Permit Application Status

B0500137


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500137
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
BUILDING E ART STUDIO RENOVATION ONLY
02/04/2005
03/29/2005
09/25/2005
11/17/2006
Locations
Contacts
THE WEITZ COMPANY, Address:9900 W 109TH ST  
SHAFER KLINE & WARREN, Address:2940 MAIN ST  
GASTINGER WALKER HARDEN ARCHITECTS, Address:817 WYANDOTTE  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/13/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Codes Administration - 2003 IBC 1008.1.2 - Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound force. The door shall be set in motion when subjected to a 30-pound force. The door shall swing to a full-open position when subjected to a 15-pound force. Forces shall be applied to the latch side.
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1014.1 - Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds the value in Table 1014.1. 2. The common path of egress travel exceeds the limitations of Section 1013.3. 3. Where required by Sections 1014.3, 1014.4 and 1014.5.
Correction

Codes Administration - 2003 IBC 302.1.1.1 - Separation. Where Table 302.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separated fron the remainder of the building with a fire barrier. Where Table 302.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidential use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend fron the floor to the underside of the fire-resistance-rated floor/ceiling assembly or fire-resistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80.
Correction

Codes Administration - The cost of this portion of the project has not been provided.
Correction

Codes Administration - 2003 IBC 715.3 - Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any materials or assembly of component materials that conforms to the test requirements of Section 715.3.1, 715.3.2 or 715.3.3 and the fire protection rating indicated in Table 715.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.
Correction

Codes Administration - The plans do not indicate the type of door hardware on the existing door located on the west end of Art Studio.
Correction

Codes Administration - I am unable to locate information regarding the kiln to be installed.
Correction

Fire Department-703.2.1 Signs. Where required by the code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR-DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR-KEEP CLOSED.
Correction

Fire Department- The occupant load of the Art Studio exceeds 50.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $452.00 $452.00 Paid 03/29/2005
24 BLDG Plan Check Fees $27.50 $27.50 Paid 03/29/2005
25 Electrical Permit Fee $57.86 $57.86 Paid 03/29/2005
25 Mechanical Permit Fees $30.50 $30.50 Paid 03/29/2005
25 Plumbing Permit Fees $17.00 $17.00 Paid 03/29/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 06/23/2005
Correction
Partial Correction
06/23/2005
None BLDG E - APPROVED - NEW PLANS WILL BE IN THE WORKS ON CHANGES THAT HAD TAKEN PLACE
Sewer Service Inspection - Commercial Request Complete 6/22/2005 6/23/2005 06/23/2005
All Rough Inspection - Commercial Failed 07/19/2005
Correction
Corrective Action Required
07/19/2005
SYSTEMS ROUGH IN-WALL AND ABOVE GWB CEILING -- INCL FRAMING ART STUDIO120> ISOLATE COPPER WATER PIPING FROM STEEL AND PROTECT PVC PIPING WHERE PENETRATION STEEL STUDS/TRACKS < 1-1/2: FROM FACE; AREAS LISTED BELOW:
All Rough Inspection - Commercial Partial 07/25/2005
Correction
Partial Correction
07/25/2005
SYSTEMS ROUGH IN-WALL AND ABOVE GWB CEILING -- INCL FRAMING ART STUDIO120; OK TO COVER WHEN READY AREAS LISTED BELOW:
Underground Electrical Inspection - Commercial Passed 10/17/2005
Correction
Resolved
10/17/2005
UNDERGROUND PVC CONDUIT @ ENTRANCE CANOPY AT LANDSCAPE AREAS OK TO COVER WHEN READY MAINTAIN 18" MIN COVER
Occupancy Inspection - Codes Commercial Failed 04/12/2006
Correction
Corrective Action Required
04/12/2006
TEXT THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS APPROVED TO INSTALL/STORE FURNITURE & SHELVING
Correction
Corrective Action Required
04/12/2006
ADA SINKS PROVIDE INSULATION ON ALL PIPING UNDER SINKS.
Correction
Corrective Action Required
04/12/2006
Receive Fire Department approval UNDER SEPARATE COVER
Occupancy Inspection - Codes Commercial Failed 04/14/2006
Correction
Partial Correction
04/14/2006
TEXT THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS 30 DAY TCO
Correction
Resolved
04/14/2006
ADA SINKS
Occupancy Inspection - Codes Commercial Failed 05/12/2006
Correction
Resolved
05/12/2006
Receive Fire Department approval APPROVED ON SITE BY CPTN. JOE DIRR
Underslab Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
None
Occupancy Inspection - Codes Commercial Failed 05/16/2006
Correction
Partial Correction
05/16/2006
TEXT
Correction
Resolved
05/16/2006
ADA SINKS
Correction
Resolved
05/16/2006
Receive Fire Department approval APPROVED ON SITE BY CPT JOE DIR
All Rough Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
SYSTEMS ROUGH IN-WALL AND ABOVE GWB CEILING -- INCL FRAMING
Occupancy Inspection - Codes Commercial Passed 05/17/2006
Correction
Resolved
05/17/2006
OCCUPANCY APPROVAL STATUS CHAPTER 353 CERTIFICATE OF COMPLIANCE NO ISSUES REMAINING OK FOR PROCESSING OF
Correction
Resolved
05/17/2006
TEXT
Correction
Resolved
05/17/2006
ADA SINKS
Correction
Resolved
05/17/2006
Receive Fire Department approval APPROVED ON SITE BY CPT JOE DIR
Occupancy Inspection - Codes Commercial Passed 11/16/2006
Correction
Resolved
11/16/2006
OCCUPANCY APPROVAL STATUS 11/15/06 CHAPTER 353 CERTIFICATE NOT REQ'D PER M DUNNING
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home