Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
03/30/2005
|
10/29/2010
|
|
|
|
Correction
Fire Department-IFC Sec. 2703.2.4.2 Above-ground tanks. Above-ground stationary tanks used for the storage of hazardous materials shall be located and protected in accordance with the requirements for outdoor storage of the particular material involved.
Exception: Above-ground tanks that are installed in
vaults complying with Section 3404.2.8 shall not be required to comply with location and protection requirements
for outdoor storage.
2703.2.4.2.1. Marking. Above-ground stationary tanks shall be marked as required by Section 2703.5.
|
|
Correction
Fire Department- IFC Sec.2703.2.2.1 Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following:
1. Piping, tubing, valves, fittings and related components
shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subject.
2. Piping and tubing shall be identified in accordance
with ANSI A13.1 to indicate the material conveyed.
3. Readily accessible manual valves, or automatic remotely
activated fail-safe emergency shutoff valves shall be installed on supply piping and tubing at the following locations:
3.1. The point of use.
3.2. The tank, cylinder or bulk source.
4. Emergency shutoff valves shall be identified and
the location shall be clearly visible and accessible
and indicated by means of a sign.
5. Backflow prevention or check valves shall be provided
when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized
discharge of hazardous materials.
6. Where gases or liquids having a hazard ranking of:
Health hazard Class 3 or 4
Flammability Class 4
Reactivity Class 3 or 4
in accordance with NFPA 704 are carried in pressurized
piping above 15 pounds per square inch gauge (psig) (103 kPa), an approved means of leak detection and emergency shutoff or excess flow control shall be provided. Where the piping originates from within a hazardous material storage
room or area, the excess flow control shall be located
within the storage room or area. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical.
Exceptions:
1. Piping for inlet connections designed to prevent
backflow.
2. Piping for pressure relief devices.
2703.2.2.2 Additional regulations for supply piping
for health-hazard materials. Supply piping and tubing
for gases and liquids having a health-hazard ranking of 3
or 4 in accordance with NFPA704 shall be in accordance
with ANSI B31.3 and the following:
1. Piping and tubing utilized for the transmission of
highly toxic, toxic or highly volatile corrosive liquids
and gases shall have welded, threaded or flanged connections throughout except for connections located within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections
if the material is a liquid.
2. Piping and tubing shall not be located within corridors,
within any portion of a means of egress required
to be enclosed in fire-resistance-rated
construction or in concealed spaces in areas not
classified as Group H occupancies.
Exception: Piping and tubing within the space
defined by thewalls of corridors and the floor or
roof above or in concealed spaces above other
occupancies when installed in accordance with
Section 415.9.6.3 of the International Building
Code for Group H-5 occupancies.
|
|
Correction
Fire Department- IFC Sec.2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official.
2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed
gases shall be conspicuously labeled: COMPRESSED
GAS.
|
|
Correction
Fire Department- IFC Sec.2704.2.1 Spill control for hazardous material liquids. Rooms, buildings or areas used for the storage of hazardous material liquids in individual vessels having a capacity of more than 55 gallons (208 L), or in which the aggregate capacity of multiple vessels exceeds 1,000 gallons (3785 L), shall be provided with spill control to prevent the flowof liquids to adjoining areas. Floors in indoor locations and similar surfaces in outdoor locations shall be constructed to contain a spill from the largest single vessel by one of the following methods:
1. Liquid-tight sloped or recessed floors in indoor locations
or similar areas in outdoor locations.
2. Liquid-tight floors in indoor locations or similar areas
in outdoor locations provided with liquid-tight raised
or recessed sills or dikes.
