Summary
B0401801
Building Permit - Commercial
Certificate of Occupancy
PREMIERLIFE REAL ESTATE HOLDING
NEW TENANT FINISH
REECE & NICHOLS TENANT FINISH
09/16/2004
10/07/2004
04/05/2005
02/09/2005
Locations
Contacts
A L HUBER, Address:10770 EL MONTE  
BELL/KNOTT & ASSOCIATES, Address:106 W 11TH SUITE 2200  
PREMIERLIFE REAL ESTATE HOLDING, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/15/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.5.
Correction

Codes Administration - 2003 IBC 1016.1 - Construction. Corridors shall be fire-resistance rated in accordance with Table 1016.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- Plans review under the 2003 International Fire Code.
Correction

Fire Department- Provide an exit sign at the corridor from the open office area (outside 117,118) to the south hallway.
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Codes Administration - All plans submitted for review on or after July 6, 2004 shall be designed to the requirements of the 2003 International Building Code, 2003 International Mechanical Code, 2003 International Plumbing Code, 2003 International Fuel Gas Code, 2003 International Fire Code, 2002 National Electric Code and the ANSI A117.1-1998 as amended and adopted by the City of Lee's Summit.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

Codes Administration - There appears to be a detail on top of the Detail 1/A6.1.
Correction

