Permit Application Status

B0401992


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0401992
Building Permit - Commercial
Certificate of Occupancy
SARAH PEPPER ENTERPRISES LLC
CHANGE OF TENANT
TENANT FINISH
10/15/2004
11/16/2004
05/15/2005
04/29/2005
Locations
Contacts
HIRST AND ASSOCIATES PC, Address:621 NE WOODS CHAPEL RD  
SARAH PEPPER ENTERPRISES, Address:228 SW MAIN ST  
SARAH PEPPER ENTERPRISES LLC, Address:5925 WALNUT  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/13/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1014.2.1 - Two exits or exit access doorways. Where two exits or exit doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways. Interlocking or scissor stairs shall be counted as one exit stairway.
Correction

Codes Administration - 2003 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1.
Correction

Fire Department- IFC Table 1016.1 reguires the second floor corridor to be rated when the occupant load exceeds 30.
Correction

Fire Department- The door schedule indicates door 12 is a rated door with a hold open device. A detail is not provided on the device or release service.
Correction

Fire Department- IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Codes Administration - A code analysis was not provided with the project.
Correction

Codes Administration - Only the dimensions of the exterior of the building and the restroom area are provided on the plans.
Correction

Codes Administration - A 2-hour fire-resistive assembly is indicated at door 12 but I am unable to locate additional information about the assembly.
Correction

Codes Administration - The lower level of the building is currently an M occupancy and the upper level appears to be a B occupancy. If the construction type is V-B the structure is limited to 1 story in height per Table 503.
Correction

Codes Administration - The finish schedule indicates a wall finish of 3 which is not listed below the table.
Correction

Codes Administration - 2003 IBC 1103.1 - Where required. Buildings and structures, temporary or permanent, includeing their associated sites and facilities, shall be accessible to persons with physical disablilities.
Correction

Codes Administration - 2003 IBC 1109.12.1 - Dressing, fitting and locker rooms. Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.
Correction

Codes Administration - A two-hour fire-resistive wall is indicated on the plans but the plans do not indicate what type of wall it is or where the wall extends to.
Correction

Codes Administration - Details where not provided on the ramp located by office 226.
Correction

Codes Administration - 2003 IBC 1019.1 - Enclosures required. Interior exit stairways and interior exit ramps shall be enclosed with fire barriers. Exit enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the shaft enclosure shall include any basements but not any mezzanines. An exit enclosure shall not be used for any purpose other than means of egress. Enclosures shall be constructed as fire barriers in accordance with Section 706.
Correction