3. Sumps and collection systems.
4. Other approved engineered systems.Except for surfacing,
the floors, sills, dikes, sumps and collection
systems shall be constructed of noncombustible material,
and the liquid-tight seal shall be compatible
with the material stored. When liquid-tight sills or
dikes are provided, they are not required at perimeter
openings having an open-grate trench across the
opening that connects to an approved collection system.
|
|
Correction
Fire Department-IFC Sec.2704.2.2 Secondary containment for hazardous material liquids and solids. Where required by Table 2704.2.2 buildings, rooms or areas used for the storage of hazardous materials liquids or solids shall be provided with secondary containment in accordance with this section when the capacity of an individual vessel or the aggregate capacity of multiple vessels exceeds the following:
1. Liquids: Capacity of an individual vessel exceeds 55
gallons (208 L) or the aggregate capacity of multiple
vessels exceeds 1,000 gallons (3785 L); and
2. Solids: Capacity of an individual vessel exceeds 550
pounds (250 kg) or the aggregate capacity of multiple
vessels exceeds 10,000 pounds (4540 kg).
|
|
Correction
Fire Department-IFC Sec. 2704.2.2.3 Indoor design. Secondary containment for indoor storage areas shall be designed to contain a spill from the largest vessel plus the design flow volume of fire protection water calculated to discharge from the fire-extinguishing system over the minimum required
system design area or area of the room or area in which
the storage is located, whichever is smaller. The containment
capacity shall be designed to contain the flow for a
period of 20 minutes.
|
|
Correction
Fire Department- IFC Sec.2704.3Ventilation. Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored.
Exception: Storage areas for flammable solids complying
with Chapter 36.
2704.3.1 System requirements. Exhaust ventilation systems
shall comply with all of the following:
1. Installation shall be in accordance with the International
Mechanical Code.
2. Mechanical ventilation shall be at a rate of not less
than 1 cubic foot per minute per square foot
[0.00508 m3/(s · m2)] of floor area over the storage
area.
3. Systems shall operate continuously unless alternative
designs are approved.
4. A manual shutoff control shall be provided outside of
the room in a position adjacent to the access door to
the room or in an approved location. The switch shall
be of the break-glass type and shall be labeled: VENTILATION
SYSTEM EMERGENCY SHUTOFF.
5. Exhaust ventilation shall be designed to consider the
density of the potential fumes or vapors released. For
fumes or vapors that are heavier than air, exhaust shall
be taken from a point within 12 inches (305 mm) of
the floor.
6. The location of both the exhaust and inlet air openings
shall be designed to provide air movement across all
portions of the floor or room to prevent the accumulation
of vapors.
7. Exhaust ventilation shall not be recirculated within
the room or building if the materials stored are capable
of emitting hazardous vapors.
|
|
Correction
Fire Department- The quantity and type of materials submitted with the Haz-mat Permit Application classifies the use of the building as H4. The applicable requirements of the IFC and IBC, 2003 editions, shall apply.
|
|
Correction
Codes Administration - 2003 IBC 415.8.2 - Floors in storage rooms. Floors in storage areas for corrosive liquids and highly toxic or toxic materials shall be of liquid-tight, noncombustible construction.
|
|
Correction
Codes Administration - 2003 IBC 414.2.1 - Construction requirements. Control areas shall be separated from each other by not less than a 1-hour fire barrier construction in accordance with Chapter 7.
|
|
Correction
Codes Administration - 2003 IBC 414.2.3 - Separation. The required fire-resistance rating for fire barrier assemblies shall be in accordance with Table 414.2.2. The floor construction of the control area, shall have a minimum 2-hour fire-resistance rating.
|
|
Correction
Codes Administration - 2003 IBC 414.5 - Inside storage, dispensing and use. The inside storage, dispensing and use of hazardous materials in excess of the maximum allowable quantities per control area of Table 307.7(1) and 307.7(2) shall be in accordance with Sections 4141.5.1 through 414.5.5 of this code and the International Fire Code.
|
|
Correction
Codes Administration - A code analysis was not provided with this permit application.
|
|
Correction
CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
|
|
Correction
CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
|
|
Correction
CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
|
|
Correction
Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
|
|
Correction
Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
|
|
Correction
Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
|
|
Correction
Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance
testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
|
|
Correction
Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
|
|
Correction
CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
|
|
Correction
CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
|
|
Correction
CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
|
|
Correction
CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
|
|
Correction
Codes Administration - 2003 IPC 302.1 - Detrimental or dangerous materials. Ashes, cinders or rags; flammable, poisonous or explosive liquids or gases; oil, grease or any other insoluble material capable of obstructing, damaging or overloading the building drainage or sewer system, or capable of interfering with the normal operation of the sewage treatment processes, shall not be deposited, by any means, into such system.
|
|
Correction
P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
|
|
|