Summary
B0402270
Building Permit - Commercial
Final Completion
GALE COMMUNITIES INC
NEW SHELL BUILDING
BLDG 12 SHELL RESTAURANT
12/07/2004
04/14/2005
10/11/2005
05/04/2007
Locations
Contacts
GOULD EVANS GOODMAN, Address:4041 MILL STREET  
MILLER STAUCH CONSTRUCTION, Address:1300 W 87TH ST PARKWAY  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/10/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1010.2 - Slope. Ramps used as part of a means of egress shall have a running slope not steeper than one unit vertical in 12 units horizontal (8-percent slope). The slope of other ramps shall not be steeper than one unit vertical in eight units horizontal (12.5-percent slope).
Correction

Codes Administration - 2003 IBC 1010.6.3 - Length. The length shall be 60 inches (1525 mm) minimum.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Codes Administration - I beleive the Code Data for building 12 is incorrect. Its my understanding that this building is to be a restaurant which would be an A-2 occupancy but the Code Data states that it is an M occupancy.
Correction

Codes Administration - The door and window schedules appear to be incomplete.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - Lee's Summit Code of Ordinance 17-6.D - Regulated smoking environments classified. No person with ownership, management, or control of a "Food Service Establishment" shall operate such establishment unless there is posted signage at a height and location conspicuous to persons entering the establishment, with primary lettering of not less than one inch in height according to one of the following classifications of food service establishements: 1. Smoke -free establishement 2. Smoking restricted establishement.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

A grease/solids interceptor must be shown with an indication of size, type and detail of the interceptor.
Correction

