Summary
B0401126
Building Permit - Commercial
Certificate of Occupancy
CITIZENS UNION STATE BANK & TRUST
NEW COMMERCIAL
NEW COMMERCIAL BUILDING
06/17/2004
11/29/2004
05/28/2005
05/16/2007
Locations
Contacts
GOULD EVANS GOODMAN, Address:4041 MILL STREET  
MILLER STAUCH CONSTRUCTION COMPANY, Address:13000 WEST 87TH ST PARKWAY SUITE 100  
CITIZENS UNION STATE BANK & TRUST, Address:102 N SECOND ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/14/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - I am unable to find information pertaining to the requirements for area of refuge communication, instructions and identification.
Correction

Fire Derpartment; When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided.
Correction

Fire Department; Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet of all portions of the facility or any portion of the exterior wall of the first story of the building as measured by an approved route around the exterior of the building or facility.
Correction

Fire Department; Fire apparatus access roads shall have an unobstructed width of not less than 20 feet except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches.
Correction

Fire Department; Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - 2000 IBC 1004.2.2.1 - Two exit or exit access doorways. Where two exits or exit access doorways are required, from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

CA - 2000 IBC 707.4.2 - Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

Fire Department; Buildings other than one- and two-family dwellings. The minimum fire flow and flow duration for buildings otherthan one- and two-family dwellings shall be as specified in Table B105.1.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

NOTE: The contractor must contact the Missouri Department of Natural Resources at 1-800-361-4827 prior to starting the demolition.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

CA - 2000 IBC 1704.1.1 - The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 3002.3 - Emergency signs. - An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occpants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 1003.2.13.3.
Correction

CA - 2000 IBC 1108.12.3 - Point of sales and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, the accessible counters shall also be dispersed.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

CA - 2000 IMC 602.2.1 - Except as required by Section 602.2.1.1 through 602.2.1.4, materials exposed within plenumbs shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

