Resolved
07/05/2005
FIREBLOCKING OF FLOOR EXPANSION JOINT @ (13) FROM (A) TO (B); FROM (C) TO (D); FROM (B) TO (C) OK TO COVER WHEN READY EXTENT LISTED BELOW:
Correction
Resolved
07/05/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A010-019; PER APPROVED DETAIL OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 07/05/2005
Correction
Partial Correction
07/05/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-036; 038-039; 040-041; 045-051; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 134-135; ALONG (19) FROM (A) TO (A.8) + (C.1) TO D); WALL ADJACENT TO CHASE ALONG (13.3) FROM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Resolved
07/05/2005
BULKHEAD @ 2A073 SOUTH
Correction
Partial Correction
07/05/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH @ ELEVATOR EQUIPMENT ROOM 1A105 SOUTH + EAST WALLS; OK TO COVER WHEN READY WALLS LISTED BELOW:
Rated Assembly Inspection Partial 07/06/2005
Correction
Partial Correction
07/06/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A004-009; 010-019; 020-024; PER APPROVED DETAIL OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 07/06/2005
Correction
Partial Correction
07/06/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 066-068; 090 N,W,S WALLS; 090A; 091-094; 098; 109 OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Resolved
07/06/2005
BULKHEAD/SOFFIT @ 2A109 OK TO COVER WHEN READY
Rough Plumbing Inspection - Commercial Partial 07/06/2005
Correction
Partial Correction
07/06/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; REMAINDER @ 1ST FLOOR BY MC 6/10/05; PRESS TEST @ KITCHEN B-D x 1-4; W @ B.8/11.9; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Partial 07/07/2005
Correction
Resolved
07/07/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR CHASE @ B.3/4.9 1ST LAYER GWB; CHASE @ B.1/4.6 2ND LAYER GWB; CHASE @ B.4/2.4 2ND LAYER GWB; CHASE @ B.5/6.4 2ND LAYER GWB; CHASE @ B.2/13.3 2nd LAYER GWB; CHASE HORIZONTAL EXTENSION @ B.2/13.3 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Correction
Resolved
07/07/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Resolved
07/07/2005
SHAFT ENCLOSURE @ B.8/9.5 2ND FLOOR N, W, S SIDES FRAMING + LINER BOARD; 1ST & 2ND LAYER GWB OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Correction
Partial Correction
07/07/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A004-009; 010-019; 020-024; 025-028; PER APPROVED DETAIL OK TO COVER WHEN READY
Correction
Partial Correction
07/07/2005
SHAFT ENCLOSURE @ C.5/12.5 FRAMING + LINER BOARD E,S,W SIDES; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 07/07/2005
Correction
Partial Correction
07/07/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 066-068; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 109 OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rough Plumbing Inspection - Commercial Partial 07/07/2005
Correction
Partial Correction
07/07/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL MAIN RISER THROUGH 2ND FLOOR: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; REMAINDER @ 1ST FLOOR BY MC 6/10/05; PRESS TEST @ KITCHEN B-D x 1-4; W @ B.8/11.9; W @ C/6; V @ B.7/11.9; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Partial 07/08/2005
Correction
Resolved
07/08/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; RM106 TYPE "A" S WALL OK WHEN FULLY-SCREWED; OK TO COVER WHEN READY WALLS/AREAS BELOW:
All Rough Inspection - Commercial Partial 07/08/2005
Correction
Partial Correction
07/08/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-036; 038-041; 042*; 043; 045-051; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); [121; 126; 127 NOT APPROVED] OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rough Plumbing Inspection - Commercial Partial 07/11/2005
Correction
Partial Correction
07/11/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL TO MAIN STACK AT: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; B-D x 1-4; W @ B.8/11.9; W @ C/6; V @ B.7/11.9; V @ B.9/6; V @ B.1/6.1; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
All Rough Inspection - Commercial Partial 07/11/2005
Correction
Partial Correction
07/11/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A003-029; 031-036; 038-041; 042*; 043; 045-051; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126; 127; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/11/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 062; 063; 065; 065A; 066-068; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 109 OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/11/2005
Correction
Resolved
07/11/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; RM106 TYPE "A" S WALL; RM 2A058 NW CORNER FRAMING + LINER BOARD; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
07/11/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A003; 004-028; 033; 036; PER APPROVED DETAIL OK TO COVER WHEN READY
Correction
Corrective Action Required
07/11/2005
SHAFT ENCLOSURE @ B.5/12.5 1ST FLOOR E & W WALL SHEETS NOT CUT FULL WIDTH + NOT FULLY SCREWED @ CORNER ANGLES
All Rough Inspection - Commercial Partial 07/12/2005
Correction
Partial Correction
07/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A012; 003-029; 031-036; 038-043; 045-051; 052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 048; 049; 053; 062; 063; 065; 065A; 066-068; 078; 078A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rough Plumbing Inspection - Commercial Partial 07/12/2005
Correction
Partial Correction
07/12/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL TO MAIN STACK AT: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; B-D x 1-4; W @ B.8/11.9; W @ C/6; V @ B.7/11.9; V @ B.9/6; V @ B.1/6.1; W @ B.1/6.1; V @ B.1/3.9; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rough Plumbing Inspection - Commercial Partial 07/13/2005
Correction
Partial Correction
07/13/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL TO MAIN STACK AT: V @ B.3/14.6; W @ A.4/14.9; V @ B.6/15.6; W @ B.6/13.4; W&V @ C.7/14.05; B-D x 1-4; W @ B.8/11.9; W @ C/6; V @ B.7/11.9; V @ B.9/6; V @ B.1/6.1; W @ B.1/6.1; V @ B.1/3.9; W @ B.1/3.9; W @ B.1/2; V @ B.1/2; VISUAL & PRESSURE TEST SUBSYSTEMS LISTED BELOW:
Rated Assembly Inspection Partial 07/13/2005
Correction
Resolved
07/13/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; RM106 TYPE "A" S WALL; RM 2A058 NW CORNER 1ST LAYER 5/8" GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
All Rough Inspection - Commercial Partial 07/13/2005
Correction
Partial Correction
07/13/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A012; 003-029; 031-036; 038-043; 045-051; 052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 07/14/2005
Correction
Partial Correction
07/14/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 048; 049; 053; 059-061; 062; 063; 065; 065A; 066-068; 078; 078A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 109; NOT APP'D: 055A; 079-085; 085A OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/14/2005
Correction
Partial Correction
07/14/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR ROOM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VESTIBULE @ TOP OF STAIR A105 FOUR WALLS BOTH FACES 2ND LAYER GWB; RM106 TYPE "A" S WALL; RM 2A058 NW CORNER 2ND LAYER 5/8" GWB; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Resolved
07/14/2005
SHAFT ENCLOSURE @ B.5/12.5 1ST FLOOR DUE TO COMPLEX CONFIGURATION OF MEP SYSTEMS. CONTINGENT ON FIRE DAMPERS AND FIRE-STOPPING AT FLOOR LEVELS ABOVE & BELOW. CONSENSUS AGREEMENT AMONG JED, ACI BOLAND, CASSELL & ASSOCIATES, AND LSCA. PER A/E & LSCA NOT REQUIRED TO BE TYPE F
All Rough Inspection - Commercial Partial 07/15/2005
Correction
Partial Correction
07/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A001; 012; 003-029; 031-036; 038-043; 045-051; 052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 048; 049; 053; 055A; 059-061; 062; 063; 065; 065A; 066-068; 078; 078A; 079-085; 085A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/15/2005
Correction
Partial Correction
07/15/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 1ST FLOOR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 2ND FLR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; W WALL 1ST LAYER GWB RE-WORK DUE TO ELECT WORK; OK TO COVER WHEN READY SURFACES LISTED BELOW:
All Rough Inspection - Commercial Partial 07/18/2005
Correction
Partial Correction
07/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A001-029; 031-036; 038-043; 045-052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130; 130D EXCEPT E WALL; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); WALL ADJ TO CHASE ALNG (13.3) FRM (B) TO (B.5); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 048; 049; 053; 055A; 059-061; 062; 063; 065; 065A; 066-068; 071-076; 077 EXCEPT W WALL; 078; 078A; 079-085; 085A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 07/19/2005
Correction
Partial Correction
