Permit Application Status

B0401218


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0401218
Building Permit - Commercial
Certificate of Occupancy
HSM WDC PINETREE LLC
CHANGE OF TENANT
PULP FICTION TENANT FINISH
06/30/2004
07/09/2004
01/05/2005
08/31/2004
Locations
Contacts
DENNFM, Address:3003 S SLAUGHTER  
HSM WDC PINETREE LLC, Address:12700 HILLCREST RD STE 125  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/27/2004 10/29/2010
Correction

Fire Department-Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - The doors located on the north side of the foyer need to be swithched so that they swing out into foyer in the direction of travel as noted on the plans.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. IFC 1003.2.10.4 Exit sign illumination shall also be in accordance with the IBC.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $68.00 $68.00 Paid 07/09/2004
24 BLDG Plan Check Fees $7.50 $7.50 Paid 07/09/2004
25 Electrical Permit Fee $30.00 $30.00 Paid 07/09/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 07/23/2004
Correction
Resolved
07/23/2004
WALL FRAMING + IN-WALL SYSTEMS ROUGH NOTE: CALL FOR ABOVE-CEILING INSPECTION WHEN READY. DO NOT RE-INSTALL TILE UNTIL APPROVED. OK TO COVER WHEN READY
Above Ceiling Inspection Not Ready 08/05/2004
Correction
Corrective Action Required
08/05/2004
READINESS FOR INSPECTION IBC 109.1, 109.5: NOT READY PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
Above Ceiling Inspection Failed 08/09/2004
Correction
Resolved
08/09/2004
READINESS FOR INSPECTION
Correction
Corrective Action Required
08/09/2004
INSTALLATION OF MC ELECTRICAL CABLE NEC 300-11 & 334-10 [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG] NOT SECURELY FASTENED WITHIN 12" OF BOXES
Correction
Corrective Action Required
08/09/2004
UNUSED OPENINGS AT ELECTRICAL PANELS / JUNCTION BOXES NOT PLUGGED NEC 110-12
Correction
Corrective Action Required
08/09/2004
SUPPORT/SECURING OF LOW-VOLTAGE CABLE OR CEILING GRID SUPPORT TO BLDG STRUCTURE NOT TO M/E/P SYSTEMS
Correction
Corrective Action Required
08/09/2004
UNUSED OPENINGS AT ELECTRICAL JUNCTION BOXES NOT PLUGGED NEC 110-12
Correction
Corrective Action Required
08/09/2004
ELECTRICAL JUNCTION BOXES NOT SECURED TO STRUCTURE
Correction
Corrective Action Required
08/09/2004
ELECTRICAL JUNCTION BOX NOT CLOSED
Correction
Corrective Action Required
08/09/2004
LIQUIDTIGHT/ARMORED CABLE NOT FULLY SUPPORTED TO STRUCTURE
Occupancy Inspection - Codes Commercial Not Ready 08/26/2004
Correction
Corrective Action Required
08/26/2004
READINESS FOR INSPECTION NOT READY FOR FINAL INSPECTION ABOVE-CEILING ISSUES NOT CORRECTED/APPROVED
Correction
Corrective Action Required
08/26/2004
Receive Fire Department approval
Correction
Resolved
08/26/2004
Receive Water Utilities Approval PER B BOICE 8/26/04 NO WU ISSUES
Above Ceiling Inspection Failed 08/27/2004
Above Ceiling Inspection Passed 08/28/2004
Correction
Resolved
08/28/2004
INSTALLATION OF MC ELECTRICAL CABLE
Correction
Resolved
08/28/2004
UNUSED OPENINGS AT ELECTRICAL PANELS / JUNCTION BOXES
Correction
Resolved
08/28/2004
SUPPORT/SECURING OF LOW-VOLTAGE CABLE
Correction
Resolved
08/28/2004
UNUSED OPENINGS AT ELECTRICAL JUNCTION BOXES
Correction
Resolved
08/28/2004
ELECTRICAL JUNCTION BOXES
Correction
Resolved
08/28/2004
ELECTRICAL JUNCTION BOX
Correction
Resolved
08/28/2004
LIQUIDTIGHT/ARMORED CABLE
Occupancy Inspection - Codes Commercial Failed 08/28/2004
Correction
Resolved
08/28/2004
READINESS FOR INSPECTION
Correction
Resolved
08/28/2004
Receive Fire Department approval PER N ULLERY
Correction
Corrective Action Required
08/28/2004
EMERGENCY LIGHTS @ EAST CORRIDOR INOP
Correction
Partial Correction
08/28/2004
OCCUPANCY STATUS OK TO STAFF & STOCK NO PUBLIC UNTIL APPROVED
Occupancy Inspection - Codes Commercial Passed 08/30/2004
Correction
Resolved
08/30/2004
EMERGENCY LIGHTS @ EAST CORRIDOR
Correction
Resolved
08/30/2004
OCCUPANCY STATUS
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home