CA - Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative.
Correction

CA - Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $5,282.00 $5,282.00 Paid 11/29/2004
24 BLDG Plan Check Fees $108.00 $108.00 Paid 11/29/2004
25 Electrical Permit Fee $317.10 $317.10 Paid 11/29/2004
25 Mechanical Permit Fees $204.50 $204.50 Paid 11/29/2004
25 Plumbing Permit Fees $128.00 $128.00 Paid 11/29/2004
84 Water Meters $625.00 $625.00 Paid 11/29/2004
85 Water Taps $13,670.00 $13,670.00 Paid 11/29/2004
89 Sewer Tap Fees $570.00 $570.00 Paid 11/29/2004
Right of Way Permit $35.00 $35.00 Paid 11/29/2004
Road and Bridge Escrow $27,694.08 $27,694.08 Paid 06/27/2005
94 Sidewalk Escrow $1,200.00 $1,200.00 Paid 06/27/2005
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Driveway Inspection Passed 03/03/2005
Miscellaneous Inspection Passed 03/21/2005
Correction
Resolved
03/21/2005
None REQUESTED INSPECTION WAS A FOR A FRAMING INSPECTION. ACTUALLY SUPT. HAD QUESTIONS ON RATED MECHANICL ROOM WALL AND CEILING. ALSO WALKED THROUGH BUILDING WITH SUPT. PRE. FRAMING INSP.
Rough Framing Inspection - Commercial Request Complete 3/18/2005 3/21/2005 03/21/2005
Water Service Inspection Not Ready 03/29/2005
Correction
Corrective Action Required
03/29/2005
NOT READY
Correction
Partial Correction
03/29/2005
None 2 INCH WATER LINE 20 FT. FROM THE BUILDING TO WITHIN 3 FT. ON WATER MAIN.
Erosion Control Inspection Residential Passed 03/29/2005
Water Service Inspection - Commercial Request Complete 3/29/2005 3/29/2005 03/29/2005
Water Service Inspection - Commercial Request Complete 3/29/2005 3/29/2005 03/29/2005
Water Service Inspection Partial 03/30/2005
Correction
Partial Correction
03/30/2005
None WATER PIPE RAN INTO THE MECHANICAL ROOM.
Correction
Resolved
03/30/2005
NOT READY
Erosion Control Inspection Residential Passed 03/30/2005
Underground Plumbing Inspection - Commercial Partial 03/30/2005
Correction
Partial Correction
03/30/2005
None ROOF DRAIN FROM STORM BOX 60 FT. TO THE SOUTH - EAST SIDE OF THE BUILDING
Water Service Inspection - Commercial Request Complete 3/30/2005 3/30/2005 03/30/2005
Erosion Control Inspection Residential Passed 04/01/2005
Gas Service Inspection - Commercial Partial 04/01/2005
Correction
Partial Correction
04/01/2005
None GAS TEST - PARTIAL APPROVAL FROM OUTSIDE BUILDING TO THROUGH THE ROOF. TEST PRESSURE 16 PSI.
Gas Piping Inspection - Commercial Partial 04/01/2005
Correction
Partial Correction
04/01/2005
None GAS PIPE PARTIAL APPROVAL FROM OUTSIDE BUILDING TO THROUGH THE ROOF.
Underground Plumbing Inspection - Commercial Passed 04/01/2005
Correction
Resolved
04/01/2005
None ROOF DRAINS COMPLETED FROM THE BUILDING TO STORM BOXES.
All Rough Inspection - Commercial Failed 04/01/2005
Correction
Corrective Action Required
04/01/2005
PVC PROTECT PVC IN RETURN AIR ABOVE CEILING WITH FLAME SPREAD AND SMOKE DEVELOPED RATING MATERIAL. ABOVE CEILING MENS BATHROOM
Correction
Corrective Action Required
04/01/2005
INS. MATERIAL PROVIDE DATA SHEET ON WATER PIPE INSULATION MATERIAL
Correction
Corrective Action Required
04/01/2005
Fireblocking (IRC) FIRESTOP PENETRATIONS BETWEEN FLOORS BETWEEN FLOORS
Correction
Partial Correction
04/01/2005
None THIS INSPECTION IS FOR 1 ST. AND 2 ND. FLOOR WALLS AND ABOVE CEILING AREAS THAT GET A HARD CEILING ONLY. OK TO ROCK THESE AREAS ONLY.
Rough Framing Inspection - Commercial Request Complete 3/31/2005 4/1/2005 04/01/2005
Erosion Control Inspection Residential Passed 04/07/2005
All Rough Inspection - Commercial Partial 04/07/2005
Correction
Partial Correction
04/07/2005
PVC PROTECT PVC IN RETURN AIR ABOVE CEILING WITH FLAME SPREAD AND SMOKE DEVELOPED RATING MATERIAL. ABOVE CEILING MENS BATHROOM
Correction
Resolved
04/07/2005
INS. MATERIAL
Correction
Resolved
04/07/2005
Fireblocking (IRC) BETWEEN FLOORS
Correction
Partial Correction
04/07/2005
None FRAMING AND ELECTRICAL APPROVED - DRIVE THROUGH AREA. INSTALL ROOF DRAIN. OK ROCK.
Erosion Control Inspection Residential Passed 04/26/2005
Gas Service Inspection - Commercial Passed 04/26/2005
Correction
Resolved
04/26/2005
None GAS APPROVED TEST PRESSURE 15 PSI RELEASE GAS
Gas Piping Inspection - Commercial Passed 04/26/2005
Correction
Resolved
04/26/2005
None
Footing Inspection - Commercial Partial 05/24/2005
Correction
Partial Correction
05/24/2005
None 3 LIGHT POLE BASES 24 INCHS X 6 FEET IN DEPTH. CONDUIT INSTALLED FOR ELECT. CONDUCTORS. NO DRIVEN GROUNG RODS AT TIME OF INSPECTION.
Erosion Control Inspection Residential Passed 05/24/2005