07/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A001-029; 031-036; 038-043; 044; 045-052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); DOOR HEADS @ 2A101 & 2A133A; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 048; 049; 053; 055A; 059-061; 062; 063; 065; 065A; 066-068; 071-076; 077; 078; 078A; 079-085; 085A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/25/2005
Correction
Partial Correction
07/25/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES EXCEPT SW CORNER OUTSIDE FACE; 115-117 FLOOR CLOSURE @ DUCTS FRAME + LINER BOARD; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
07/25/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR RM 083 ONE LAYER GWB EXTERIOR FACE OK -- INTERIOR REQUIRES CLOSURES AT TOP OF E & S WALLS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 07/25/2005
Correction
Resolved
07/25/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2ND FLOOR: 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); DOOR HEADS @ 2A101 & 2A133A; CONT'D OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/25/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 118; 130C WEST WALL ONE FACE ONLY; 140; 141; 141A; OK TO COVER WHEN READY WALLS AT SPACES LISTED
All Rough Inspection - Commercial Partial 07/26/2005
Correction
Partial Correction
07/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 046; 048; 049; 050; 051; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-076; 077; 078; 078A; 079-085; 085A; 090 N,W,S WALLS; 090A; 091-094; 098; 099; 100; 100A/B/C/D; 106; 107; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
07/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 118; 119; 120; 130C WEST WALL ONE FACE ONLY; 131; 131A; 131B; 132; 140; 141; 141A; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 07/26/2005
Correction
Partial Correction
07/26/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR RM 083 ONE LAYER GWB BOTH FACES; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 07/27/2005
Correction
Partial Correction
07/27/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME, LINER BOARD, 2LAYERS GWB OK BUT FRAME/TOP YET TO BE SEALED; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Corrective Action Required
07/27/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A003; 004-028; 033; 036; NOT APPROVED: 037-044; 045-049 PER APPROVED DETAIL OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 07/27/2005
Correction
Partial Correction
07/27/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 118; 119; 120; 130C; 131; 131A; 131B; 132; 140; 141; 141A; OK TO COVER WHEN READY WALLS AT SPACES LISTED
All Rough Inspection - Commercial Partial 07/29/2005
Correction
Partial Correction
07/29/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A043; 044; 045; 046; 047; 048-051; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 106; 107; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 07/29/2005
Correction
Corrective Action Required
07/29/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A003; 004-028; 033; 036-044; 045-050 PER APPROVED DETAIL OK TO COVER WHEN READY
Rated Assembly Inspection Partial 08/01/2005
Correction
Partial Correction
08/01/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK AT FOLLOWING ROOMS: 2A003; 004-028; 033; 036-044; 045-050 PER APPROVED DETAIL OK TO COVER WHEN READY
Correction
Corrective Action Required
08/01/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR RM 083 ONE LAYER GWB BOTH FACES; CORR 1A097 WEST & EAST WALLS CORRIDOR FACE NOT READY FOR INSP -- SOME SHEETS NOT FULLY SCREWED OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
08/01/2005
GWB CLOSURES AT TRENCH DRAINS @ DECK ABOVE FIRST FLOOR TWO @ 033B; ONE @ 041C; 043; 045; 046; NEAR (D) ONE EACH SIDE OF BEAM @ (6), (5), (4), (3), (2) + ONE @ (1); NEAR (A) ONE @ (1) + ONE EACH SIDE OF BEAM @ (2)-(7), (13), (14); ROOMS/LOCATIONS LISTED
Correction
Corrective Action Required
08/01/2005
SHEET METAL CLOSURES AT TRENCH DRAINS @ DECK ABOVE FIRST FLOOR THREE @ 1A055; ONE @ 060; 061; 063; NEAR (A) ONE EACH SIDE OF BEAM @ (15); (16) ROOMS/LOCATIONS LISTED DETAIL APPROVED?
All Rough Inspection - Commercial Partial 08/03/2005
Correction
Partial Correction
08/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 106; 107; 109; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
08/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 118; 119; 120; 130C; 131; 131A; 131B; 132; 137; 140; 141; 141A; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 08/03/2005
Correction
Partial Correction
08/03/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME, LINER BOARD, 2LAYERS GWB; 115&116 FRAME + LINER BOARD; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
08/03/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 1ST FLOOR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 2ND FLR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; W WALL 1ST LAYER GWB RE-WORK DUE TO ELECT WORK; N WALL FRAME + LINER BOARD; OK TO COVER WHEN READY SURFACES LISTED BELOW:
Correction
Partial Correction
08/03/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR RM 083 ONE LAYER GWB BOTH FACES; CORR 1A097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6) LOWER 10' ONLY; CORR 1A057 S WALL CORRIDOR FACE; 1A078 N & E WALLS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 08/04/2005
Correction
Partial Correction
08/04/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 1ST FLOOR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 2ND FLR S WALL FRAME + LINER BOARD + 2 LAYERS GWB, N WALL FRAME + LINER BOARD, E & N WALLS 1ST LAYER GWB; OK TO COVER WHEN READY SURFACES LISTED BELOW:
Correction
Partial Correction
08/04/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR RM 083 ONE LAYER GWB BOTH FACES; CORR 1A097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); CORR 1A057 S WALL CORRIDOR FACE; 1A078 N & E WALLS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/04/2005
Correction
Partial Correction
08/04/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 115; 116; 117; 118; 119; 120; 130C; 131; 131A; 131B; 131B SHORT WALL + COLUMN; 132; 137; 140; 141; 141A; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 08/05/2005
Correction
Corrective Action Required
08/05/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME, LINER BOARD, 2LAYERS GWB; 115&116 FRAME + LINER BOARD; 130G NOT READY OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
08/05/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 1ST FLOOR S WALL FRAME + LINER BOARD + 2 LAYERS GWB; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 2ND FLR S WALL FRAME + LINER BOARD + 2 LAYERS GWB, N WALL FRAME + LINER BOARD, E, N, & W WALLS 2ND LAYER GWB; OK TO COVER WHEN READY SURFACES LISTED BELOW:
Correction
Partial Correction
08/05/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 053 E WALL; 083 ONE LAYER GWB BOTH FACES; 097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); 057 S WALL CORRIDOR FACE; 078 N & E WALLS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 08/05/2005
Correction
Partial Correction
08/05/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A (ENSURE TEMP ELECT WIRING IS REMOVED); OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/05/2005
Correction
Partial Correction
08/05/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 041; 041C-041K; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/08/2005
Correction
Partial Correction
08/08/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A092; 096; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Failed 08/08/2005
Correction
Partial Correction
08/08/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 041; 041C-041K; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Corrective Action Required
08/08/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3);
Above Ceiling Inspection Failed 08/09/2005
Correction
Partial Correction
08/09/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A092; 096; 094 NOT APPROVED OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Failed 08/09/2005
Correction
Corrective Action Required
08/09/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR, CONT'D 2A115 NOT APPROVED
All Rough Inspection - Commercial Failed 08/09/2005
Correction
Resolved
08/09/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 08/10/2005
Correction
Partial Correction
08/10/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS ONE LAYER GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME, LINER BOARD, 2LAYERS GWB; 115 WALLS FRAME + LINER BOARD + 5/8" GWB OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
08/10/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR, CONT'D 116 WALLS FRAME + LINER BOARD; 130G NOT READY;
Above Ceiling Inspection Partial 08/10/2005
Correction
Partial Correction
08/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A092; 094; 096; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
