Summary
B0500107
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
BUILDING A AND ATRIUM RENOVATIONS
01/28/2005
03/29/2005
09/25/2005
11/15/2006
Locations
Contacts
GASTINGER WALKER HARDEN ARCHITECTS, Address:817 WYANDOTTE  
SHAFER KLINE & WARREN, Address:2940 MAIN ST  
THE WEITZ COMPANY, Address:9900 W 109TH ST  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/13/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1004.1 - Design occupant load. In determining means of egress requirements, the number of occupants for whom meansof egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1008.1.2 - Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound force. The door shall be set in motion when subjected to a 30-pound force. The door shall swing to a full-open position when subjected to a 15-pound force. Forces shall be applied to the latch side.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 715.3 - Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any materials or assembly of component materials that conforms to the test requirements of Section 715.3.1, 715.3.2 or 715.3.3 and the fire protection rating indicated in Table 715.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.
Correction

Fire Department- Place the manual pull for the hood system opposite the hinged side of the door. Shown two ways on the plans.
Correction

Fire Department IFC 905.3.1 Building height. Class I standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than two stories above the lowest level of the fire department vehicle access, or where the floor level of the lowest story is located more than two stories below the highest level of fire department vehicle access.
Correction

Fire Department- Fire protection systems for the occupied portion of the building shall remain operable.
Correction

Fire Department- Door 116 from the Entry Hall shall swing in the direction of egress travel.
Correction

Fire Department- Clarify the use of the roll down fire door between the atrium and library.
Correction

Codes Administration - The life safety plan on Sheet A1 does not provide does not include information on the location and types of new and existing rated assemblies.
Correction

Codes Administration - The exiting plan on Sheet A1 shows the exit path going through a fire shutter door.
Correction

Codes Administration - The Code Analysis shows the existing building to be of Type III-B construction and the addition of Type V-B construction. The plans do not indicate a fire-wall between the two areas to create two separate buildings.
Correction

Codes Administration - The plans show the corridor walls as rated across from the restroom and on the south side of the restroom but the walls and doors between the restroom and corridor are not rated.
Correction

Codes Administration - I am unable to locate information on the hood system to be installed.
Correction

Codes Administration - I am unable to locate details regarding the construction of the shafts for the ducts to be installed from the first floor through the roof.
Correction

Codes Administration - 2003 IMC 506.1 - General. Commercial kitchen hood ventilation ducts and exhaust equipment shall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served.
Correction