Codes Administration - 2003 IPC 1003.3.1 - Grease traps and grease interceptors required. A grease trap or grease interceptor shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias, or restaurants and clubs.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,697.00 $1,697.00 Paid 04/14/2005
24 BLDG Plan Check Fees $48.25 $48.25 Paid 04/14/2005
25 Electrical Permit Fee $45.00 $45.00 Paid 04/14/2005
25 Plumbing Permit Fees $32.00 $32.00 Paid 04/14/2005
84 Water Meters $625.00 $625.00 Paid 04/14/2005
85 Water Taps $13,670.00 $13,670.00 Paid 04/14/2005
Road and Bridge Escrow $5,521.69 $5,521.69 Paid 04/14/2005
Right of Way Permit $35.00 $35.00 Paid 04/14/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection Passed 04/21/2005
Sewer Service Inspection - Commercial Request Complete 4/21/2005 4/21/2005 04/21/2005
Water Service Inspection Passed 05/06/2005
Correction
Resolved
05/06/2005
None WATER APPROVED
Erosion Control Inspection Residential Passed 05/06/2005
Underslab Electrical Inspection - Commercial Passed 05/06/2005
Correction
Resolved
05/06/2005
None UNDERSLAB CONDUIT FOR WATER LINE GROUND.
Water Service Inspection - Commercial Request Complete 5/6/2005 5/6/2005 05/06/2005
Rough Plumbing Inspection - Commercial Partial 06/08/2005
Correction
Partial Correction
06/08/2005
None ROOF DRAINS BUILDING 12 APPROVED. 6- 4 INCH AND 2 - 2 INCH ROOF DRAINS.
Electrical Service Inspection Failed 07/28/2005
Correction
Corrective Action Required
07/28/2005
CONNECT SERVICE GROUND TERMINAL TO SERVICE ENCLOSURE
Correction
Corrective Action Required
07/28/2005
SHALL BOND SERVICE GROUNDED CONDUCTOR TO ENCLOSURE WITH GREEN GROUND SCREW
Correction
Corrective Action Required
07/28/2005
SHALL BOND TOGETHER ALL AVAILABLE GROUNDING ELECTRODES WITH BONDING JUMPER SIZED PER NEC 250-66 (SAME AS GROUND TO WATER OR BUILDING STEEL). EXCEPT THAT GROUNDING ELECTRODE CONDUCTOR FROM SUPPLEMENTARY GROUNDING ROD CAN BOND TO ENCLOSURE METAL
Correction
Corrective Action Required
07/28/2005
MAIN BONDING JUMPER-NEC 250-28 MAIN BONDING JUMPER SHALL BOND SERVICE GROUNDED CONDUCTOR, SERVICE DISCONNECT ENCLOSURE, AND EQUIPMENT GROUNDING CONDUCTORS AT SERVICE DISCONNECT VIA JUMPER SIZED PER 250-66
Correction
Corrective Action Required
07/28/2005
SHALL BOND ELECTRODE GROUNDING CONDUCTOR FROM BUILDING STEEL TO METALLIC CONDUIT WITH LISTED GROUNDING BUSHING/FITTING. LOOK ABOVE WALL INSIDE BUILDING-NEC 250-64
Electrical Service Inspection Failed 08/02/2005
Correction
Corrective Action Required
08/02/2005
Premises Identification (IRC) INDENTIFY BUILDING BY ADDRESS OR BUILDING PERMIT FROM ROAD FRONT
Above Ceiling Inspection Partial 08/03/2005
Correction
Partial Correction
08/03/2005
SOFFIT @ EAST ENTRANCE CANOPY OK TO COVER WHEN READY
Electrical Service Inspection Passed 08/03/2005
Correction
Resolved
08/03/2005
CONNECT SERVICE GROUND TERMINAL TO SERVICE ENCLOSURE
Correction
Resolved
08/03/2005
SHALL BOND SERVICE GROUNDED CONDUCTOR TO ENCLOSURE
Correction
Resolved
08/03/2005
SHALL BOND TOGETHER ALL AVAILABLE GROUNDING ELECTRODES
Correction
Resolved
08/03/2005
MAIN BONDING JUMPER-NEC 250-28
Correction
Resolved
08/03/2005
SHALL BOND ELECTRODE GROUNDING CONDUCTOR FROM BUILDING STEEL
Correction
Resolved
08/03/2005
Premises Identification (IRC)
Rough Plumbing Inspection - Commercial Passed 12/01/2005
Correction
Resolved
12/01/2005
None ROOF DRAINS BUILDING 12 APPROVED. 6- 4 INCH AND 2 - 2 INCH ROOF DRAINS.
Final Inspection - Commercial Failed 12/01/2005
Correction
Corrective Action Required
12/01/2005
None DO NOT OCCUPY
Correction
Corrective Action Required
12/01/2005
ELECTRICAL 1- DISCONNECT SWITCHES REQUIRED TO SERVE OVERHEAD ELECTRIC UNIT HEATERS 2- LABEL EXTERIOR HOUSE PANEL
Correction
Corrective Action Required
12/01/2005
Receive Water Utilities Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/01/2005
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/01/2005
Receive Planning & Development Approval UNDER SEPARATE COVER
Correction
Corrective Action Required
12/01/2005
Receive Fire Department approval UNDER SEPARATE COVER
Above Ceiling Inspection Passed 12/01/2005
Correction
Resolved
12/01/2005
SOFFIT @ EAST ENTRANCE CANOPY OK TO COVER WHEN READY
Final Inspection - Commercial Failed 12/08/2005
Correction
Resolved
12/08/2005
Receive Water Utilities Approval UNDER SEPARATE COVER
Final Inspection - Commercial Failed 12/21/2005
Correction
Corrective Action Required
12/21/2005
None DO NOT OCCUPY
Correction
Resolved
12/21/2005
ELECTRICAL
Correction
Resolved
12/21/2005
Receive Public Works Approval UNDER SEPARATE COVER
Correction
Resolved
12/21/2005
Receive Fire Department approval UNDER SEPARATE COVER
Final Inspection - Commercial Failed 10/11/2006
Correction
Partial Correction
10/11/2006
None
Final Inspection - Commercial Failed 10/12/2006
Correction
Partial Correction
10/12/2006
None
Final Inspection - Commercial Passed 05/03/2007
Correction
Resolved
05/03/2007
None
Correction
Resolved
05/03/2007
Receive Planning & Development Approval UNDER SEPARATE COVER
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home