08/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS 1A051 OUTER PERIMETER; OK TO COVER WHEN READY ROOMS / PARTIALS BELOW:
All Rough Inspection - Commercial Partial 08/10/2005
Correction
Partial Correction
08/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 08/11/2005
Correction
Partial Correction
08/11/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME; 115 WALLS FRAME + LINER BOARD + 5/8" GWB + FRAME & LINER BOARD @ CEILING OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
08/11/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB OK; 053 E WALL; 057 S WALL CORRIDOR FACE; 078 N & E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 08/11/2005
Correction
Partial Correction
08/11/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS 1A050 & 051 OUTER PERIMETER FOR GWB; OK TO COVER WHEN READY ROOMS / PARTIALS BELOW:
All Rough Inspection - Commercial Partial 08/12/2005
Correction
Resolved
08/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); DOOR HEADS @ 2A101 & 2A133A; CONT'D 2ND FL SPACES/WALLS BELOW
Correction
Partial Correction
08/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; O90 LOW WALL NOT APP'D OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Corrective Action Required
08/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 115; 116; 117; 118; 119; 120; 130C; 131; 131A; 131B; 131B SHORT WALL + COLUMN; 132; 137; 140; 141; 141A; NOT APPROVED: 116 ROUGH ABOVE GWB CEILING ALREADY COVERED; 125; 129 OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 08/12/2005
Correction
Resolved
08/12/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS GWB BOTH FACES; VEST @ TOP OF STAIR 105; 106 TYPE "A" S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS FRAME; 115 WALLS FRAME + LINER BOARD + 5/8" GWB + FRAME, LINER BOARD & GWB @ CEILING OK TO COVER WHEN READY WALLS/AREAS BELOW:
Correction
Partial Correction
08/12/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR, CONT'D 116 WALLS FRAME + LINER BOARD; 130G NOT READY;
Above Ceiling Inspection Partial 08/16/2005
Correction
Partial Correction
08/16/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A; 003-009; 020-028 (ENSURE TEMP ELECT WIRING IS REMOVED); OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/16/2005
Correction
Partial Correction
08/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090 N,W,S WALLS; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; O90 LOW WALL OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Corrective Action Required
08/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 115; 116; 117; 118; 119; 120; 125; 129; 130C; 131; 131A; 131B; 131B SHORT WALL + COLUMN; 132; 137; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109 NOT APPROVED: 116 ROUGH ABOVE GWB CEILING ALREADY COVERED; OK TO COVER WHEN READY WALLS AT SPACES LISTED
All Rough Inspection - Commercial Partial 08/17/2005
Correction
Partial Correction
08/17/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
08/17/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A002; 004-007; 007B; 041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/17/2005
Correction
Partial Correction
08/17/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A; 003-009; 020-028 (ENSURE TEMP ELECT WIRING IS REMOVED); 2A067-068; 070-073; 075-076; 081; 082*; 083*; 084; *NO CEILING TO BE INSTALLED--OK PENDING FINAL OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Not Ready 08/18/2005
Correction
Corrective Action Required
08/18/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB OK; 053 E WALL; 057 S WALL CORRIDOR FACE; 078 N & E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); ALREADY COVERED: SHAFT WALL ON (9.5) FROM (B) TO (C) OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/18/2005
Correction
Partial Correction
08/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A013A,B,C,D; 021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/18/2005
Correction
Partial Correction
08/18/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A; 003-009; 020-028; 059-064; 2A067-068; 070-073; 075-076; 078; 081; 082*; 083*; 084; 085; 087; 088; 091; 093; NOT APPROVED: 066; 092 DUE TO FIREBLOCKING OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
08/18/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS 1A050 & 051 OUTER PERIMETER FOR GWB; OK TO COVER WHEN READY ROOMS / PARTIALS BELOW:
Above Ceiling Inspection Partial 08/19/2005
Correction
Partial Correction
08/19/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A; 003-009; 020-028; 2A059-064; 066; 067-068; 070-073; 075-076; 078; 081; 082*; 083*; 084; 085; 087; 088; 091; 092; 093; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 08/19/2005
Correction
Corrective Action Required
08/19/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB OK; 053 E WALL; 057 S WALL CORRIDOR FACE; 078 N & E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); NOT APPROVED: SHAFT WALL ON (9.5) FROM (B) TO (C) SEAL ALL OPENINGS IN LINER BOARD OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/19/2005
Correction
Partial Correction
08/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A013A,B,C,D; 021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/22/2005
Correction
Partial Correction
08/22/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A10A-019A; 003-009; 020-028; CORR LOCKER RECESSES @ 069 & 077 FROM (1) TO (3.6); 2A015-019; 059-064; 066-068; 070-073; 075-076; 078; 081; 082*; 083*; 084; 085; 087; 088; 091-093; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/22/2005
Correction
Partial Correction
08/22/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A002; 004-007; 007B; 031A; 041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
08/22/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A013A,B,C,D; 021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; NOT APPROVED: 011 NOT READY: 012; 014E OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 08/23/2005
Correction
Partial Correction
08/23/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A011; 012; 013A,B,C,D; 014E; 021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/23/2005
Correction
Partial Correction
08/23/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A; 002; 003-028; 029-032; 099-100; CORR RECESSES @ 069 & 077 FRM (1) TO (3.6) + 065 & 086 FRM (3.6) TO (7); 2A009-011; 013-014; 015-019; 020; 059-064; 066-068; 070-073; 074; 075-076; 078; 080; 081; 082*; 083*; 084; 085; 087; 088; 091-093; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 08/24/2005
Correction
Partial Correction
08/24/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-032; 099-100; CORR RECESSES @ 069 & 077 FRM (1) TO (3.6) + 065 & 086 FRM (3.6) TO (7); 2A009-011; 013-020; 059-064; 066-068; CORR 069 EXCEPT S END; 070-076; 078; 080; 081; 082*; 083*; 084; 085; 087-088; 091-093; NOT APPROVED: CORR 077 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
08/24/2005
ABOVE-CEILING SYSTEMS ROUGH -- ENTRANCE CANOPIES MAIN ENTRANCE CANOPY; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/24/2005
Correction
Resolved
08/24/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091; 094; 102-107; 109-111A; 114/114A; 121; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); DOOR HEADS @ 2A101 & 2A133A; 2A136, CONT'D 2ND FL SPACES/WALLS BELOW
Correction
Partial Correction
08/24/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A011; 012; 013A,B,C,D; 014E; 021 FRAMING ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; CORR 024 E WALL + W WALL FROM (3) TO (6); CORR 026 S WALL OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 08/25/2005
Correction
Partial Correction
08/25/2005
TOPS OF ELEVATOR SHAFTS ELEV #5 & #6: FRAMINING + LINER BOARD; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 08/25/2005
Correction
Partial Correction
08/25/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-032; 099-100; 2A005-008; 009-011; 013-020; 059-064; 066-068; CORR 069; 070-076; 077; 078; 080; 081; 082*; 083*; 084; 085; 087; 088; 091-093; NOT APPROVED: 021-025; 065; 086 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/25/2005
Correction
Partial Correction
08/25/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A011; 012; 013A,B,C,D; 014E; 021 ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; CORR 024 E WALL + W WALL FROM (3) TO (6); CORR 026 S WALL; D1-D3 TOP; C1-D1 T&B; NOT APP'D: 023 N WALL OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 08/26/2005
Correction
Partial Correction
08/26/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-032; 099-100; NOT APP'D: 033-039; 047-050; 052; 053B 2A005-008; 009-011; 013-020; 022-025; 059-064; 065; 066-068; CORR 069; 070-076; 077; 078; 080; 081; 082*; 083*; 084; 085; 087; 088; 091-093; NOT APP'D: 021; 086 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/26/2005
Correction
Resolved
08/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A002; 004-007; 007B; 031A; 041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Resolved