Fire Department- 703.2.1 Signs. Where required by the code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR-DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR-KEEP CLOSED.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - Lee's Summit Code of Ordinance 17-6.D - Regulated smoking environments classified. No person with ownership, management, or control of a "Food Service Establishment" shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, with primary lettering of not less than one inch in height according to one of the following classifications of food service establishements: 1. Smoke -free establishement 2. Smoking restricted establishement.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,778.00 $1,778.00 Paid 03/29/2005
24 BLDG Plan Check Fees $49.60 $49.60 Paid 03/29/2005
25 Electrical Permit Fee $156.03 $156.03 Paid 03/29/2005
25 Mechanical Permit Fees $74.50 $74.50 Paid 03/29/2005
25 Plumbing Permit Fees $121.50 $121.50 Paid 03/29/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 06/29/2005
Correction
Partial Correction
06/29/2005
BUILDING SANITARY DRAIN CORRIDOR 119 FROM (A) TO S OF MECH 111; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
06/29/2005
UNDER-SLAB BRANCH WASTE & VENT PIPING SPACES 105+106 EXCEPT RISERS; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Underground Plumbing Inspection - Commercial Request Complete 6/28/2005 6/29/2005 06/29/2005
Underslab Plumbing Inspection - Commercial Partial 07/01/2005
Correction
Partial Correction
07/01/2005
BUILDING SANITARY DRAIN CORR119 FROM (A) TO S OF MECH 111; CONNECTION IN CORRIDOR 119 AT (A); OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Correction
Partial Correction
07/01/2005
UNDER-SLAB BRANCH WASTE & VENT PIPING SPACES 105+106 EXCEPT RISERS; 4"/3" BRANCH FROM CORRIDOR INTO SERVERY108; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Underslab Plumbing Inspection - Commercial Partial 07/12/2005
Correction
Partial Correction
07/12/2005
UNDER-SLAB BRANCH WASTE & VENT PIPING SPACES 105+106 EXCEPT RISERS; 4"/3" BRANCH FROM CORRIDOR INTO SERVERY108; GREASE TRAP + PIPING SUBSTANTIALLY COMPLETE IN 108; 109; 111 OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Footing Inspection - Commercial Partial 07/12/2005
Correction
Partial Correction
07/12/2005
PERIMETER GRADE BEAM + COLUMN FOOTINGS @ DINING/COMMONS ADDITION INCLUDING PILASTER WIDENS OK TO POUR WHEN READY
Underground Plumbing Inspection - Commercial Partial 07/14/2005
Correction
Corrective Action Required
07/14/2005
ROOF DRAIN STORM PIPING INCLUDING LATERALS. OK TO COVER WHEN READY OUTSIDE WEST WALL FROM STA 2+25.14 TO 1+26.75
Underground Plumbing Inspection - Commercial Partial 07/15/2005
Correction
Partial Correction
07/15/2005
ROOF DRAIN STORM PIPING OUTSIDE WEST WALL FROM STA 2+25.14 TO 1+26.75; FROM STA 1+26.75 WEST TO DROP INLET @ STA 8+60.75; INCLUDING LATERALS OK TO COVER WHEN READY
Underslab Plumbing Inspection - Commercial Partial 08/16/2005
Correction
Resolved
08/16/2005
BUILDING SANITARY DRAIN CORR119 FROM (A) TO S OF MECH 111; CONNECTION IN CORRIDOR 119 AT (A); COMPONENTS LISTED BELOW:
Correction
Partial Correction
08/16/2005
UNDER-SLAB BRANCH WASTE & VENT PIPING SPACES 105+106 EXCEPT RISERS; 4"/3" BRANCH FROM CORRIDOR INTO SERVERY108; GREASE TRAP; PIPING IN BAR 107; SERVERY 108; PREP/STORAGE 109; 111 OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
All Rough Inspection - Commercial Partial 08/19/2005
Correction
Partial Correction
08/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 103; 104; OK TO COVER WHEN READY SPACES LISTED BELOW:
Underslab Plumbing Inspection - Commercial Passed 10/12/2005
Correction
Resolved
10/12/2005
UNDER-SLAB BRANCH WASTE & VENT PIPING SPACES 105+106 EXCEPT RISERS; 4"/3" BRANCH FROM CORRIDOR INTO SERVERY108; GREASE TRAP; PIPING IN BAR 107; SERVERY 108; PREP/STORAGE 109; 111; CONDENSATE DRAIN @ 105 + FCO IN CORRIDOR OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rough Plumbing Inspection - Commercial Partial 10/27/2005