Electrical Service Inspection Passed 06/01/2005
Correction
Resolved
06/01/2005
None 800 AMP MAIN SERVICE APPROVED - RELEASE. 3 - 125 AMPSERVICES APPROVED - RELEASE. 1 - 200 AMP SERVICE APPROVED - RELEASE.
Underground Electrical Inspection - Commercial Passed 06/01/2005
Correction
Resolved
06/01/2005
None 3 PARKING LOT LIGHT POLE BASES APPROVED. GROUNDING APPROVED.
Rough Electrical Inspection - Commercial Partial 06/01/2005
Correction
Partial Correction
06/01/2005
None ENTRY CANOPY CAN LIGHTS APPROVED. WEST SIDE
Erosion Control Inspection Residential Passed 06/01/2005
Above Ceiling Inspection Failed 06/13/2005
Correction
Corrective Action Required
06/13/2005
OPEN J-BOX 0PEN J-BOX 1 ST FLOOR BATHROOM 2 ND FLOOR BATHROOM
Correction
Corrective Action Required
06/13/2005
FL;OOR PENETRATIONS GROUNT MOP SINK DRAIN THROUGH THE FLOOR.
Correction
Resolved
06/13/2005
None CONTACT CAPTIAN NEIL ULLERY AT 935-3453 FOR KNOX BOX LOCATION.
All Rough Inspection - Commercial Partial 06/13/2005
Correction
Resolved
06/13/2005
PVC ABOVE CEILING MENS BATHROOM
Correction
Partial Correction
06/13/2005
None FRAMING AND ELECTRICAL APPROVED - DRIVE THROUGH AREA. INSTALL ROOF DRAIN. OK ROCK.
Rated Assembly Inspection Passed 06/27/2005
Correction
Resolved
06/27/2005
None ELEVATOR APPROVED
Above Ceiling Inspection Passed 06/27/2005
Correction
Resolved
06/27/2005
FL;OOR PENETRATIONS
Correction
Resolved
06/27/2005
OPEN J-BOX
All Rough Inspection - Commercial Passed 06/27/2005
Correction
Resolved
06/27/2005
None
Correction
Resolved
06/27/2005
None
Occupancy Inspection - Codes Commercial Failed 06/27/2005
Correction
Corrective Action Required
06/27/2005
ELEVATOR INSPECTION PROVIDE STATE ELEVATOR INSPECTION WHEN COMPLETED
Correction
Corrective Action Required
06/27/2005
Guards (IBC) COMPLETE GUARDRAILS AND HAND RAILS Stairway
Correction
Corrective Action Required
06/27/2005
SEE CORRECTIONS OK FOR OWNER SUPPLIED EQUIPMENT AND FURNISHINGS. NOT TO BE OPEN TO THE PUBLIC.
Correction
Corrective Action Required
06/27/2005
SIDEWALKS REQUIRED
Correction
Corrective Action Required
06/27/2005
DOOR LATCH NW DOOR REQUIRED TO HAVE A THUMB LATCH.
Correction
Corrective Action Required
06/27/2005
FOUNTAIN COMPLETE FOUNTATION INSTALLATION
Correction
Corrective Action Required
06/27/2005
Receive Planning & Development Approval
Correction
Corrective Action Required
06/27/2005
Receive Public Works Approval SEE PUBLIC WORKS REQUIREMENTS.
Correction
Corrective Action Required
06/27/2005
ESCROW ESCROW REQUIRED TO BE PAID PRIOR TO OCCUOANCY.
Footing Inspection - Commercial Passed 06/27/2005
Correction
Resolved
06/27/2005
None
Occupancy Inspection - Codes Commercial Partial 06/28/2005
Correction
Partial Correction
06/28/2005
Receive Public Works Approval SEE PUBLIC WORKS REQUIREMENTS. ENTRANCE AND EXIT TO THE BANK IS TO BE FROM LONGVIEW RD. THROUGH GRAVEL ENTRANCE ON THE WEST PARKING LOT. .ENTRANCE TO LONGVIEW FARM RD IS TO BE BLOCKED.
Correction
Corrective Action Required
06/28/2005
Receive Planning & Development Approval PLANING AND DEVELOPMENT PHONE # 969-7313
Correction
Resolved
06/28/2005
DOOR LATCH
Correction
Resolved
06/28/2005
SIDEWALKS REQUIRED ESCROW POSTED
Correction
Partial Correction
06/28/2005
Guards (IBC) COMPLETE GUARDRAILS AND HAND RAILS TO 2 ND FLOOR. 2 ND FLOOR NOT TO BE OCCUPIED. Stairway
Correction
Resolved
06/28/2005
ESCROW
Erosion Control Inspection Residential Passed 06/28/2005
Water Service Inspection Passed 02/02/2006
Correction
Resolved
02/02/2006
None
Correction
Resolved
02/02/2006
NOT READY
Correction
Resolved
02/02/2006
None
Rough Electrical Inspection - Commercial Passed 02/02/2006
Correction
Resolved
02/02/2006
None WEST SIDE
Occupancy Inspection - Codes Commercial Partial 02/02/2006
Correction
Resolved
02/02/2006
FOUNTAIN
Correction
Resolved
02/02/2006
ELEVATOR INSPECTION STATE INSPECTION REPORT IN PERMIT FILE
Correction
Resolved
02/02/2006
Guards (IBC) Stairway
Correction
Resolved
02/02/2006
SEE CORRECTIONS
Occupancy Inspection - Codes Commercial Passed 05/04/2007
Correction
Resolved
05/04/2007
Receive Public Works Approval
Correction
Resolved
05/04/2007
Receive Planning & Development Approval
Correction
Resolved
05/04/2007
None OCCUPANCY APPROVED CLOSE PERMIT C. O.
Sewer Service Inspection Passed 05/14/2007
Correction
Resolved
05/14/2007
None SEWER WAS APPROVED - UNKNOWN AS TO WHY IT DOSEN'T SHOW IN THE HISTORY.
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Citizens Union State Bank Re-Inspection
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home