08/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A011; 012; 013A,B,C,D; 014E; 021 ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 023 N WALL; 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; CORR 024 E WALL + W WALL FROM (3) TO (6); CORR 026 S WALL; D1-D3 TOP; C1-D1 T&B; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
08/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017A; 027-029; 029A-C; 033; 033B NOT APP'D: 017; 029D; 029E; 033C; 034 OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 08/29/2005
Correction
Partial Correction
08/29/2005
TOPS OF ELEVATOR SHAFTS ELEV #5 & #6: FRAMING + LINER BOARD; 1ST LAYER 5/8" GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
08/29/2005
CLOSURES OF CMU ELEVATOR SHAFT OPENINGS ELEVATOR #6 SHAFT WALL OPENINGS @ 1ST & 2ND FLR OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 08/29/2005
Correction
Partial Correction
08/29/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-032; 033-039; 047-050; 052; 053B 2A005-008; 009-011; 013-020; 021; 022-025; 059-064; 065; 066-068; CORR 069; 070-076; 077; 078; 080; 081; 082*; 083*; 084; 085; 086; 087; 088; 091-093; 099-100; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 08/29/2005
Correction
Corrective Action Required
08/29/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 115; 116; 117; 118; 119; 120; 124; 125; 129; 130C; 131; 131A; 131B; 131B SHORT WALL + COLUMN; 132; 137; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109 NOT APPROVED: 116 ROUGH ABOVE GWB CEILING ALREADY COVERED; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Correction
Partial Correction
08/29/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033B; 034; NOT APP'D: 033C (COVERED PRIOR TO APPROVAL) OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 08/30/2005
Correction
Partial Correction
08/30/2005
CLOSURES OF CMU ELEVATOR SHAFT OPENINGS ELEVATOR #6 SHAFT WALL OPENINGS @ 1ST & 2ND FLR FRAME, LINER BOARD, 1ST LAYER GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/30/2005
Correction
Partial Correction
08/30/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033B; 033C; 034; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 08/31/2005
Correction
Partial Correction
08/31/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054; 115; 116; 117; 118; 119; 120; 124; 125; 129; 130C; 131; 131A; 131B; 132; 137; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109 NOT APPROVED: 116 ROUGH ABOVE GWB CEILING ALREADY COVERED; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Above Ceiling Inspection Partial 08/31/2005
Correction
Partial Correction
08/31/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-039; 040-046; 047-050; 052; 053B 2A005-008; 009-011; 013-020; 021; 022-025; 059-078; 080; 081; 082*; 083*; 084; 085; 086; 087; 088; 091-093; 099-100; CORRIDOR RECESSES @ 089/7.5&8.5; 056&057/001/002; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 08/31/2005
Correction
Partial Correction
08/31/2005
TOPS OF ELEVATOR SHAFTS ELEV #5 & #6: FRAMING + LINER BOARD; 1ST LAYER 5/8" GWB; 2ND LAYER 5/8" GWB OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 09/05/2005
Correction
Partial Correction
09/05/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-039; 040-046; 047-050; 052; 053B 2A003-011; 013-030; 058-078; 080; 081; 082*; 083*; 084; 085; 086; 087; 088; 091-093; 099-100; CORRIDOR RECESSES @ 089/7.5&8.5; 056&057/001/002; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 09/05/2005
Above Ceiling Inspection Partial 09/06/2005
Correction
Partial Correction
09/06/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-039; 040-046; 047-050; 052; 053B 2A003-011; 013-030; 058-078; 080; 081; 082*; 083*; 084; 085; 086; 087; 088; 091-093; 099-100; CORRIDOR RECESSES @ 089/7.5&8.5; 056&057/001/002; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Corrective Action Required
09/06/2005
See Comment MECHANICAL NOT READY ELECTRICAL, PLUMBING - READY FOR CEILING TILE Corridor 89
Above Ceiling Inspection Partial 09/08/2005
Correction
Partial Correction
09/08/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-030; 058-078; 080-088; 089; 091-093; 099-100; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Resolved
09/08/2005
See Comment
All Rough Inspection - Commercial Partial 09/08/2005
Correction
Partial Correction
09/08/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rough Framing Inspection - Commercial Partial 09/09/2005
Correction
Partial Correction
09/09/2005
LIGHT-GUAGE STEEL FRAMING @ EXT WALLS ON (A) FROM (1) TO (7); ON (D) FROM (1) TO (6.7); NOT APPROVED: BELOW WINDOWS ON (D) FROM (1) TO (3); OK TO COVER WHEN READY 1ST FLOOR WALL SECTIONS:
Above Ceiling Inspection Partial 09/09/2005
Correction
Partial Correction
09/09/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-030; 031; 032; 058-078; 080-089; 091-093; 099-100; 102-105; NOT APPROVED: 033; 034 OK TO COVER WHEN READY SPACES LISTED BELOW:
Rough Framing Inspection - Commercial Partial 09/12/2005
Correction
Partial Correction
09/12/2005
LIGHT-GUAGE STEEL FRAMING @ EXT WALLS ON (A) FROM (1) TO (7); ON (D) FROM (1) TO (6.7); BELOW WINDOWS ON (D) FROM (1) TO (3); COLUMNS (D/1)-(D/5); OK TO COVER WHEN READY 1ST FLOOR WALL SECTIONS:
Above Ceiling Inspection Partial 09/12/2005
Correction
Partial Correction
09/12/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A092; 094; 096; ELEV LOBBY 003 ABOVE ELLIPTICAL SOFFIT; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/12/2005
Correction
Resolved
09/12/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091; 094; 101; 102-107; 109-111A; 114/114A; 121; 122 S WALL @ 044; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); CONTINUED ELSEWHERE 2ND FL SPACES/WALLS BELOW
Above Ceiling Inspection Partial 09/13/2005
Correction
Partial Correction
09/13/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-032; 033; 034; 058-078; 080-089; 091-093; 099-100; 102-105; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 09/14/2005
Correction
Corrective Action Required
09/14/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB OK; 053 E WALL; 057 S WALL CORRIDOR FACE; 078 N & E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 WEST WALL CORRIDOR FACE FROM (11.8) TO (15.6); SHAFT WALL ON (9.5) FROM (B) TO (C); 1A003 WEST WALL GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 09/14/2005
Correction
Resolved
09/14/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A002; 004-007; 007B; 031A; 041; 041; 041A&B; 041C-041K; 043; 044; 045; 046; 047; 048-051; 052; 053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090; 090A; 091-094; 098-100; 100A/B/C/D; 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
09/14/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; NOT APPROVED: AA'/10.8; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 09/14/2005
Correction
Partial Correction
09/14/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-032; 033; 034; 051; 051A; 058-078; 080-089; 091-093; 098; 098A; 099; 099B; 100; 100B; 102-105; 107; 109; 110; 111; 111A; 134; 134A; 135; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rough Framing Inspection - Commercial Partial 09/14/2005
Correction
Partial Correction
09/14/2005
LIGHT-GUAGE STEEL FRAMING LOBBY 1A001 SOFFIT @ EAST WALL; ELEVATOR LOBBY 1A003 ELLIPSE SOFFIT FRAMING; OK TO COVER WHEN READY ELEMENTS LISTED BELOW:
Above Ceiling Inspection Partial 09/15/2005
Correction
Partial Correction
09/15/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-032; 033; 034; 051; 051A; 058-078; 080-089; 091-093; 098; 098A; 099; 099B; 100; 100B; 102-105; 107; 109; 110; 111; 111A; 114; 114A; 116; 134; 134A; 135; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/15/2005
Correction
Resolved
09/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091; 094; 101; 102-107; 109-111A; 114/114A; 121; 122 S WALL @ 044; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); CONT'D CONTINUED ELSEWHERE 2ND FL SPACES/WALLS BELOW
Correction
Partial Correction
09/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054 INCL KNEE WALL @ CENTER; 115; 116; 117; 118; 119; 120; 123; 124; 125; 129; 130C; 131; 131A; 131B; 132; 137; 138; 139; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 09/16/2005
Correction
Partial Correction
09/16/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR RM A072 E,N,W WALLS; VEST@TOP OF STAIR 105; 106 S WALL; 058 NW CORNER 2ND LAYER 5/8" GWB; 126 BOTH FACES; 115-117 FLOOR CLOSURE @ DUCTS; 115 WALLS & CEILING; 201 GWB W WALL FROM SOFFIT ELEV TO STRUCT ABOVE; OK TO COVER WHEN READY WALLS/AREAS BELOW:
Above Ceiling Inspection Partial 09/16/2005
Correction
Partial Correction
09/16/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-034; 036; 037; 038; 051; 051A; 058-078; 080-089; 091-093; 098; 098A; 099; 099B; 100; 100B; 102-105; 107; 108; 109-111; 111A; 113; 114; 114A; 116; 134; 134A; 135; 201 ELLIPTICAL SOFFIT FRAMING + SYSTEMS ABOVE OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/16/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A092; 094; 096; ELEV LOBBY 003 ABOVE ELLIPTICAL SOFFIT; 104 EAST SOFFIT; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/16/2005