Correction
Partial Correction
10/27/2005
COPPER DOMESTIC WATER & RECIRCULATION PIPING ENTRY HALL 116; SERVERY 108; PREP/STORAGE 109; MOP SINK; RR 117/118; RECIRC MAIN NORTH TO POINT OF CONN TO EXSTG; IN-WALL & ABOVE CEILING OK TO INSULATE WHEN READY
Rough Plumbing Inspection - Commercial Partial 11/01/2005
Correction
Partial Correction
11/01/2005
COPPER DOMESTIC WATER & RECIRCULATION PIPING ENTRY HALL 116; SERVERY 108; PREP/STORAGE 109; MOP SINK; RR 117/118; RECIRC MAIN NORTH TO POINT OF CONN TO EXSTG; CONNECTIONS OF RECIRC MAIN @ EAST, SOUTH, & NORTHEAST IN-WALL & ABOVE CEILING OK TO INSULATE WHEN READY
Above Ceiling Inspection Partial 11/10/2005
Correction
Partial Correction
11/10/2005
None FIRE BARRIERS IN LIGHT BOXES APPROVED. A BUILDING
Underslab Electrical Inspection - Commercial Passed 11/10/2005
Correction
Resolved
11/10/2005
None UNDER SLAB IN ATRIUM APPROVED.
All Rough Inspection - Commercial Partial 11/14/2005
Correction
Partial Correction
11/14/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 103; 104; ROOMS WEST OF CORRIDOR, EXCLUDING WEST EXTERIOR WALL OK TO COVER WHEN READY SPACES LISTED BELOW:
Rated Assembly Inspection Partial 11/22/2005
Correction
Partial Correction
11/22/2005
RATED WALLS & CEILINGS GWB CEILING @ 106 EXCEPT N 10'; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 11/30/2005
Correction
Partial Correction
11/30/2005
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH 106 HIGH CEILING; 106 DROP SOFFIT @ S END + WEST SIDE FROM (F.2) TO (B); OK TO COVER WHEN READY SPACES/AREAS LISTED BELOW
Rated Assembly Inspection Partial 12/07/2005
Correction
Partial Correction
12/07/2005
RATED WALLS & CEILINGS GWB CEILING @ 106 EXCEPT N 10'; PARTIALLY COMPLETED: GWB CEILING @ CORR 119 (A) TO (F.3) INCLUDING DOOR BULKHEADS + VESTIBULE @ N END OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 12/09/2005
Correction
Partial Correction
12/09/2005
RATED WALLS & CEILINGS GWB CEILING @ 106 EXCEPT N 10'; GWB CEILING @ CORR 119 (A) TO (F.3) INCLUDING 2 LAYERS @ DOOR BULKHEADS + VESTIBULE @ N END OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 12/14/2005
Correction
Resolved
12/14/2005
None A BUILDING LIGHT BOXES FIRE BARRIERS APPROVED
Correction
Partial Correction
12/14/2005
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH 106 HIGH CEILING; 106 DROP SOFFIT @ S END + WEST SIDE FROM (F.2) TO (B); 106 DROP SOFFIT @ EAST SIDE FROM (F.2) TO (B); OK TO COVER WHEN READY SPACES/AREAS LISTED BELOW
Gas Piping Inspection - Commercial Passed 12/14/2005
Correction
Resolved
12/14/2005
GAS PIPING TO KITCHEN @ DRAWING NOTE (20) AT >= 10 PSI FOR >=10 MIN TEST PRESSURE LEVEL HELD STEADY
All Rough Inspection - Commercial Partial 01/06/2006
Correction
Partial Correction
01/06/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH 103; 104; ROOMS WEST OF CORRIDOR, EXCLUDING WEST EXTERIOR WALL; OK TO COVER WHEN READY SPACES LISTED BELOW:
Above Ceiling Inspection Partial 01/06/2006
Correction
Partial Correction
01/06/2006
LAY-IN TILE FRAMING + ABOVE-CEILING SYSTEMS 103; 104; OK TO COVER WHEN READY SPACES LISTED BELOW:
Hood/Duct Inspection Partial 01/06/2006
Correction
Partial Correction
01/06/2006
EXHAUST HOOD DUCT FABRICATION MATERIAL ON-SITE FABRICATION APPROVED
Rated Assembly Inspection Failed 01/12/2006
Correction
Partial Correction
01/12/2006
RATED WALLS & CEILINGS GWB CEILING @ 106 EXCEPT N 10'; GWB CEILING @ CORR 119 (A) TO (F.3) INCLUDING 2 LAYERS @ DOOR BULKHEADS + VESTIBULE @ N END; NOT APPROVED: CEILING RECESS ABOVE KITCHEN HOOD OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 01/13/2006
Correction
Partial Correction
01/13/2006
RATED WALLS & CEILINGS GWB CEILING @ 106 EXCEPT N 10'; GWB CEILING @ CORR 119 (A) TO (F.3) INCLUDING 2 LAYERS @ DOOR BULKHEADS + VESTIBULE @ N END; CEILING RECESS ABOVE KITCHEN HOOD; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Above Ceiling Inspection Partial 01/19/2006