Fire Department- Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $251.00 $251.00 Paid 10/07/2004
24 BLDG Plan Check Fees $18.30 $18.30 Paid 10/07/2004
25 Electrical Permit Fee $243.88 $243.88 Paid 10/07/2004
25 Mechanical Permit Fees $19.50 $19.50 Paid 10/07/2004
25 Plumbing Permit Fees $59.00 $59.00 Paid 10/07/2004
89 Sewer Tap Fees $360.00 $360.00 Paid 10/07/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 10/29/2004
Correction
Partial Correction
10/29/2004
None SHEET E2 ROOMS 102 TO 127 - ELECTRICAL OUTLET ONLY, WIRING & J-BOXES NOT INSTALLED AT COLUMNS
All Rough Inspection - Commercial Failed 11/10/2004
Correction
Corrective Action Required
11/10/2004
ELECTRICAL WIRING INCOMPLETE
Correction
Corrective Action Required
11/10/2004
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATION OF STEEL STUDS & TRACKS
Correction
Corrective Action Required
11/10/2004
DWV PRESSURE TEST COMPLETE SUCCESSFUL TEST
Rough Electrical Inspection - Commercial Passed 11/12/2004
Correction
Resolved
11/12/2004
None
All Rough Inspection - Commercial Partial 11/12/2004
Correction
Partial Correction
11/12/2004
ELECTRICAL WIRING TO BE COMPLETED @ DOORS IN CONJUNCTION W/ FRAMES
Correction
Resolved
11/12/2004
PROTECTION OF COPPER PIPING
Correction
Resolved
11/12/2004
DWV PRESSURE TEST
All Rough Inspection - Commercial Passed 11/24/2004
Correction
Resolved
11/24/2004
ELECTRICAL WIRING TWO PROTOTYPE INSTALLATIONS APPROVED. OK TO PROCEDE WITH ALL SIMILAR. & BOXES BETWEEN DOOR FRAMES & BLU FRAMES
Rated Assembly Inspection Partial 11/30/2004
Correction
Partial Correction
11/30/2004
DEMISING WALL + MECH RM BOTH FACES ALL WALLS. WATER SHUTOFF VALVE + CONNNECTION OF ELECT SVC GEC MUST BE ACCESSIBLE @ FINAL. 1 LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY
Rough Framing Inspection - Commercial Request Complete 11/29/2004 11/30/2004 11/30/2004
Occupancy Inspection - Codes Commercial Not Ready 12/23/2004
Correction
Corrective Action Required
12/23/2004
COMPLIANCE OF LIGHTED SIGNS TENANT SIGNS @ E & W WALLS DEMONSTRATE UL LABEL OR OTHER APPROVABLE DATA
Above Ceiling Inspection Not Ready 12/23/2004
Correction
Corrective Action Required
12/23/2004
ABOVE-CEILING PORTION OF RATED WALLS RE-STATUS "RATED ASSMBLY" WHEN APPROVED ENSURE FULLY SEALED BOTH FACES
Above Ceiling Inspection Failed 12/27/2004
Correction
Corrective Action Required
12/27/2004
TROFFER LIGHT SUPPORT TROFFER LIGHTS TO BE PROPERLY SUPPORTED THROUGHOUT
Correction
Corrective Action Required
12/27/2004
EXPOSED CONDUCTORS COMPLETE INSTALLATION OF ELECTRICAL - EXPOSED CONDUCTORS IN OPEN JUNCTION BOX Entryway
Correction
Corrective Action Required
12/27/2004
FLEXIBLE CONDUIT SUPPORT FLEXIBLE CONDUIT TO BE SECURED WITHIN 12" OF EXITING JUNCTION BOX, DEVICE, ETC. THROUGHOUT
Correction
Partial Correction
12/27/2004
DUCTWORK OFFICE WITH CURVED GLASS - SUPPORT FLEXIBLE DUCTWORK FROM STRUCTURE
Correction
Partial Correction
12/27/2004
None OK TO INSTALL CEILING ON EAST HALF OF BUILDING.
Above Ceiling Inspection Passed 12/28/2004
Correction
Resolved
12/28/2004
TROFFER LIGHT SUPPORT TROFFER LIGHTS TO BE PROPERLY SUPPORTED THROUGHOUT
Correction
Resolved
12/28/2004
EXPOSED CONDUCTORS COMPLETE INSTALLATION OF ELECTRICAL - EXPOSED CONDUCTORS IN OPEN JUNCTION BOX Entryway
Correction
Resolved
12/28/2004
FLEXIBLE CONDUIT SUPPORT FLEXIBLE CONDUIT TO BE SECURED WITHIN 12" OF EXITING JUNCTION BOX, DEVICE, ETC. THROUGHOUT
Correction
Resolved
12/28/2004
DUCTWORK OFFICE WITH CURVED GLASS - SUPPORT FLEXIBLE DUCTWORK FROM STRUCTURE
Correction
Resolved
12/28/2004
None OK TO INSTALL CEILING ON EAST HALF OF BUILDING.
Rated Assembly Inspection Passed 12/29/2004
Correction
Resolved
12/29/2004
DEMISING WALL + MECH RM BOTH FACES ALL WALLS. WATER SHUTOFF VALVE + CONNNECTION OF ELECT SVC GEC MUST BE ACCESSIBLE @ FINAL. 1 LAYER 5/8" TYPE X GWB OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 12/29/2004
Correction
Corrective Action Required
12/29/2004
LABEL SERVICE PANELS WITH PERM. LABEL
Correction
Corrective Action Required
12/29/2004
SEE SHELL BUILDING
Correction
Corrective Action Required
12/29/2004
WATER HEATER RELIEF VALVE REQUIRED TO TERMINATE WITHIN 6 INCHES FROM FLOOR, INTO DRAIN. CUST. CLOSET
Correction
Corrective Action Required
12/29/2004
Receive Fire Department approval UNDER SEPARATE COVER. OK FOR TEMP.
Correction
Partial Correction
12/29/2004
OPEN ELECTRICAL INSTALLED IN TEMP. J-BOX ABOVE CEILING 101 VEST NE CORNER
Correction
Corrective Action Required
12/29/2004
EXIT SIGN NOT INSTALLED 102 VEST HALL
Occupancy Inspection - Codes Commercial Failed 01/31/2005
Correction
Corrective Action Required
01/31/2005
UL LABELING OF LIGHTED SIGNS NO LABELS FOUND
Correction
Corrective Action Required
01/31/2005
LABEL SERVICE PANELS OCCUPIED POSITIONS LABELING INCOMPLETE
Correction
Resolved
01/31/2005
SEE SHELL BUILDING
Correction
Resolved
01/31/2005
WATER HEATER RELIEF VALVE
Correction
Resolved
01/31/2005
Receive Fire Department approval PER N ULLERY 1/31/05
Correction
Resolved
01/31/2005
OPEN ELECTRICAL
Correction
Resolved
01/31/2005
EXIT SIGN
Occupancy Inspection - Codes Commercial Passed 02/08/2005
Correction
Resolved
02/08/2005
UL LABELING OF LIGHTED SIGNS
Correction
Resolved
02/08/2005
LABEL SERVICE PANELS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home