Correction
Partial Correction
09/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054 INCL KNEE WALL @ CENTER; 115; 116; 117; 118; 119; 120; 123; 124; 125; 129; 130C; 131; 131A; 131B; 132; 137; 138; 139; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; 201 FASCIA E OF ELLIPTICAL SOFFIT OK TO COVER WHEN READY WALLS AT SPACES LISTED
Correction
Partial Correction
09/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; NOT APPROVED: AA'/10.8; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 09/19/2005
Correction
Resolved
09/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 058; 062-078; 080-088; 091-092; 094; 101-107; 109-111A; 114/114A; 121; 122 S WALL @ 044; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM (A) TO (A.8) + (C.1) TO D); (13.3) FRM (B) TO (B.5); CONT'D CONTINUED ELSEWHERE 2ND FL SPACES/WALLS BELOW
Correction
Partial Correction
09/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 09/19/2005
Correction
Partial Correction
09/19/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-034; 035; 036-038; 049; 050; 051; 051A; 058-078; 080-089; 091-093; 098; 098A; 099; 099B; 100; 100B; 102-105; 107-111; 111A; 113; 114; 114A; 116; 134; 134A; 135; 201 ELLIPTICAL SOFFIT FRAMING + SYSTEMS ABOVE OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 09/20/2005
Correction
Partial Correction
09/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-034; 035; 036-038; 049; 050; 051; 051A; 058-078; 080-089; 091-093; 094; 098; 098A; 099; 099B; 100; 100B; 102-105; 107-111; 111A; 113; 114; 114A; 116; 117; 120; 134; 134A; 135; 201 ELLIPTICAL SOFFIT OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 GWB SOFFITS; 058; 059-063; 065-067; 069-077; 079; 082-085; 085A; 092; 094; 096; ELEV LOBBY 003 ABOVE ELLIPTICAL SOFFIT; 104 EAST SOFFIT; NOT APPROVED: 052; 107; 080; 081 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/20/2005
Correction
Partial Correction
09/20/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 055 ALONG (A.8) FROM (11) TO (12); 058; 062-078; 080-088; 091-092; 094; 101-107; 109-111A; 114/114A; 121; 122 S WALL @ 044; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM(A)TO (A.8)+(C.1)TO(D); (13.3) FRM(B)TO(B.5); CONT'D CONTINUED ELSEWHERE 2ND FL SPACES/WALLS BELOW
Above Ceiling Inspection Partial 09/21/2005
Correction
Partial Correction
09/21/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-034; 035; 036-038; 049; 050; 051; 051A; 058-078; 080-089; 091-093; 094; 098; 098A; 099; 099B; 100; 100B; 102-105; 107-111; 111A; 113; 114; 114A; 116; 117; 120; 121; 134; 134A; 135; 201 ELLIPTICAL SOFFIT OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/21/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 GWB SOFFITS; 048; 049; 052; 053; 058-063; 065-067; 068; 069-077; 078A; 079; 081; 082-085; 085A; 092; 094; 096; ELEV LOBBY 003 ABOVE ELLIP SOFFIT; 104 EAST SOFFIT; 020 CIRCLE SOFFITS @ NE & S; NOT APP'D: 047; 078; 080; 098; 099; 100A-C; 107 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/21/2005
Correction
Resolved
09/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D 1A011; 012; 013A,B,C,D; 014E; 021 ABOVE E CMU WALL ON (C) FROM (2.3) TO (3); 023 N WALL; 104 N,W,S WALLS; 104A; 114; 114B; 114C; 114D; 114F; 114G; 114H; 131; 031A; CORR 024 E WALL + W WALL FROM (3) TO (6); CORR 026 S WALL; D1-D3 TOP; C1-D1 T&B; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
09/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; 020 COLUMN ENCLOSURES + WALL @ (B/2) & (B/3) OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 09/22/2005
Correction
Partial Correction
09/22/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR TOILETS 2A001A-050; 052; 053B 2A003-011; 013-038; 039-042; 049-051; 051A; 058-078; 080-089; 091-094; 098; 098A; 099; 099B; 100; 100B; 101; 102-105; 107-111; 111A; 113; 114; 114A; 116; 117; 119; 120; 121; 126; 127; 134; 134A; 135; 201 ELLIPTICAL SOFFIT OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/22/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 GWB SOFFITS; ELEV LOBBY 003 ABOVE ELLIP SOFFIT; 020 CIRCLE SOFFITS @ NE & S; 047; 048; 049; 052; 053; 058-063; 065-067; 068-077; 078; 078A; 079; 080; 081; 082-085; 085A; 092; 094; 096; 098; 099; 100A-C; 104 EAST SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 09/23/2005
Correction
Partial Correction
09/23/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A003-011; 013-038; 039-042; 049-051; 051A; 058-078; 080-089; 090; 091-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 107-111; 111A; 113; 114; 114A; 115; 116; 117; 118; 119-121; 126; 127; 134; 134A; 135; 141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/23/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 GWB SOFFITS; ELEV LOBBY 003 ABOVE ELLIP SOFFIT; 020 CIRCLE SOFFITS + SOFFIT/FASCIA @ SERVE LINE & E ENTRANCE; 046; 047-049; 052; 053; 058-063; 065-078; 078A; 079-085; 085A; 092; 094; 096; 098; 099; 100A-C; 104 EAST SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 09/23/2005
Correction
Resolved
09/23/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 2A001-029; 031-036; 038-052; 055 ALONG (A.8) FROM (11) TO (12); 058; 062-078; 080-088; 091-092; 094; 101-107; 109-111A; 114/114A; 121; 122 S WALL @ 044; 126-127; 130; 130D; 130E,F,G; 134-135; (19) FRM(A)TO (A.8)+(C.1)TO(D); (13.3) FRM(B)TO(B.5); CONT'D CONTINUED ELSEWHERE 2ND FL SPACES/WALLS BELOW
Correction
Partial Correction
09/23/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054 INCL KNEE WALL @ CENTER; 115; 116; 117; 118; 119; 120; 123; 124; 125; 129; 130C; 131; 131A; 131B; 132; 137; 138; 139; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; 201 WEST WALLS 6" & 4" RADIUS; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Above Ceiling Inspection Partial 09/26/2005
Correction
Partial Correction
09/26/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A003-011; 013-042; 043; 044; 049-051; 051A; 058-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 107-111; 111A; 113; 114; 114A; 115-121; 126; 127; 134; 134A; 135; 141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 09/27/2005
Correction
Partial Correction
09/27/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A003-011; 013-044; 049-051; 051A; 056; 057; 058-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 107-111; 111A; 113; 114; 114A; 115-121; 126; 127; 134; 134A; 135; 140; 141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/27/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 GWB SOFFITS; ELEV LOBBY 003 ABOVE ELLIP SOFFIT; 010; 020 CIRCLE SOFFITS + SOFFIT/FASCIA @ SERVE LINE & E ENT; 041-041L; 043-044; 046-049; 052-053; 055; 058-063; 065-078; 078A; 079-085; 085A; 092; 094; 096; 098-099; 100A-C; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Resolved
09/27/2005
ABOVE-CEILING SYSTEMS ROUGH -- ENTRANCE CANOPIES MAIN ENTRANCE CANOPY; CANOPY @ NE VESTIBULE 115 OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 09/27/2005
Correction
Partial Correction
09/27/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054; 095; 096; 115; 116; 117; 118; 119; 120; 123; 124; 125; 129; 130C; 131; 131A; 131B; 132; 137; 138; 139; 140; 141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; 201 N & S WALLS + WEST WALLS 6" & 4" RADIUS; OK TO COVER WHEN READY WALLS AT SPACES LISTED
Above Ceiling Inspection Partial 09/28/2005
Correction
Partial Correction
09/28/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001; 003-011; 013-044; 045-048; 049-051; 051A; 052-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 107-111; 111A; 113-114; 114A; 115-121; 126; 127; 134; 134A; 135; 140-141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/28/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE ELLIP SOFFIT; 010; 020 GWB SOFFITS & FASCIAS; 041-041L; 043-044; 046-049; 052-053; 055; 055A; 057; 058-063; 065-078; 078A; 079-085; 085A; 090A; 091; 092; 094; 096; 098-099; 100A-C; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/28/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS 1A050 & 051 OUTER PERIMETER; 2A123 & 124 OUTER PERIMETER FOR GWB OK TO COVER WHEN READY ROOMS / PARTIALS BELOW:
Above Ceiling Inspection Partial 09/29/2005
Correction
Partial Correction
09/29/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001; 002; 003-011; 013-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 106; 107-111; 111A; 113-114; 114A; 115-121; 126-127; 130; 130A; 130D; 131A; 131B; 134; 134A; 135; 140-141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/29/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE ELLIP SOFFIT; 010; 020 GWB SOFFITS & FASCIAS; 033; 033A; 033D; 034; 035; 036; 041-041L; 043-044; 046-049; 052-053; 055; 055A; 056; 057; 058-063; 089; 090; 090A; 091; 093; 097; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Resolved