Correction
Partial Correction
01/19/2006
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH 106 HIGH CEILING; 106 DROP SOFFIT @ S END + WEST SIDE FROM (F.2) TO (B); 106 DROP SOFFIT @ E SIDE FROM (F.2) TO (B); DROP SOFFIT + CHASE FRAMING @ 106 NW; OK TO COVER WHEN READY SPACES/AREAS LISTED BELOW
Above Ceiling Inspection Partial 01/30/2006
Correction
Partial Correction
01/30/2006
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH 106 HIGH CEILING; 106 DROP SOFFIT @ S END + WEST SIDE FROM (F.2) TO (B); 106 DROP SOFFIT @ E SIDE FROM (F.2) TO (B); DROP SOFFIT + CHASE FRAMING @ 106 NW; WATER + SPRINKLER PIPING @ DOOR (102/1) OPNG; OK TO COVER WHEN READY SPACES/AREAS LISTED BELOW
Above Ceiling Inspection Partial 02/02/2006
Correction
Partial Correction
02/02/2006
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH 106 COMPLETE EXCEPT FIRE DOOR (102/1) FUSIBLE LINK MAY NOT BE CONCEALED BY CEILING SYSTEM OK TO COVER WHEN READY SPACES/AREAS LISTED BELOW
Above Ceiling Inspection Partial 02/08/2006
Correction
Partial Correction
02/08/2006
LAY-IN TILE FRAMING + ABOVE-CEILING SYSTEMS 103; 104; 102A; 108; 109; CORR 119 FINISHED SOUTH END; OK TO COVER WHEN READY SPACES LISTED BELOW:
Hood/Duct Inspection Partial 02/08/2006
Correction
Resolved
02/08/2006
EXHAUST HOOD DUCT FABRICATION
Correction
Partial Correction
02/08/2006
GREASE DUCT INSTALLATION FROM HOOD TO ROOF
Above Ceiling Inspection Partial 02/13/2006
Correction
Partial Correction
02/13/2006
LAY-IN TILE FRAMING + ABOVE-CEILING SYSTEMS 103; 104; 102A; 108; 109; 117 + 118 AFTER FIRE-CAULKING COMPLETED; CORR 119 FINISHED SOUTH END; OK TO COVER WHEN READY SPACES LISTED BELOW:
Rough Mechanical Inspection - Commercial Partial 03/08/2006
Correction
Partial Correction
03/08/2006
MECHANICAL ROOM WATER HEATER PIPING APPROVED TO COVER.
Rated Assembly Inspection Partial 03/21/2006
Correction
Resolved
03/21/2006
RATED WALLS & CEILINGS
Correction
Partial Correction
03/21/2006
KITCHEN PASS-THROUGH WINDOW LINER BOARD @ TOP + SIDES; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rated Assembly Inspection Partial 03/22/2006
Correction
Partial Correction
03/22/2006
KITCHEN PASS-THROUGH WINDOW LINER BOARD @ TOP + SIDES; TWO LAYERS 5/8" TYPE X GWB @ TOP + SIDES; OK TO COVER WHEN READY COMPONENTS LISTED BELOW:
Rough Electrical Inspection - Commercial Passed 03/24/2006
Correction
Resolved
03/24/2006
MC CABLE + BOXES @ KITCHEN PASS-THROUGH WINDOW SEAL ALL PENETRATIONS OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 04/12/2006
Correction
Corrective Action Required
04/12/2006
Receive Fire Department approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
RECEIVE JACKSON COUNTY HEALTH DEPT. APPROVAL KITCHEN MUST BE APPROVED BY JACKSON COUNTY HEALTH DEPARTMENT PRIOR TO USE UNDER SEPARATE COVER
Correction
Corrective Action Required
04/12/2006
ABOVE CEILING PATCH FIRE PROTECTIVE LID ABOVE LAY-IN CEILING. DO NOT COVER Kitchen
Correction
Corrective Action Required
04/12/2006
Panel Circuit Identification (IRC) 1- ALL CIRCUITS TO BE LABELED (IN INK) 2- COVER BLANK CIRCUITS VESTIBULE 116
Correction
Corrective Action Required
04/12/2006
REQUIRED SIGNAGE PROVIDE ALL REQUIRED ACCESSIBILITY SIGNAGES THROUGHOUT
Correction
Corrective Action Required
04/12/2006
RESTROOMS 1- INSTALL ALL RESTROOM ACCOUTREMENTS (MIRRORS, TOWEL DISPENSERS, ETC.) 2- TIGHTEN LOOSE RECEPTACLES. RESTROOMS
Correction
Corrective Action Required
04/12/2006
ACCESS TO UNFINISHED AREAS DOORS TO UNFINISHED AREAS (NOT CLEARED FOR OCCUPANCY) SHALL BE PROVIDE WITH LOCKS)
Correction
Corrective Action Required
04/12/2006
ELECTRICAL INCOMPLETE COMPLETE LIGHTING. GIFT SHOP & LIBRARIES
Correction
Corrective Action Required
04/12/2006
EXPOSED CONDUCTORS PROVIDE CAP/COVER IN TOP OF RECEPTACLE NEAR BOTTOM OF RAMP ATRIUM
Correction
Corrective Action Required
04/12/2006
PROVIDE ADDRESS IDENTIFIABLE FROM STREET EXTERIOR
Correction
Corrective Action Required
04/12/2006
