Permit Application Status

B0401544


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0401544
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
NEW TENANT FINISH
INGENIOUS TOYS TENANT FINISH
08/16/2004
08/19/2004
02/15/2005
09/21/2004
Locations
Contacts
SCHARHAG ARCHITECTS, Address:1806 SWIFT SUITE 203  
ZIPCO CONTRACTING INC, Address:1019 SWIFT AVE  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/12/2005 10/29/2010
Correction

Codes Administration - 2003 IBC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be proivided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways locate in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1023.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2003 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2003 IBC 1020.3 - Construction. Exit passageway enclosures shall have walls, floors and ceilings of not less than 1-hour fire-resistance rating, and not less than that required for any connecting exit enclosure. Exit passageways shall be constructed as fire barriers in accordance with Section 706.
Correction

Codes Administration - 2003 IBC 1020.4 - Openings and penetrations. Exit passageway opening protectives shall be in accordance with the requirements of Section 715. Except as permitted in Section 402.4.6, openings in exit passageways other than unexposed exterior openings shall be limited to those necessary for exit access to the exit passageway from normally occupied spaces and for egress from the exit passageway. Where interior exit enclosures are extended to the exterior of a building by an exit passageway, the door assembly from the exit enclosure to the exit passageway shall be protected by a fire door conforming to the requirements in Section 715.3. Fire door assemblies in exit passageways shall comply with Section 715.3.4.
Correction

Codes Administration - 2003 IBC 1109.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2003 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

Codes Administration - 2003 IBC 1013.2 - Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room that can be locked to prevent egress.
Correction

Codes Administration - 2003 IBC 1008.1.2 - Egress doors shall be side-hinged swinging. Doors shall swing in the directrion of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy.
Correction

Codes Administration - LSCO Chapter 7 - The City of Lee's Summit is currently utilizing the 2003 International Codes, including the IFC and the 2002 National Electrical Code.
Correction

Codes Administration - 2003 IBC 1004.1 - In determining the means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through 1004.1.3.
Correction

Codes Administration - 2003 IBC Chapter 6 - The constrution type is shown as II-B, which does not permit combustible materials. The Codes Administration Department will permit the floor of the display area to be fire treated plywood, but not regular plywood as shown.
Correction

Codes Administration - 2002 NEC 230.72 (C) - In a multiple occupancy building, each occupant shall have access to the occupant's service disconnecting means.
Correction

Fire Department; Egress from a room or space shall not pass through adjoining or interven-ing rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass though a room which can be locked to prevent egress.
Correction

Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cove-ings, nor shall such cords be subject to environmental damage or physical impact.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $170.00 $170.00 Paid 08/19/2004
24 BLDG Plan Check Fees $15.60 $15.60 Paid 08/19/2004
25 Electrical Permit Fee $30.00 $30.00 Paid 08/19/2004
25 Plumbing Permit Fees $19.00 $19.00 Paid 08/19/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 08/24/2004
Correction
Partial Correction
08/24/2004
UNDER-SLAB DWV PIPING PIPE MUST BE CAPPED OK TO COVER WHEN READY EXCEPT @ RR WHERE EXSTG
Underslab Plumbing Inspection - Commercial Passed 08/25/2004
Correction
Resolved
08/25/2004
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY
All Rough Inspection - Commercial Failed 08/30/2004
Correction
Corrective Action Required
08/30/2004
PROTECTION OF COPPER & PVC PIPING IPC 305.8; IRC P2603: INSTALL SHIELD PLATES AT STUDS & TRACKS < 1-1/2" FROM FACE OF STUDS / TRACKS
Correction
Corrective Action Required
08/30/2004
PROTECTION OF COPPER WATER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATION OF STEEL STUDS & TRACKS
Rated Assembly Inspection Partial 08/30/2004
Correction
Partial Correction
08/30/2004
SOUTH DEMISING WALL N FACE GWB OK TO TAPE/MUD; S FACE OK TO INSTALL GWB; FRAMING OK OK TO COVER FOLLOWING:
Correction
Partial Correction
08/30/2004
RATED EGRESS CORRIDOR-1 CEILING FRAMING OK TO COMPLETE GWB TOP SURFACE; GWB @ WALLS & CEILING OK TO TAPE/MUD
All Rough Inspection - Commercial Passed 08/31/2004
Correction
Resolved
08/31/2004
PROTECTION OF COPPER & PVC PIPING
Correction
Resolved
08/31/2004
PROTECTION OF COPPER WATER PIPING
Rated Assembly Inspection Partial 08/31/2004
Correction
Partial Correction
08/31/2004
SOUTH DEMISING WALL N FACE GWB OK TO TAPE/MUD; S FACE LOWER 12' OK TO TAPE/MUD; FRAMING OK OK TO COVER FOLLOWING:
Rated Assembly Inspection Partial 09/02/2004
Correction
Partial Correction
09/02/2004
SOUTH DEMISING WALL OK TO TAPE/MUD: N FACE SALES; S FACE LOWER 12'; STORAGE-2 S WALL ; FRAMING OK OK TO COVER FOLLOWING:
Correction
Resolved
09/02/2004
RATED EGRESS CORRIDOR - 2 WHEN READY WALLS & HARD LID OK TO TAPE & MUD
Rough Framing Inspection - Commercial Request Complete 9/1/2004 9/2/2004 09/02/2004
Above Ceiling Inspection Partial 09/07/2004
Correction
Partial Correction
09/07/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY EXCEPT @ OPEN ELECT JB's
Rated Assembly Inspection Passed 09/13/2004
Correction
Resolved
09/13/2004
SOUTH DEMISING WALL OK TO TAPE/MUD: N FACE SALES; S FACE LOWER 12'; STORAGE-2 S WALL ; FRAMING OK OK TO COVER FOLLOWING:
Correction
Resolved
09/13/2004
RATED EGRESS CORRIDOR-1 CEILING FRAMING OK TO COMPLETE GWB TOP SURFACE; GWB @ WALLS & CEILING OK TO TAPE/MUD
Correction
Resolved
09/13/2004
None SCREW PATTERN APPROVED OK TO COVER SOUTH ELEV DEMISING WALL
Above Ceiling Inspection Passed 09/13/2004
Correction
Resolved
09/13/2004
ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Partial 09/15/2004
Correction
Resolved
09/15/2004
Receive Fire Department approval PER N ULLERY 9/15/04
Correction
Resolved
09/15/2004
Receive Water Utilities Approval PER B BOYCE 9/15/04
Correction
Corrective Action Required
09/15/2004
ELECTRICAL RECEPTACLES @ SALES AS REQUIRED SOME BROKEN; SOME LOOSE REPAIR/REPLACE/TIGHTEN
Correction
Corrective Action Required
09/15/2004
ELECTRICAL RECEPTACLE @ STORAGE #1 INSTALL EXTENSION RING IF >1/4" FROM WALL PLANE WEST WALL NOT TIGHT TO BOX
Correction
Corrective Action Required
09/15/2004
UNUSED OPENING AT ELECTRICAL PANEL NOT PLUGGED NEC 110-12
Correction
Corrective Action Required
09/15/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 110-22; 384-13; IRC E36O6.2. EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. SERVICE PANELS PERMANENT SCHEDULES
Correction
Corrective Action Required
09/15/2004
LIGHTED SIGN @ FASCIA BOX NOT UL LABELED
Correction
Partial Correction
09/15/2004
ELECTRICAL WIRING IN CANOPY BOXES NOT CLOSED + MC CONDUCTORS EXPOSED
Correction
Partial Correction
09/15/2004
OCCUPANCY STATUS NO CUSTOMERS OR PUBLIC UNTIL APPROVED OK TO FIXTURE & STOCK FOR SETUP FOR BUSINESS
Occupancy Inspection - Codes Commercial Passed 09/17/2004
Correction
Resolved
09/17/2004
ELECTRICAL RECEPTACLES @ SALES
Correction
Resolved
09/17/2004
ELECTRICAL RECEPTACLE @ STORAGE #1
Correction
Resolved
09/17/2004
UNUSED OPENING AT ELECTRICAL PANEL
Correction
Resolved
09/17/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
09/17/2004
LIGHTED SIGN @ FASCIA BOX NOW UL LABELED
Correction
Resolved
09/17/2004
ELECTRICAL WIRING IN CANOPY
Correction
Resolved
09/17/2004
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home