Summary
B0402249
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
T/F 1ST FLOOR WEST END
12/03/2004
01/10/2005
07/09/2005
04/28/2005
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
J E DUNN CONSTRUCTION, Address:929 HOLMES  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/01/2005 10/29/2010
Correction

Fire Department: Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators, and relief devices and valves, shall comply with NFPA 99 and the general provisions of this chapter. Documentation shall be provided of the pressure test of at least 150 psi for a minimum of 24 hours on installers letterhead.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Codes Administration - The address on the plans is incorrect.
Correction

Codes Administration - The comments for the third pary electrical review have not been provided.
Correction

Codes Administration - The project cost has not been provided.
Correction

Fire Department- Indicate the specific use of the "Hot Lab". If used for the preparation of of nuclear med. products, provide a list of materials with MSDS's and method of containment. The room shall be placarded.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,781.00 $1,781.00 Paid 01/10/2005
24 BLDG Plan Check Fees $49.65 $49.65 Paid 01/10/2005
25 Electrical Permit Fee $189.74 $189.74 Paid 01/10/2005
25 Mechanical Permit Fees $136.50 $136.50 Paid 01/10/2005
25 Plumbing Permit Fees $31.00 $31.00 Paid 01/10/2005
89 Sewer Tap Fees $90.00 $90.00 Paid 01/10/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/14/2004
All Rough Inspection - Commercial Partial 01/05/2005
Correction
Partial Correction
01/05/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; [NOT APPROVED: W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28] OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 01/06/2005
Correction
Partial Correction
01/06/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28 OK TO COVER WHEN READY SPACES LISTED BELOW:
Rough Plumbing Inspection - Commercial Passed 01/10/2005
Correction
Resolved
01/10/2005
DWV PLUMBING PIPING TOP ROUGH VISUAL & PRESSURE TEST
Rated Assembly Inspection Passed 01/10/2005
Correction
Resolved
01/10/2005
NORTH WALL ROOMS 28, 29, 34 ONE LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY
Correction
Resolved
01/10/2005
WALL ALONG D:(1) COMPRISING E WALLS OF RMS 1D088, 027, 028 1ST LAYER 5/8" TYPE X: TOP 5'; 1ST LAYER REMAINDER OF WALL HEIGHT; OK TO COVER WHEN READY
Rated Assembly Inspection Passed 01/10/2005
Correction
Resolved
01/10/2005
WALL ALONG D:(1) COMPRISING E WALLS OF RMS 1D088, 027, 028 1ST LAYER 5/8" TYPE X OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 01/18/2005
Correction
Partial Correction
01/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28; COMPLETE RMS ID10-21; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 01/19/2005
Correction
Partial Correction
01/19/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28; COMPLETE RMS ID09-21; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 01/21/2005
Correction
Partial Correction
01/21/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28; COMPLETE RMS ID09-21; ID22-25; ID32-33; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Rated Assembly Inspection Partial 01/21/2005
Correction
Partial Correction
01/21/2005
ROOM ID23 EAST WALL 1ST LAYER 5/8" TYPE X GWB; 2-HR WALL PER CODE PLAN OK TO COVER WHEN READY
Correction
Resolved
01/21/2005
NORTH WALL ROOMS 28, 29, 34 ONE LAYER 5/8" TYPE X GWB
Correction
Resolved
01/21/2005
WALL ALONG D:(1) COMPRISING E WALLS OF RMS 1D088, 027, 028 1ST LAYER 5/8" TYPE X: TOP 5'; 1ST LAYER REMAINDER OF WALL HEIGHT
Rated Assembly Inspection Partial 01/24/2005
Correction
Resolved
01/24/2005
ROOM ID23 EAST WALL 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 2-HR WALL PER CODE PLAN OK TO COVER WHEN READY