09/29/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS ROOMS FOLLOWING: 1A050 & 051; 2A123 & 124 OUTER PERIMETER FOR GWB OK TO COVER WHEN READY
Correction
Partial Correction
09/29/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 065-078; 078A; 079-085; 085A; 090A; 091-092; 094; 096; 098-099; 100A-C; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 09/29/2005
Correction
Partial Correction
09/29/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 2ND FLR ALL WALLS; 1ST FLR S WALL; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 1ST FLOOR N WALL FRAME + LINER BOARD; OK TO COVER WHEN READY SURFACES LISTED BELOW:
Correction
Partial Correction
09/29/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB; 053 E WALL; 057 S WALL CORR FACE; 078 N&E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 W WALL CORR FACE FRM (11.8) TO (15.6); SHAFT WALL ON (9.5) FRM (B) TO (C); 1A003 W WALL GWB; MECH SHAFT WALL @ 007A NORTH FRAMING + LINER BOARD OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Resolved
09/29/2005
SHEET METAL CLOSURES AT TRENCH DRAINS @ DECK ABOVE FIRST FLOOR THREE @ 1A055; ONE @ 060; 061; 063; NEAR (A) ONE EACH SIDE OF BEAM @ (15); (16) APPROVED DETAIL PROVIDED ROOMS/LOCATIONS LISTED
Above Ceiling Inspection Partial 09/30/2005
Correction
Partial Correction
09/30/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001; 002; 003-011; 013-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-105; 106; 107-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 130; 130A; 130B; 130C; 130D; 131; 131A; 131B; 134; 134A; 135; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/30/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE ELLIP SOFFIT; 007B; 010; 012; 013; 013A-E; 020 GWB SOFFITS & FASCIAS; 033; 033A; 033D; 034; 035; 036; 041-041L; 043-044; 046-049; 052-053; 055; 055A; 056; 057; 058-063; 089; 090; 090A; 091; 093; 097; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/30/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 065-078; 078A; 079-085; 085A; 090A; 091-092; 094; 096; 098-099; 100A-C; 101; 102; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
09/30/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR CONT'D 140-141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/03/2005
Correction
Partial Correction
10/03/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001-011; 013-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 130; 130A; 130B; 130C; 130D; 130E; 130F; 130G; 131; 131A; 131B; 133A; 134; 134A; 135; 138; 139 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/03/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE ELLIP SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012; 013; 013A-E; 014; 014A-H; 020 GWB SOFFITS & FASCIAS; 031A; 033; 033A; 033D; 034-036; 041-041L; 043-044; 046-049; 052-053; 055; 055A; 056-063; NOT APP'D: 031 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/03/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 065-078; 078A; 079-085; 085A; 089-090; 090A; 091-092; 093; 094; 096; 097; 098-099; 100A-C; 101; 102; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 10/03/2005
Correction
Resolved
10/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR 1A002; 003 W RADIUS WALL; 004-007; 007A; 007B; 021 S WALL @ DOOR 021C; 031A; 041; 041; 041A&B; 041C-041K; 043-053; 055; 055A; 056; 059-061; 062; 063; 065; 065A; 066-068; 071-085A; 090; 090A; 091-094; 098-100; 100A/B/C/D; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Correction
Partial Correction
10/03/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; 020 COLUMN ENCLOSURES + WALL @ (B/2) & (B/3); 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 10/03/2005
Correction
Partial Correction
10/03/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2 2ND FLR ALL WALLS; 1ST FLR S WALL; 1ST FLOOR E&W WALLS FRAME + LINER BOARD + 1ST LAYER GWB; 1ST FLOOR N WALL FRAME + LINER BOARD + 1ST LAYER 5/8" GWB; OK TO COVER WHEN READY SURFACES LISTED BELOW:
Above Ceiling Inspection Partial 10/04/2005
Correction
Partial Correction
10/04/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013; 013A-E; 014; 014A-H; 020 GWB SOFFITS & FASCIAS; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 031 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/04/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 052-053; 055; 055A; 056-063; 065-078; 078A; 079-085; 085A; 089-090; 090A; 091-094; 096-099; 100A-C; 101; 102; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 10/05/2005
Correction
Partial Correction
10/05/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB; 053 E WALL; 057 S WALL CORR FACE; 078 N&E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 W WALL CORR FACE FRM (11.8) TO (15.6); SHAFT WALL ON (9.5) FRM (B) TO (C); 1A003 W WALL GWB OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
10/05/2005
CLOSURES OF CMU ELEVATOR SHAFT OPENINGS ELEVATOR #6 SHAFT WALL OPENINGS @ 1ST & 2ND FLR FRAME, LINER BOARD, 1ST LAYER GWB; 2ND FLR 2ND LAYER GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
10/05/2005
SHAFT ENCLOSURE @ (C.2/9.4) -- 1ST FLOOR NORTH, WEST, SOUTH WALLS: FRAMING + LINER BOARD; 1ST LAYER 5/8" GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 10/06/2005
Correction
Partial Correction
10/06/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001-011; 013-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 128 TO (17); 130; 130A-G; 131; 131A; 131B; 133A; 134; 134A; 135; 138-139 OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/06/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 052-053; 054; 055; 055A; 056-063; 064; 064A; 065-078; 078A; 079-085; 085A; 089-090; 090A; 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 10/06/2005
Correction
Partial Correction
10/06/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054; 095; 096; 115-120; 123-125; 129; 130C; 131; 131A; 131B; 132; 137; 138-141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; 201 N&S WALLS + W WALLS 6" & 4" RADIUS; 128 N END @ STAIR DOOR OK TO COVER WHEN READY WALLS AT SPACES LISTED
Rated Assembly Inspection Partial 10/06/2005
Correction
Partial Correction
10/06/2005
SHAFT ENCLOSURE @ (C.2/9.4) -- 1ST FLOOR NORTH, WEST, SOUTH WALLS: FRAMING + LINER BOARD; 1ST LAYER 5/8" GWB; 2ND LAYER NOT APP'D OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 10/07/2005
Correction
Partial Correction
10/07/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001-011; 012; 013-053; 056-078; 080-094; 098; 098A; 099; 099B; 100; 100B; 101-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 128 TO (17); 130; 130A-G; 131; 131A; 131B; 133A; 134; 134A; 135; 136; 138-139 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 10/07/2005
Correction
Partial Correction
10/07/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029; 029A-C; 029D; 029E; 033; 033A; 033B; 033C; 034; 038; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; 020 COLUMN ENCLOSURES + WALL @ (B/2) & (B/3); 101; 102; 106; 107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 10/12/2005
Correction
Partial Correction
10/12/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013; 013A-E; 014; 014A-H; 018; 019; 020 SOFFITS & FASCIAS; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 020; 031 OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/13/2005
Correction
Partial Correction
10/13/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014; 014A-H; 018-019; 020 SOFFITS & FASCIAS; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 020; 031; 021 OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/14/2005
Correction
Partial Correction
10/14/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014; 014A-H; 018-019; 020 SOFFITS & FASCIAS; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 020; 031; 021 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 10/18/2005
Correction
Partial Correction
10/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR 053; 053A; 053B; 054; 069 S @ ELEV ENT; 095; 096; 115-120; 123-125; 129; 130C; 131; 131A; 131B; 132; 137; 138-141; 141A; MODS @ INFANT PROTECTION WORK STATIONS @ 130B, 141, 109; 201 N&S WALLS + W WALLS 6" & 4" RADIUS; 128 N END @ STAIR DOOR OK TO COVER WHEN READY WALLS AT SPACES LISTED
Above Ceiling Inspection Partial 10/18/2005
Correction
Partial Correction
10/18/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-019; 020 SOFFITS & FASCIAS; 021; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 020; 031; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/20/2005
Correction
Partial Correction
10/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001-053; 054 EXCEPT N WALL; 055; 056-078; 080-094; 095; 096; 097; 098; 098A; 099; 099B; 100; 100B; 101-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 128 TO (17); OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-019; 020; 021; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 031; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 052-055; 055A; 056-063; 064; 064A; 065-078; 078A; 079-085; 085A; 089-090; 090A; 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/20/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR CONT'D 130; 130A-G; 131; 131A; 131B; 133A; 134; 134A; 135; 136; 138-141; 201 ELLIP SOFFIT + FASCIA E OF ELLIP; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/21/2005
