Summary
B0402239
Building Permit - Commercial
Certificate of Occupancy
LE GRAND APARTMENTS LLC
NEW TENANT FINISH
TENANT FINISH
12/01/2004
12/08/2004
06/06/2005
01/10/2005
Locations
Contacts
VHL INVESTMENT PROPERTIES, Address:609 W LUCY WEBB RD  
LE GRAND APARTMENTS LLC, Address:25706 E SHADYBROOK LN  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/30/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - The plans do not clearly indicate what is new and what is existing.
Correction

Codes Administration - Plans and specifications for the mechanical, electrical and plumbing work have not been provided.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $122.00 $122.00 Paid 12/08/2004
24 BLDG Plan Check Fees $12.00 $12.00 Paid 12/08/2004
25 Electrical Permit Fee $60.00 $60.00 Paid 12/08/2004
25 Mechanical Permit Fees $46.00 $46.00 Paid 12/08/2004
25 Plumbing Permit Fees $29.00 $29.00 Paid 12/08/2004
89 Sewer Tap Fees $60.00 $60.00 Paid 12/08/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Passed 12/09/2004
Underslab Plumbing Inspection - Commercial Passed 12/09/2004
Rough Electrical Inspection - Commercial Passed 12/15/2004
Rough Plumbing Inspection - Commercial Passed 12/15/2004
Rough Framing Inspection - Commercial Passed 12/15/2004
Correction
Resolved
12/15/2004
None OK TO INSULATE OK TO ROCK
Gas Service Inspection - Commercial Passed 12/16/2004
Correction
Resolved
12/16/2004
None HELD 14 PSI FOR 10 MINUTES
Gas Piping Inspection - Commercial Passed 12/16/2004
Above Ceiling Inspection Failed 12/22/2004
Correction
Corrective Action Required
12/22/2004
SECURE LIGHTING EACH LIGHTING UNIT REQUIRED TO HAVE 2 SUPPORTS - ONE ON EACH END OR BALANCED SUPPORT
Correction
Corrective Action Required
12/22/2004
HVAC SUPPORT SUPPORT DUCTWORK AT LEAST 10' KEEP DUCTWORK AWAY FROM LIGHTING
Correction
Corrective Action Required
12/22/2004
ELECTRICAL SUPPORT ELECTRICAL WIRING REQUIRED TO BE SECURE STRUCTURE WITHIN 12" FROM BOXES
Above Ceiling Inspection Partial 12/27/2004
Correction
Resolved
12/27/2004
SECURE LIGHTING EACH LIGHTING UNIT REQUIRED TO HAVE 2 SUPPORTS - ONE ON EACH END OR BALANCED SUPPORT
Correction
Resolved
12/27/2004
HVAC SUPPORT SUPPORT DUCTWORK AT LEAST 10' KEEP DUCTWORK AWAY FROM LIGHTING
Correction
Partial Correction
12/27/2004
ELECTRICAL SUPPORT ELECTRICAL WIRING REQUIRED TO BE SECURE STRUCTURE WITHIN 12" FROM BOXES
Correction
Resolved
12/27/2004
None OK TO LID ALL EXCEPT SOUTH MECH. ROOM. SOME CONDUITS STILL NEED SECURED WITHIN 12" OF JUNCTION BOXES.
Above Ceiling Inspection Passed 01/03/2005
Correction
Resolved
01/03/2005
ELECTRICAL SUPPORT ELECTRICAL WIRING REQUIRED TO BE SECURE STRUCTURE WITHIN 12" FROM BOXES
Occupancy Inspection - Codes Commercial Failed 01/03/2005
Correction
Resolved
01/03/2005
ABOVE CEILING VIOLATIONS WIRES IN SOUTH MECHANICAL ROOM NOT SECURE WITHIN 12" OF J-BOX
Correction
Corrective Action Required
01/03/2005
WATER HEATER RUN WATER HEATER OVERFLOW TO FLOOR DRAIN
Correction
Corrective Action Required
01/03/2005
ADA REQUIREMENTS PROTECTION FROM PLUMBING PIPES UNDER SINK
Correction
Partial Correction
01/03/2005
None 10 DAY TCO - GRANTED RECIEVED VERBAL APPROVAL FROM FIRE
Occupancy Inspection - Codes Commercial Failed 01/05/2005
Correction
Corrective Action Required
01/05/2005
WATER HEATER RUN WATER HEATER OVERFLOW TO FLOOR DRAIN, OR TO A SAFE PLACE OUTSIDE (6"-24" ABOVE GRADE). SHALL NOT CONNECT TO DRAINAGE SYSTEM DUE TO POSSIBILITY OF CONTAMINATION
Correction
Resolved
01/05/2005
ADA REQUIREMENTS
Correction
Partial Correction
01/05/2005
None 10 DAY TCO - GRANTED RECIEVED VERBAL APPROVAL FROM FIRE
Occupancy Inspection - Codes Commercial Passed 01/07/2005
Correction
Resolved
01/07/2005
WATER HEATER
Correction
Resolved
01/07/2005
None OCCUPANCY APPROVED CLOSE PERMIT C. O. FIRE DEPT. APPROVED - JIM EDEN
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home