Permit Application Status

B0500049


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0500049
Building Permit - Commercial
Certificate of Occupancy
CECEMEGMITSCHSQ LLC
NEW TENANT FINISH
TENANT FINISH
01/18/2005
02/18/2005
08/17/2005
05/06/2005
Locations
Contacts
CONSTRUCTION MASTERS INC, Address:14243 W 121ST STREET  
CECEMEGMITSCHSQ LLC, Address:708 NW COMMERCE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/17/2005 10/29/2010
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - 2003 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Tale 403.1 shall be considered individually by the code official. The number of occupants shall be deetermined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

Codes Administration - 2003 IPC 608.16.9 - Dental pump equipment. Where dental pumping equipment connects to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, 608.13.2, 608.13.5, 608.13.6 or 608.13.8.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - The construction type on the shell building was Type V-B to allow for the use of wood in the structure.
Correction

Codes Adminsitration - The North indicator on the vacinity map is incorrect. Douglas Street runs north/south and Chipman Road runs east/west.
Correction

Codes Administration - The occupant load of the space should be 20 when rounding up from 19.72.
Correction

Codes Administration - Electrical panel schedules are not provided.
Correction

Codes Administration - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

Codes Administration - I am unable to locate information on the water heater.
Correction

Codes Administration - I am unable to locate information regarding the installation of the X-ray equipment.
Correction

Codes Administration - 2002 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13 (A) and (B).
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $302.00 $302.00 Paid 02/18/2005
24 BLDG Plan Check Fees $20.00 $20.00 Paid 02/18/2005
25 Electrical Permit Fee $69.02 $69.02 Paid 02/18/2005
25 Mechanical Permit Fees $28.50 $28.50 Paid 02/18/2005
25 Plumbing Permit Fees $39.00 $39.00 Paid 02/18/2005
89 Sewer Tap Fees $240.00 $240.00 Paid 02/18/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 02/23/2005
Correction
Resolved
02/23/2005
UNDER-SLAB DWV, AIR, VACUUM PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 03/03/2005
Correction
Partial Correction
03/03/2005
None WALLS ONLY APPROVED OK TO ROCK WALLS WALLS ONLY
Above Ceiling Inspection Not Ready 03/21/2005
Correction
Corrective Action Required
03/21/2005
SUPPORT/SECURING OF LOW VOLTAGE CABLE NOT SECURED TO STRUCTURE LYING LOOSE ON MEP SYSTEM
Correction
Corrective Action Required
03/21/2005
DIAGONAL BRACES ON BUILDING FRAME ATTACHMENT NOT APPROVED SEE SHELL PERMIT FINAL
All Rough Inspection - Commercial Passed 03/21/2005
Correction
Resolved
03/21/2005
None WALL FRAMING & IN-WALL SYSTEMS
Above Ceiling Inspection Partial 03/22/2005
Correction
Partial Correction
03/22/2005
IF COVER, AT RISK DUE TO SHELL PERMIT ISSUE
Correction
Resolved
03/22/2005
SUPPORT/SECURING OF LOW VOLTAGE CABLE LYING LOOSE ON MEP SYSTEMS CORRECTION IN PROGRESS NOT SECURED TO STRUCTURE
Occupancy Inspection - Codes Commercial Failed 04/04/2005
Correction
Corrective Action Required
04/04/2005
OUTDOOR LIGHTED SIGN PER NEC 600.3 IF INSTALLED MUST BE LISTED
Correction
Partial Correction
04/04/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Corrective Action Required
04/04/2005
LABELING OF ELECT CIRCUIT BREAKER POSITIONS IN SERVICE PANEL SOME LABELS NOT ALINGED WITH BREAKERS
Correction
Corrective Action Required
04/04/2005
SEALING OF RESTROOM WATER CLOSET TO FLOOR NOT COMPLETED
Correction
Resolved
04/04/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Corrective Action Required
04/04/2005
Receive Fire Department approval CONTACT JIM EDEN FOR REINSPECTION
Above Ceiling Inspection Passed 04/04/2005
Correction
Resolved
04/04/2005
IF COVER, AT RISK SEE OCCUPANCY INSPECTION RE SHELL PERMIT ISSUE
Correction
Resolved
04/04/2005
SUPPORT/SECURING OF LOW VOLTAGE CABLE
Correction
Resolved
04/04/2005
DIAGONAL BRACES ON BUILDING FRAME ATTACHMENT NOT APPROVED SEE SHELL PERMIT FINAL
Occupancy Inspection - Codes Commercial Failed 04/04/2005
Correction
Corrective Action Required
04/04/2005
Receive Water Utilities Approval
Correction
Corrective Action Required
04/04/2005
Receive Fire Department approval
Correction
Corrective Action Required
04/04/2005
STATUS OF BUILDING SHELL PERMIT TEMP APPROVAL EXPIRED
Occupancy Inspection - Codes Commercial Failed 04/07/2005
Correction
Resolved
04/07/2005
LABELING OF ELECT CIRCUIT BREAKER POSITIONS IN SERVICE PANEL
Correction
Resolved
04/07/2005
SEALING OF RESTROOM WATER CLOSET TO FLOOR
Occupancy Inspection - Codes Commercial Failed 04/08/2005
Correction
Resolved
04/08/2005
Receive Fire Department approval PER NEIL ULLERY 4/8/05
Occupancy Inspection - Codes Commercial Failed 05/04/2005
Correction
Resolved
05/04/2005
OUTDOOR LIGHTED SIGN
Correction
Corrective Action Required
05/04/2005
OCCUPANCY APPROVAL STATUS COFO CANNOT BE ISSUED UNTIL BUILDING SHELL APPD
Occupancy Inspection - Codes Commercial Passed 05/05/2005
Correction
Resolved
05/05/2005
STATUS OF BUILDING SHELL PERMIT
Correction
Resolved
05/05/2005
OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home