Correction
Partial Correction
10/21/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR 2A001-053; 054 EXCEPT N WALL; 055; 056-078; 080-094; 095; 096; 097; 098; 098A; 099; 099B; 100; 100B; 101-111; 111A; 112 N TO (17) EXCEPT @ (C/15.5); 113-114; 114A; 115-121; 126-127; 128; NOT APP'D: 122 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 10/21/2005
Correction
Partial Correction
10/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029E; 033-033D; 034; 038; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; 020 COLUMN ENCLOSURES + WALL @ (B/2) & (B/3); 101-102; 106-107; 109; 114 CORR/LINK W/N WALL; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 10/21/2005
Correction
Partial Correction
10/21/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB; 053 E WALL; 057 S WALL CORR FACE; 078 N&E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 W WALL CORR FACE FRM (11.8) TO (15.6); SHAFT WALL ON (9.5) FRM (B) TO (C); 1A003 W WALL GWB; 114 CORR/LINK W/N WALL PART ONE LAYER 5/8" TYPE X GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 10/24/2005
Correction
Partial Correction
10/24/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D 1A014; 017; 017A; 027-029E; 033-033D; 034; 038; 064 EXCEPT EAST WALL; 064A; COLUMNS AA'/9.3; AA'/9.5; AA'/10.5; AA'/10.8; 020 COLUMN ENCLOSURES + WALL @ (B/2) & (B/3); 101-102; 106-107; 109; 330; 336; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 10/24/2005
Correction
Partial Correction
10/24/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR 047-049 E WALL GWB; 053 E WALL; 057 S WALL CORR FACE; 078 N&E WALLS; 083 ONE LAYER GWB BOTH FACES; 097 W WALL CORR FACE FRM (11.8) TO (15.6); SHAFT WALL ON (9.5) FRM (B) TO (C); 1A003 W WALL GWB; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 10/24/2005
Correction
Partial Correction
10/24/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-019; 020-021; 022; 022A-C; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 031; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/25/2005
Correction
Partial Correction
10/25/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-021; 022; 022A-C; 029; 029A; 029B; 029E; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; NOT APP'D: 031; 032; 037-040; 042 OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/26/2005
Correction
Partial Correction
10/26/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-021; 022; 022A-C; 029; 029A; 029B; 029E; 031; 032*; 037-040; 042; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
10/26/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 052-055; 055A; 056-063; 064; 064A; 065-078; 078A; 079-085; 085A; 088 ACT AREA EXCEPT N END; 089-090; 090A; 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 10/28/2005
Correction
Partial Correction
10/28/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-021; 021C; 022-022C; 029; 029A; 029B; 029E; 031; 032; 037-040; 042; 031A; 033; 033A; 033B; 033D; 034-036; 041-041L; 043-044; 046-049; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 11/02/2005
Correction
Partial Correction
11/02/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 004; 005; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 018-021; 021C; 022-022C; 024; 026; 029; 029A; 029B; 029E; 031; 032; 037-040; 042; 031A; 033; 033A; 033B; 033D; 034-036; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/02/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 041-041L; 043-044; 046-049; 052-055; 055A; 056-063; 064; 064A; 065-078; 078A; 079-085; 085A; 088 ACT AREA EXCEPT N END; 089-090; 090A; 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 11/03/2005
Correction
Partial Correction
11/03/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 003 ABOVE SOFFIT; 004; 005; 006; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 016; 018-021; 021C; 022-022C; 024; 026; 029; 029A; 029B; 029E; 030; 031; 031A; 032; 033; 033A; 033B; 033D; 034-036; 037-040; 042; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 11/07/2005
Correction
Partial Correction
11/07/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 001 S SERPENTINE 10' CEILING; 003 ABOVE SOFFIT; 004-006; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 015 ACT AREA; 016; 018-021; 021C; 022-022C; 024; 026; 029; 029A; 029B; 029E; 017; 017A NOT APPROVED OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/07/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 030-031; 031A; 032-033; 033A; 033B; 033D; 034-041L; 042-044; 046-049; 052-055; 055A; 056-064; 064A; 065-078; 078A; 079-085; 085A; 088 ACT AREA EXCEPT N END; 089-090; 090A; 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/07/2005
ABOVE CEILING SYSTEMS ROUGH -- 1ST FLOOR, CONTD
Above Ceiling Inspection Partial 11/08/2005
Correction
Partial Correction
11/08/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 001 S SERPENTINE 10' CEILING; 003 ABOVE SOFFIT; 004-006; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 015 ACT AREA; 016; 017/017A; 018-021; 021C; 022-022C; 024; 026; 029; 029A; 029B; 029E; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/08/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 030-031; 031A; 032-033; 033A; 033B; 033D; 034-041L; 042-044; 046-049; 052-055; 055A; 056-064; 064A; 065-078; 078A; 079-085; 085A; 087; 088 ACT AREA EXCEPT N END; 089-090; 090A; 091-094; 096-100A-C; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/08/2005
ABOVE CEILING SYSTEMS ROUGH -- 1ST FLOOR, CONTD 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 11/15/2005
Correction
Partial Correction
11/15/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR 1A001&002 SOFFITS; 001 S & N SERPENTINE 10' CEILING; 001 ACT 11' CEILING; 003 ABOVE SOFFIT; 004-006; 007B; 009 SOFFIT / FASCIA @ CHAPEL; 010; 012-013A-E; 014-014H; 015 ACT AREA; 016; 017/017A; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/15/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D 018-021; 021C; 022-022C; 024; 026; 029; 029A; 029B; 029E; 030-031; 031A; 032-033; 033A; 033B; 033D; 034-041L; 042-044; 046-049; 052-055; 055A; 056-064; 064A; 065-078; 078A; 079-085; 085A; 087; 088 ACT AREA EXCEPT N END; 089-090; 090A; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
11/15/2005
ABOVE CEILING SYSTEMS ROUGH -- 1ST FLOOR, CONTD 091-094; 096-100A-C; 101-102; 104 E SOFFIT; 104 CUTS AROUND CIRCLE FASCIA; 107; OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Hood/Duct Inspection Passed 12/01/2005
Correction
Resolved
12/01/2005
DUCTWORK FROM 2ND FLOOR LEVEL TO ROOF
Correction
Resolved
12/01/2005
DUCTWORK AT 1ST FLOOR
Correction
Resolved
12/01/2005
CONNECTION OF GREASE DUCTS TO KITCHEN HOODS
Occupancy Inspection - Codes Commercial Failed 12/06/2005
Correction
Resolved
12/06/2005
ADVANCE USE OF STORAGE ROOM A038 APPROVED BY FD & CA
Correction
Corrective Action Required
12/06/2005
ROOFTOP / PENTHOUSES ROOFTOP LIGHTNING PROTECTION SYSTEM NOT COMPLETED PARTIAL LIST PROVIDED TO JED 12/5/05
Occupancy Inspection - Codes Commercial Not Ready 12/06/2005
Correction
Corrective Action Required
12/06/2005
2ND FLOOR FINAL INSPECTION SOME AREAS NOT READY COMPUTERS BEING SET UP
Occupancy Inspection - Codes Commercial Failed 12/07/2005
Correction
Corrective Action Required
12/07/2005
2ND FLOOR FINAL INSPECTION PROGRESSIVE LIST PROVIDED TO JED
Rated Assembly Inspection Passed 12/10/2005
Correction
Resolved
12/10/2005
FRAMING + GWB @ MECHANICAL CHASES -- 2ND FLOOR
Correction
Resolved
12/10/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR
Correction
Resolved
12/10/2005
SHAFT ENCLOSURE @ B.3/15.6
Correction
Resolved
12/10/2005
STEEL STUD SHAFT ENCLOSURE @ ELEVATOR #2
Correction
Resolved
12/10/2005
SHAFT ENCLOSURE @ B.8/9.5 2ND FLOOR
Correction
Resolved
12/10/2005
FIREBLOCKING OF FLOOR EXPANSION JOINT @ (13)
Correction
Resolved
12/10/2005
CLOSURES AT TRENCH DRAINS @ 2ND FLOOR ROOF DECK
Correction
Resolved
12/10/2005
SHAFT ENCLOSURE @ C.5/12.5
Correction
Resolved
12/10/2005
SHAFT ENCLOSURE @ B.5/12.5 1ST FLOOR
Correction
Resolved
12/10/2005
FRAMING + GWB @ RATED WALLS -- 1ST FLOOR
Correction
Resolved
12/10/2005
GWB CLOSURES AT TRENCH DRAINS @ DECK ABOVE FIRST FLOOR
Correction
Resolved
12/10/2005
SHEET METAL CLOSURES AT TRENCH DRAINS @ DECK ABOVE FIRST FLOOR
Correction
Resolved
12/10/2005
FRAMING + GWB @ RATED WALLS -- 2ND FLOOR, CONT'D
Correction
Resolved
12/10/2005
TOPS OF ELEVATOR SHAFTS
Correction
Resolved
12/10/2005
CLOSURES OF CMU ELEVATOR SHAFT OPENINGS
Correction
Resolved
12/10/2005
SHAFT ENCLOSURE @ (C.2/9.4) -- 1ST FLOOR
Above Ceiling Inspection Passed 12/10/2005
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLOOR
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- OPERATING ROOMS