TEXT THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS APPROVED TO INSTALL/STORE FURNITURE
Correction
Corrective Action Required
04/12/2006
None DO NOT OCCUPY
Occupancy Inspection - Codes Commercial Failed 04/14/2006
Correction
Resolved
04/14/2006
ABOVE CEILING
Correction
Resolved
04/14/2006
Panel Circuit Identification (IRC)
Correction
Resolved
04/14/2006
REQUIRED SIGNAGE
Correction
Resolved
04/14/2006
RESTROOMS
Correction
Resolved
04/14/2006
ACCESS TO UNFINISHED AREAS
Correction
Resolved
04/14/2006
ELECTRICAL INCOMPLETE
Correction
Resolved
04/14/2006
EXPOSED CONDUCTORS
Correction
Resolved
04/14/2006
PROVIDE ADDRESS IDENTIFIABLE FROM STREET
Correction
Partial Correction
04/14/2006
TEXT THIS PERMIT IS UNDER THE SAME OR SIMILAR 353 AGREEMENT AS BUILDING 'E' (512) AND FOLLOWS SAME REQUIREMENTS APPROVED TO INSTALL/STORE FURNITURE
Correction
Resolved
04/14/2006
None 30 DAY TCO
Occupancy Inspection - Codes Commercial Failed 05/12/2006
Correction
Resolved
05/12/2006
Receive Fire Department approval APPROVED ON SITE BY CPTN. JOE DIRR
Correction
Resolved
05/12/2006
RECEIVE JACKSON COUNTY HEALTH DEPT. APPROVAL
Footing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
PERIMETER GRADE BEAM + COLUMN FOOTINGS @ DINING/COMMONS ADDITION
Underground Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
ROOF DRAIN STORM PIPING
Rough Plumbing Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
COPPER DOMESTIC WATER & RECIRCULATION PIPING
Rough Mechanical Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
MECHANICAL ROOM WATER HEATER PIPING
Hood/Duct Inspection Partial 05/16/2006
Occupancy Inspection - Codes Commercial Failed 05/16/2006
Correction
Resolved
05/16/2006
TEXT
Correction
Resolved
05/16/2006
None
All Rough Inspection - Commercial Passed 05/16/2006
Correction
Resolved
05/16/2006
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Above Ceiling Inspection Passed 05/16/2006
Correction
Resolved
05/16/2006
None
Correction
Resolved
05/16/2006
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ROUGH
Correction
Resolved
05/16/2006
LAY-IN TILE FRAMING + ABOVE-CEILING SYSTEMS
Rated Assembly Inspection Passed 05/16/2006
Correction
Resolved
05/16/2006
KITCHEN PASS-THROUGH WINDOW
Hood/Duct Inspection Passed 05/17/2006
Correction
Resolved
05/17/2006
EXHAUST HOOD DUCT FABRICATION
Correction
Resolved
05/17/2006
GREASE DUCT INSTALLATION
Correction
Resolved
05/17/2006
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS SEE OCCUPANCY INSPECTION
Occupancy Inspection - Codes Commercial Failed 05/17/2006
Correction
Resolved
05/17/2006
Receive Planning & Development Approval NO REMAINING ISSUES
Correction
Resolved
05/17/2006
Receive Public Works Approval NO REMAINING ISSUES
Correction
Resolved
05/17/2006
Receive Water Utilities Approval NO REMAINING ISSUES
Correction
Corrective Action Required
05/17/2006
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16 REPORT VELOCITY TEST + DEMONSTRATE SMOKE CAPTURE
Correction
Partial Correction
05/17/2006
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Failed 05/30/2006
Correction
Partial Correction
05/30/2006
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS IMC 507.16 SMOKE CAPTURE TEST WITNESSED 5/30/06 REPORT VELOCITY TEST CERTIFIED RESULTS
Correction
Partial Correction
05/30/2006
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Passed 07/03/2006
Correction
Resolved
07/03/2006
Receive Fire Department approval APPROVED ON SITE BY CPT JOE DIR
Correction
Resolved
07/03/2006
COMMERCIAL KITCHEN HOOD PERFORMANCE TESTS SMOKE CAPTURE TEST WITNESSED 5/30/06 VELOCITY TEST REPORT RECEIVED; ACCEPTED 7/3/06
Correction
Resolved
07/03/2006
OCCUPANCY APPROVAL STATUS CHAPTER 353 CERTIFICATE OF COMPLIANCE NO ISSUES REMAINING OK FOR PROCESSING OF
Occupancy Inspection - Codes Commercial Passed 11/13/2006
Correction
Resolved
11/13/2006
OCCUPANCY APPROVAL STATUS PER M DUNNING 11/13/06 CHAPTER 353 CERTIFICATE NOT APPLICABLE
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home