Permit Application Status

B0401762


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0401762
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
NEW TENANT FINISH
TENANT FINISH 2ND FLOOR BLDG D
09/13/2004
12/10/2004
06/08/2005
04/22/2005
Locations
Contacts
ACI BOLAND, Address:11229 NALL SUITE 140  
J E DUNN CONSTRUCTION, Address:929 HOLMES  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/12/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1110.1 - Signs. Required accessible elements shall be identified by the International Symbol of Accessiblity a the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessbile areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered in a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the checkout aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible.
Correction

Codes Administration - 2003 IBC 407.3 - Corridor walls. Corridor walls shall be constructed as smoke partitions.
Correction

St. Lukes - The City shall not issue any temporary or final Certificate of Occupancy for any structure in the Developerment until a Certificate of Substantial Completion for the Road Improvements has been issued by MoDOT.
Correction

St. Lukes - A Proprtionate Share of the Total Road Contribution shall be made to the City at or before the time a certificate of occupancy is issued by the City for a building constructed by, or by a building contractor on behalf of, the Developer on the Property, excluding the medical office buildings.
Correction

CA - A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2003 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

Codes Administration - The cost of the project has not been provided.
Correction

Codes Administration - Third party review of the electrical system will be required due to amount of medical exam and treatment space.
Correction

Codes Administration - 2003 IBC 603.1 - Allowable materials. Combustible materials shall be permitted in buildings of Type I and II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3.
Correction

CA - I am unclear as to the types of activites/treatments performed in the Bone Density and Treatment rooms.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

Fire Department: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required fire protection systems shall be extended, altered, or augmented as necessary to maintain and continue pro-tection whenever the building is altered, remodeled or added to.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