Codes Administration - An elelctrical service detail has not been provided.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 304.9 - Clearance from grade. Equipment and appliances in stalled at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade or shall be suspended a minimum of 6 inches above adjoining grade.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IMC 602.2.1 - Materials exposed within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials exposed within plenums shall be noncombustible or shall have a flame spread index of not more than 25 and an smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $197.00 $197.00 Paid 11/16/2004
24 BLDG Plan Check Fees $16.50 $16.50 Paid 11/16/2004
25 Electrical Permit Fee $197.54 $197.54 Paid 11/16/2004
25 Mechanical Permit Fees $55.00 $55.00 Paid 11/16/2004
25 Plumbing Permit Fees $41.00 $41.00 Paid 11/16/2004
89 Sewer Tap Fees $210.00 $210.00 Paid 11/16/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 01/13/2005
Correction
Corrective Action Required
01/13/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 216-229; NOTE APPROVED DRAWING INDICATION THAT TYPES E, F, G, & H ARE TO FINISH PER UL U305 OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 02/02/2005
Correction
Partial Correction
02/02/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 201-211; 216-229; OK TO COVER WHEN READY SPACES LISTED BELOW:
All Rough Inspection - Commercial Partial 02/25/2005
Correction
Partial Correction
02/25/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 201-211; 216-229; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Partial Correction
02/25/2005
None SCREW INSPECTION 1 ST. FLOOR SEPERATION WALL BETWEEN 228 AND 230 APPROVED. 2 ND. FLOOR WALL AT DOOR # 12 SCREW INSP. APPROVED. [2 LAYERS 5/8 FIRE ROCK]
Above Ceiling Inspection Not Ready 03/10/2005
Correction
Corrective Action Required
03/10/2005
READINESS FOR INSPECTION IBC 109.1, 109.5: NOT READY PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
Above Ceiling Inspection Partial 03/11/2005
Correction
Partial Correction
03/11/2005
READINESS FOR INSPECTION OKAY TO HANG TILE ABOVE STAIRWAY AND ALL ROOMS SOUTH OF STAIRWAY INSPECTED. NORTH SIDE OF STAIRWAY NOT INSPECTED. FRESHLY FINISHED FLOOR
Gas Piping Inspection - Commercial Partial 03/25/2005
Correction
Partial Correction
03/25/2005
None SEE GAS SERVICE TEST INSPECTION FOR INFORMATION.
Gas Service Inspection - Commercial Partial 03/25/2005
Correction
Partial Correction
03/25/2005
None GAS TEST APPROVED FROM FURNACE INSTALLATION TO WITHIN APPROX. TWO FEET FROM THE GROUND ON OUTSIDE WALL. TEST PRESSURE 17 PSI. GAS PIPE REQUIRED TO BE INSTALLED AND TESTED TO METER LOCATION.
Above Ceiling Inspection Failed 03/25/2005
Correction
Corrective Action Required
03/25/2005
FIRESTOP FIRESTOP PENETRATIONS IN RATED WALL ABOVE THE DOOR [ATTIC]. AB0VE DOOR FROM STAIRS TO NORTH AREA
Correction
Corrective Action Required
03/25/2005
BATH FANS VENT BATH FANS.
Correction
Corrective Action Required
03/25/2005
Wiring Installation and Support (IRC) SUPPORT MC CABLE OFF CEILING GRID. HALL
Correction
Corrective Action Required
03/25/2005
Junction Box Required (IRC) TERMINATE MC CABLE THROUGH TOP PLATE HANGING INTO SE. ROOM. 2 ND. FLOOR SE. ROOM WEST WALL
Above Ceiling Inspection Failed 04/01/2005
Correction
Resolved
04/01/2005
READINESS FOR INSPECTION
Correction
Resolved
04/01/2005
FIRESTOP
Correction
Resolved
04/01/2005
BATH FANS
Correction
Resolved
04/01/2005
Wiring Installation and Support (IRC)
Correction
Resolved
04/01/2005
Junction Box Required (IRC)
Correction
Corrective Action Required
04/01/2005
UNUSED OPENINGS AT ELECTRICAL JUNCTION BOXES NOT PLUGGED CORR 211; MEN 207
Correction
Corrective Action Required
04/01/2005
PLACEMENT OF CEILING TILE LOCATIONS CITED OK TO PLACE WHEN READY ALL SPACES EXCEPT TWO
All Rough Inspection - Commercial Passed 04/01/2005
Correction
Resolved
04/01/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 201-211; 216-229; OK TO COVER WHEN READY SPACES LISTED BELOW:
Correction
Resolved
04/01/2005
None SCREW INSPECTION 1 ST. FLOOR SEPERATION WALL BETWEEN 228 AND 230 APPROVED. 2 ND. FLOOR WALL AT DOOR # 12 SCREW INSP. APPROVED. [2 LAYERS 5/8 FIRE ROCK]
Gas Service Inspection - Commercial Passed 04/01/2005
Correction
Resolved
04/01/2005
None
Correction
Resolved
04/01/2005
TEST PRESSURE LEVEL RELEASE GAS SERVICE HELD STEADY AT >= 10 PSI FOR >10 MIN
Gas Piping Inspection - Commercial Passed 04/01/2005
Correction
Resolved
04/01/2005
None NOT TO BE IN CONTACT WITH EARTH CAUTION FOR FINAL INSPECT UNPROTECTED STEEL PIPE
Occupancy Inspection - Codes Commercial Passed 04/28/2005
Correction
Resolved
04/28/2005
Receive Fire Department approval PER N ULLERY 4/28/05
Above Ceiling Inspection Passed 04/28/2005
Correction
Resolved
04/28/2005
UNUSED OPENINGS AT ELECTRICAL JUNCTION BOXES
Correction
Resolved
04/28/2005
PLACEMENT OF CEILING TILE
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home