Permit Application Status

B0401783


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0401783
Building Permit - Commercial
Certificate of Occupancy
LEES LANDING PROPERTIES LLC
NEW TENANT FINISH
TENANT FINISH
09/15/2004
10/19/2004
04/17/2005
03/04/2005
Locations
Contacts
MEMCO ENTERPRISES, Address:14219 KENNEDY RD  
LEES LANDING PROPERTIES LLC, Address:2270 NW SUMMERFIELD DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/14/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - The cost of the project was not provided with the permit application.
Correction

Codes Administration - 2003 IPC 608.1 - General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.9.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; IFC 1003.3.1.8 Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department; Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Combustible debris, waste materials and trash shall not be burned on site.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IMC 403.3 - Ventilation rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3 based on the occupancy of the space and occupant load or other parameter as stated therein. The occupant load utilized for design of the ventilation system shall not be less than the number determined fron the estimated maximum occupant load rate indicated in Table 403.3. Ventilation rates for occupancies not represented in Table 403.3 shall be determined by an approved engineering analysis. The ventilation system shall b designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code.
Correction

Codes Administration - 2003 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Tale 403.1 shall be considered individually by the code official. The number of occupants shall be deetermined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $35.00 $35.00 Paid 10/19/2004
24 BLDG Plan Check Fees $4.75 $4.75 Paid 10/19/2004
25 Electrical Permit Fee $35.77 $35.77 Paid 10/19/2004
25 Mechanical Permit Fees $24.00 $24.00 Paid 10/19/2004
25 Plumbing Permit Fees $25.00 $25.00 Paid 10/19/2004
89 Sewer Tap Fees $150.00 $150.00 Paid 10/19/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 12/27/2004
Correction
Corrective Action Required
12/27/2004
Through Penetrations (IRC) FIRESTOP ALL PENETRATIONS THROUGH TOP PLATES.
Correction
Corrective Action Required
12/27/2004
INCOMPLETE INSTALLATION COMPLETE INSTALLATION OF JUNCTION BOX SERVING EXTERIOR GFCI NEAR A/C UNITS. EAST WALL
Correction
Resolved
12/27/2004
None OK TO INSULATE AND ROCK.
Above Ceiling Inspection Failed 02/15/2005
Correction
Corrective Action Required
02/15/2005
LOW-VOLTAGE CABLE INSTALLATION UNIDENTIFIED L.V. CABLE LAID LOOSE ON CEILING SUPPORT WIRES AND OTHER SYSTEMS NOT SECURELY ATTACHED TO STRUCTURE
Above Ceiling Inspection Passed 02/16/2005
Correction
Resolved
02/16/2005
LOW-VOLTAGE CABLE INSTALLATION
All Rough Inspection - Commercial Passed 02/23/2005
Correction
Resolved
02/23/2005
Through Penetrations (IRC)
Correction
Resolved
02/23/2005
INCOMPLETE INSTALLATION
Correction
Resolved
02/23/2005
None
Electrical Service Inspection Passed 02/23/2005
Correction
Resolved
02/23/2005
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
Occupancy Inspection - Codes Commercial Passed 03/03/2005
Correction
Resolved
03/03/2005
None OCCUPANCY APPROVED CLOSE PERMIT C. O.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home