Codes Administration - 2003 IPC 701.5 - Damage to drainage system or public sewer. Wastes detrimental to the public sewer system or to the functioning of the sewate-treatment plant shall be treated and disposed of in accordance with Section 1003 as directed by the code official.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $3,590.00 $3,590.00 Paid 12/10/2004
24 BLDG Plan Check Fees $79.80 $79.80 Paid 12/10/2004
25 Electrical Permit Fee $359.31 $359.31 Paid 12/10/2004
25 Mechanical Permit Fees $67.00 $67.00 Paid 12/10/2004
25 Plumbing Permit Fees $159.00 $159.00 Paid 12/10/2004
89 Sewer Tap Fees $1,080.00 $1,080.00 Paid 12/10/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Partial 11/22/2004
Correction
Partial Correction
11/22/2004
DWV SUBSYSTEM @ 1ST FLOOR TENANT FINISH AREA D/6; VISUAL & PRESSURE TEST VENTING TO ROOF @LOCATION
Correction
Resolved
11/22/2004
ROOF DRAIN/STORM SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA
Correction
Partial Correction
11/22/2004
DWV SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA D/6; VISUAL & PRESSURE TEST VENTING TO ROOF @LOCATION
Rough Plumbing Inspection - Commercial Partial 11/23/2004
Correction
Partial Correction
11/23/2004
DWV SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA D/6; B/6; VISUAL & PRESSURE TEST VENTING TO ROOF @LOCATION
Rough Plumbing Inspection - Commercial Partial 11/24/2004
Correction
Partial Correction
11/24/2004
DWV SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA D/6; B/6; VENTS W/ VTR @ B/3; VISUAL & PRESSURE TEST VENTING TO ROOF @LOCATION
All Rough Inspection - Commercial Partial 12/17/2004
Correction
Partial Correction
12/17/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH 215-217; 219-221; 222-225; 227-235; 237; 240; 241; OK TO COVER WHEN READY SPACES LISTED BELOW
Rough Plumbing Inspection - Commercial Passed 12/17/2004
Correction
Resolved
12/17/2004
DWV SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA
Correction
Resolved
12/17/2004
ROOF DRAIN/STORM SUBSYSTEM @ 2ND FLOOR TENANT FINISH AREA
Correction
Resolved
12/17/2004
DWV SUBSYSTEM @ 1ST FLOOR TENANT FINISH AREA
All Rough Inspection - Commercial Partial 12/20/2004
Correction
Partial Correction
12/20/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH 215-217; 219-221; 222-225; 227-235; 237; 240; 241; 213; 218; 218A; 226; 236; 239; 242; 244-246; OK TO COVER WHEN READY SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 01/05/2005
Correction
Partial Correction
01/05/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 215-218; 218A-226; 227-237; 213; 239-242; 244-246; 273-277; 280-287; 289; 248 W OF (4.8); OK TO COVER WHEN READY SPACES LISTED BELOW
Above Ceiling Inspection Partial 02/02/2005
Correction
Partial Correction
02/02/2005
ABOVE-CEILING SYSTEMS ROOMS 213-237; 239-243; 238: NO FIREWALL GWB FOUND ABOVE DUCT @ NW CORNER AREAS LISTED BELOW OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 03/16/2005
Correction
Corrective Action Required
03/16/2005
Receive Fire Department approval
Correction
Corrective Action Required
03/16/2005
COVER PLATES ON NON-EMERGENCY ELECT RECEPTS NOT PROPER FOR CIRCUIT
Correction
Corrective Action Required
03/16/2005
SURFACE-MOUNTED ELECTRICAL PLUG STRIP LISTING INFO REQUIRED + NOT HOT FOR TEST
Correction
Corrective Action Required
03/16/2005
OCCUPANCY APPROVAL STATUS IBC 110.1: UNTIL APPROVED DO NOT OCCUPY OR PLACE PERSONAL PROPERTY
Correction
Corrective Action Required
03/16/2005
FIRE-RATED DOORS ON SHELL STAIRWELLS/CORRIDORS ENSURE ALL IN PLACE
Correction
Corrective Action Required
03/16/2005
EGRESS PATH AT EAST END OF BUILDING ENSURE CLEAR, TRAVERSIBLE
Correction
Corrective Action Required
03/16/2005
PADDING OF PIPING UNDER H.C. RESTROOM SINKS NOT INSTALLED ADA/ANSI
Correction
Corrective Action Required
03/16/2005
HANDICAPPED ACCESSIBLE RESTROOM SIGNS ADA/ANSI RESTROOM DOORS NOT FOUND
Above Ceiling Inspection Partial 03/16/2005
Correction
Partial Correction
03/16/2005
ABOVE-CEILING SYSTEMS ROOMS 213-237; 239-243; 238: NO FIREWALL GWB FOUND ABOVE DUCT @ NW CORNER AREAS LISTED BELOW OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 03/16/2005
Correction
Partial Correction
03/16/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH 215-218; 218A-226; 227-237; 213; 239-242; 244-246; 273-277; 280-287; 289; 248 W OF (4.8); OK TO COVER WHEN READY SPACES LISTED BELOW
All Rough Inspection - Commercial Passed 03/18/2005
Correction
Resolved
03/18/2005
WALL FRAMING + IN-WALL SYSTEMS ROUGH
Above Ceiling Inspection Passed 03/18/2005
Correction
Resolved
03/18/2005
ABOVE-CEILING SYSTEMS
Occupancy Inspection - Codes Commercial Failed 03/18/2005
Correction
Resolved
03/18/2005
Receive Fire Department approval PER N ULLERY 3/14/05
Correction
Resolved
03/18/2005
COVER PLATES ON NON-EMERGENCY ELECT RECEPTS
Correction
Corrective Action Required
03/18/2005
SHELL BUILDING PERMIT STATUS NOT FULLY APPROVED
Correction
Partial Correction
03/18/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
03/18/2005
FIRE-RATED DOORS ON SHELL STAIRWELLS/CORRIDORS
Correction
Resolved
03/18/2005
EGRESS PATH AT EAST END OF BUILDING
Correction
Resolved
03/18/2005
PADDING OF PIPING UNDER H.C. RESTROOM SINKS
Correction
Resolved
03/18/2005
HANDICAPPED ACCESSIBLE RESTROOM SIGNS SEE SHELL BLDG PERMIT
Correction
Corrective Action Required
03/18/2005
SURFACE-MOUNTED ELECTRICAL PLUG STRIP LISTING INFO REQUIRED + NOT HOT FOR TEST
Occupancy Inspection - Codes Commercial Passed 04/21/2005
Correction
Resolved
04/21/2005
SHELL BUILDING PERMIT STATUS
Correction
Resolved
04/21/2005
OCCUPANCY APPROVAL STATUS
Correction
Resolved
04/21/2005
HANDICAPPED ACCESSIBLE RESTROOM SIGNS
Correction
Resolved
04/21/2005
SURFACE-MOUNTED ELECTRICAL PLUG STRIP
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home