Correction
Partial Correction
01/24/2005
WALL ALONG D:(1) COMPRISING E WALLS OF RMS 1D088, 027, 028 1ST LAYER 5/8" TYPE X: TOP 5'; 1ST LAYER REMAINDER OF WALL HEIGHT; 2ND LAYER OK TO COVER WHEN READY SPACES 23; 26; 27; 28
All Rough Inspection - Commercial Partial 01/26/2005
Correction
Partial Correction
01/26/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH W WALL ID20, 18, 17, 16; S WALL ID16, 15, 14; E WALL ID14, 17, 13, 12; S WALL ID22-25, 32, 33; E WALL ID22, 27, 28; W WALL ID31, 33, 34, 36; N WALL ID34, 29, 28; COMPLETE RMS ID09-25; ID32-33; ID04-08, 26, 31, 34, 35 NOT READY: ID36 OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
All Rough Inspection - Commercial Partial 01/28/2005
Correction
Partial Correction
01/28/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH ID04-26; 29; 30; 31; 32; 33; 34, 35; 36; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Footing Inspection - Commercial Passed 02/02/2005
All Rough Inspection - Commercial Partial 02/02/2005
Correction
Partial Correction
02/02/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH ID01 EAST WALL ONLY; 04-26; 29; 30; 31; 32; 33; 34, 35; 36; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 02/16/2005
Correction
Partial Correction
02/16/2005
ABOVE-CEILING SYSTEMS ID09-21; OK TO COVER WHEN READY SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 02/16/2005
Correction
Partial Correction
02/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH ID01 EAST WALL ONLY; 04-26; 29; 30; 31; 32; 33; 34, 35; 36; 36A; 36B; OK TO COVER WHEN READY SPACES/WALLS LISTED BELOW
Above Ceiling Inspection Partial 02/17/2005
Correction
Partial Correction
02/17/2005
ABOVE-CEILING SYSTEMS ID09-21; ID01-07; OK TO COVER WHEN READY SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/18/2005
Correction
Partial Correction
02/18/2005
ABOVE-CEILING SYSTEMS ID09-21; ID01-07; ID08; ID22-25; OK TO COVER WHEN READY SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/23/2005
Correction
Partial Correction
02/23/2005
ABOVE-CEILING SYSTEMS ID09-21; ID01-07; ID08; ID22-25; 26 EXCEPT N 2'; 27; 28; 30-34; OK TO COVER WHEN READY SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/24/2005
Correction
Partial Correction
02/24/2005
ABOVE-CEILING SYSTEMS ID01-25; 26 EXCEPT N 2'; 27; 28; 30-34; 36; 36A; OK TO COVER WHEN READY SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/28/2005
Correction
Partial Correction
02/28/2005
ABOVE-CEILING SYSTEMS 36A (HOT LAB)- 6 INCH DUCT PENETRATES 1 HOUR WALL. PROVIDE DAMPER AND ACCESS. OKAY TO DROP TILE IN OTHER ROOMS. OK TO COVER WHEN READY SPACES LISTED BELOW
Occupancy Inspection - Codes Commercial Failed 03/15/2005
Correction
Corrective Action Required
03/15/2005
BUILDING SHELL FINAL APPROVAL PENDING
Correction
Resolved
03/15/2005
Receive Fire Department approval
All Rough Inspection - Commercial Passed 03/15/2005
Correction
Resolved
03/15/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Above Ceiling Inspection Passed 03/15/2005
Correction
Resolved
03/15/2005
ABOVE-CEILING SYSTEMS
Rated Assembly Inspection Passed 03/15/2005
Correction
Resolved
03/15/2005
ROOM ID23 EAST WALL
Correction
Resolved
03/15/2005
NORTH WALL ROOMS 28, 29, 34
Correction
Resolved
03/15/2005
WALL ALONG D:(1) COMPRISING E WALLS OF RMS 1D088, 027, 028
Occupancy Inspection - Codes Commercial Failed 03/18/2005
Correction
Resolved
03/18/2005
Receive Fire Department approval PER N ULLERY 3/14/05
Correction
Corrective Action Required
03/18/2005
BUILDING SHELL FINAL APPROVAL NOT FULLY APPROVED
Correction
Partial Correction
03/18/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Passed 04/21/2005
Correction
Resolved
04/21/2005
BUILDING SHELL FINAL APPROVAL
Correction
Resolved
04/21/2005
OCCUPANCY APPROVAL STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home