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- ENTRANCE CANOPIES
Correction
Resolved
12/10/2005
See Comment
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- 1ST FLR CONT'D
Correction
Resolved
12/10/2005
ABOVE-CEILING SYSTEMS ROUGH -- 2ND FLOOR CONT'D
Correction
Resolved
12/10/2005
ABOVE CEILING SYSTEMS ROUGH -- 1ST FLOOR, CONTD
All Rough Inspection - Commercial Passed 12/10/2005
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Correction
Resolved
12/10/2005
BULKHEAD @ 2A073 SOUTH
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLOOR
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH @ ELEVATOR EQUIPMENT ROOM 1A105
Correction
Resolved
12/10/2005
BULKHEAD/SOFFIT @ 2A109
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 2ND FLOOR
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR CONT'D
Correction
Resolved
12/10/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH -- 1ST FLR, CONT'D
Occupancy Inspection - Codes Commercial Failed 12/10/2005
Correction
Resolved
12/10/2005
ADVANCE USE OF STORAGE ROOM A038
Correction
Corrective Action Required
12/10/2005
STAIR TOWERS FINAL INSPECTION STEPS @ DOOR TO ROOF @ MIDDLE STAIR PENTHOUSE
Correction
Corrective Action Required
12/10/2005
PERFORMANCE TESTING OF KITCHEN HOODS VELOCITY TEST REPORT + SMOKE CAPTURE WITNESS
Correction
Corrective Action Required
12/10/2005
Receive Water Utilities Approval
Correction
Corrective Action Required
12/10/2005
Receive Public Works Approval
Correction
Corrective Action Required
12/10/2005
Receive Planning & Development Approval
Correction
Corrective Action Required
12/10/2005
Receive Fire Department approval
Correction
Corrective Action Required
12/10/2005
1ST FLOOR FINAL INSPECTION RECETACLES + LIGHTING @ GIFT SHOP RATED DOORS + SMOKE GASKETS ELECTRICAL ROOM ISSUES DUST COVERS TO BE REMOVED FROM FIRE/SMOKE DEVICES
Correction
Corrective Action Required
12/10/2005
2ND FLOOR FINAL INSPECTION ACCESSIBILITY OF LAVS PER 28/A-29 AND PER ANSI ELECTRICAL ROOM ISSUES RATED DOORS + SMOKE GASKETS SETBACK OF RECEPTS @ COMBUSTIBLE WALL SURFACES DUST COVERS TO BE REMOVED FROM FIRE/SMOKE DEVICES
Correction
Corrective Action Required
12/10/2005
ROOFTOP / PENTHOUSES ROOFTOP LIGHTNING PROTECTION SYSTEM NOT COMPLETED LIST PROVIDED TO JED 12/5/05
Rough Framing Inspection - Commercial Passed 12/10/2005
Correction
Resolved
12/10/2005
LIGHT-GUAGE STEEL FRAMING @ EXT WALLS
Correction
Resolved
12/10/2005
LIGHT-GUAGE STEEL FRAMING
Rough Plumbing Inspection - Commercial Passed 12/10/2005
Correction
Resolved
12/10/2005
ROOF DRAIN SYSTEM - 2ND FLOOR LEVEL
Correction
Resolved
12/10/2005
DWV SYSTEM -- 2ND FLOOR LEVEL
Correction
Resolved
12/10/2005
WASTE/VENT SYSTEM -- 1ST FLOOR LEVEL
Correction
Resolved
12/10/2005
ROOF DRAIN SYSTEM -- 1ST FLOOR LEVEL
Occupancy Inspection - Codes Commercial Failed 12/12/2005
Correction
Corrective Action Required
12/12/2005
ROOFTOP / PENTHOUSES ROOFTOP LIGHTNING PROTECTION SYSTEM AND OTHER OPEN ISSUES NOW SAID TO BE COMPLETED; TO BE INSPECTED. LIST PROVIDED TO JED 12/5/05
Correction
Partial Correction
12/12/2005
2ND FLOOR FINAL INSPECTION ACCESSIBILITY OF LAVS PER 28/A-29 AND PER ANSI INSP OF RATED DOORS + SMOKE GASKETS IN PROGRESS INSPECTION OF ELECTRICAL ROOMS IN PROGRESS DUST COVERS TO BE REMOVED FROM FIRE/SMOKE DEVICES
Correction
Partial Correction
12/12/2005
1ST FLOOR FINAL INSPECTION RECETACLES + LIGHTING @ GIFT SHOP RATED DOORS + SMOKE GASKETS INSPECTION OF ELECTRICAL ROOMS IN PROGRESS DUST COVERS TO BE REMOVED FROM FIRE/SMOKE DEVICES
Correction
Partial Correction
12/12/2005
Receive Fire Department approval OK FOR TEMP OCCUPANCY PER J EDEN 12/12/05
Correction
Corrective Action Required
12/12/2005
Receive Planning & Development Approval EXTERIOR COMPONENTS TO BE APPROVED
Correction
Corrective Action Required
12/12/2005
Receive Public Works Approval EXTERIOR COMPONENTS TO BE APPROVED
Correction
Partial Correction
12/12/2005
PERFORMANCE TESTING OF KITCHEN HOODS VELOCITY TEST REPORT + SMOKE CAPTURE WITNESS
Correction
Corrective Action Required
12/12/2005
REPAIR OF HOLES CUT IN ELEVATOR SHAFT LIDS
Correction
Corrective Action Required
12/12/2005
FINAL INSPECTION OF ENERGY CENTER AND TUNNEL INSPECTION IN PROGRESS UNDER SEPARATE PERMIT
Correction
Corrective Action Required
12/12/2005
EMERGENCY CIRCUITS IN 1A041 AT FURNITURE BEING INSTALLED YET TO BE TESTED REQUEST WHEN READY
Hood/Duct Inspection Partial 12/12/2005
Correction
Resolved
12/12/2005
SMOKE CAPTURE TEST WITNESSED 12/12/05 ALL HOODS TESTED
Correction
Partial Correction
12/12/2005
VELOCITY TESTING REPORT RECEIVED 12/12/05 TO BE REVIEWED
Occupancy Inspection - Codes Commercial Failed 12/13/2005
Correction
Corrective Action Required
12/13/2005
EMERGENCY CIRCUITS IN 1A041 AT FURNITURE BEING INSTALLED GIFT SHOP -- SAME YET TO BE TESTED REQUEST WHEN READY
Correction
Resolved
12/13/2005
STAIR TOWERS FINAL INSPECTION
Correction
Partial Correction
12/13/2005
PERFORMANCE TESTING OF KITCHEN HOODS RECEIVED; UNDER REVIEW SMOKE CAPTURE TEST OK VELOCITY TEST REPORT
Correction
Corrective Action Required
12/13/2005
ROOFTOP / PENTHOUSES RESOLVE EACH ISSUE LIST PROVIDED TO JED 12/5/05
Hood/Duct Inspection Passed 12/13/2005
Correction
Resolved
12/13/2005
VELOCITY TESTING SEE OCCUPANCY INSPECTION REPORT RECEIVED 12/12/05 REVIEW IN PROGRESS
Occupancy Inspection - Codes Commercial Failed 12/14/2005
Correction
Corrective Action Required
12/14/2005
ROOFTOP / PENTHOUSES LIST PROVIDED TO JED 12/5/05. RESOLVE EACH REMAINING ISSUE. REINSPECTION W/ J HAWLEY OF ISSUES RECORDED IN
Occupancy Inspection - Codes Commercial Failed 12/20/2005
Occupancy Inspection - Codes Commercial Failed 01/04/2006
Occupancy Inspection - Codes Commercial Failed 01/05/2006
Occupancy Inspection - Codes Commercial Failed 01/09/2006
Correction
Resolved
01/09/2006
Receive Public Works Approval NO ISSUES PRESENTED
Correction
Resolved
01/09/2006
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
01/09/2006
FINAL INSPECTION OF ENERGY CENTER AND TUNNEL CODES ISSUES RESOLVED SEE SEPARATE PERMIT
Correction
Resolved
01/09/2006
TEST OF ELECTRICAL POWER EMERGENCY TRANSFER SWITCHES ATS-1; ATS-2; ATS-3 TRANSFER TESTED OK 1/9/06
Occupancy Inspection - Codes Commercial Failed 01/10/2006
Occupancy Inspection - Codes Commercial Failed 01/11/2006
Occupancy Inspection - Codes Commercial Failed 01/12/2006
Occupancy Inspection - Codes Commercial Failed 01/13/2006
Correction
Partial Correction
01/13/2006
PERFORMANCE TESTING OF KITCHEN HOODS RECEIVED; UNDER REVIEW SMOKE CAPTURE TEST OK VELOCITY TEST REPORT
Correction
Resolved
01/13/2006
REPAIR OF HOLES CUT IN ELEVATOR SHAFT LIDS
Occupancy Inspection - Codes Commercial Failed 01/18/2006
Correction
Resolved
01/18/2006
EMERGENCY CIRCUITS @ ENERGY CENTER TESTED BY SHAW ELECTRIC SHAW CERT LTR DTD 1/9/06
Occupancy Inspection - Codes Commercial Failed 01/19/2006
Correction
Resolved
01/19/2006
ROOFTOP / PENTHOUSES REPAIR IN PROGRESS OF STUCCO HOLES/PENETRATIONS
Correction
Resolved
01/19/2006
2ND FLOOR FINAL INSPECTION
Correction
Resolved
01/19/2006
1ST FLOOR FINAL INSPECTION
Correction
Partial Correction
01/19/2006
Receive Fire Department approval
Correction
Resolved
01/19/2006
Receive Public Works Approval NO REMAINING ISSUES PRESENTED BY B LYON
Correction
Partial Correction
01/19/2006
Receive Water Utilities Approval VERIFY BACKFLOW PREVENTER ON LAWN IRRIGATION SYSTEM
Correction
Resolved
01/19/2006
EMERGENCY CIRCUITS IN 1A041 AT FURNITURE BEING INSTALLED TESTED 1/19/06
Occupancy Inspection - Codes Commercial Failed 01/23/2006
Correction
Resolved
01/23/2006
PERFORMANCE TESTING OF KITCHEN HOODS RECEIVED ACCEPTED BY A/E (JAYNT) 1/23/06. SMOKE CAPTURE TEST OK VELOCITY TEST REPORT
Occupancy Inspection - Codes Commercial Failed 01/24/2006
Correction
Resolved
01/24/2006
Receive Water Utilities Approval PER BEN HASKAMP 1/24/06
Occupancy Inspection - Codes Commercial Failed 01/25/2006
Correction
Resolved
01/25/2006
ROOFTOP / PENTHOUSES
Correction
Resolved
01/25/2006
Receive Fire Department approval PER JIM EDEN 1/25/06
Occupancy Inspection - Codes Commercial Failed 01/26/2006
Correction
Corrective Action Required
01/26/2006
Receive Planning & Development Approval 1) ALL SIGN PERMITS TO BE FINALIZED NLT 2/2/06 PER JED 2) PLANTINGS TO BE COMPLETED PER DRAWINGS + P&D RQMTS EXTERIOR COMPONENTS TO BE APPROVED
Correction
Resolved
01/26/2006
Receive Public Works Approval PER BILL LYON 1/23/06
Occupancy Inspection - Codes Commercial Failed 02/03/2006
Correction
Partial Correction
02/03/2006
Receive Planning & Development Approval PER AGREEMENT AND COMMUNICATIONS AMONG PLANNING & DEVELOPMENT, SAINT LUKES HOSPITAL, AND JE DUNN. SEE ATTACHED E-MAIL MESSAGE FROM ANTHONY CRISE TO J BORNS. COMPLETE/RESOLVE PLANTING AND SCREENING
Occupancy Inspection - Codes Commercial Passed 05/12/2006
Correction
Resolved
05/12/2006
Receive Planning & Development Approval PER M GORECKI 5/11/06
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home