Summary
B0402113
Building Permit - Commercial
Certificate of Occupancy
GRANDLAND DEVELOPMENT LC
CHANGE OF TENANT
TENANT FINISH
11/03/2004
11/22/2004
05/21/2005
02/02/2005
Locations
Contacts
THOLEN WOLFE CONTRACTORS, Address:1929 INDIAN AVE  
GRANDLAND DEVELOPMENT LC, Address:PO BOX 10076  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/02/2005 10/29/2010
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

Codes Administration - Information was not provided for the mechanical, electrical and plumbing work to be performed.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- The maximum occupant load shall be posted in a conspicuos location near the front door.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $197.00 $197.00 Paid 11/22/2004
24 BLDG Plan Check Fees $16.50 $16.50 Paid 11/22/2004
25 Electrical Permit Fee $30.00 $30.00 Paid 11/22/2004
25 Mechanical Permit Fees $21.50 $21.50 Paid 11/22/2004
25 Plumbing Permit Fees $37.00 $37.00 Paid 11/22/2004
89 Sewer Tap Fees $120.00 $120.00 Paid 11/22/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 11/24/2004
Underslab Electrical Inspection - Commercial Passed 12/03/2004
Correction
Resolved
12/03/2004
BOXES & CONDUIT FOR EXERCISE EQUIPMENT OK TO COVER WHEN READY
All Rough Inspection - Commercial Failed 12/09/2004
Correction
Corrective Action Required
12/09/2004
IN-WALL & ABOVE-CEILING SYSTEMS PROTECTION OF COPPER & PVC PIPING < 1-1/2" FROM FACE OF STUDS & TRACKS - IPC 305.8 INSTALL SHIELD PLATES; PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL STUDS & TRACKS - INSTALL GROMMETS ENCLOSED SPACES @ N END
All Rough Inspection - Commercial Passed 12/10/2004
Correction
Resolved
12/10/2004
IN-WALL & ABOVE-CEILING SYSTEMS ENCLOSED SPACES @ N END
Occupancy Inspection - Codes Commercial Failed 12/22/2004
Correction
Corrective Action Required
12/22/2004
ELECTRICAL SERVICE GROUND SUBJECT TO APPROVAL GEC TO BE TRACED FROM DISCONNECT TO WATER LINE
Correction
Corrective Action Required
12/22/2004
JANITOR SINK INSTALLATION IN PROGRESS
Correction
Corrective Action Required
12/22/2004
WATER HEATER INSTALLATION IN PROGRESS SUBJECT TO APPROVAL
Occupancy Inspection - Codes Commercial Failed 12/23/2004
Correction
Resolved
12/23/2004
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
12/23/2004
Receive Fire Department approval PER N ULLERY 12/22/04
Occupancy Inspection - Codes Commercial Failed 01/31/2005
Correction
Resolved
01/31/2005
ELECTRICAL SERVICE GROUND AND WITNESSED BY JB WEEK OF 1/24/05 EFFECTIVENESS OF GROUND TESTED BY E.C.
Occupancy Inspection - Codes Commercial Passed 02/01/2005
Correction
Resolved
02/01/2005
WATER HEATER INSTALLATION SECURE BOTTOM OF GAS FEEDER PIPE TO PREVENT DAMAGE
Correction
Resolved
02/01/2005
JANITOR SINK INSTALLATION
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home