Summary
B0401108
Building Permit - Commercial
Certificate of Occupancy
MEDICAL PLAZA INC
NEW COMMERCIAL
NEW COMMERCIAL BUILDING
06/15/2004
08/12/2004
02/08/2005
04/19/2005
Locations
Contacts
SHUKLA AND ASSOCIATES, Address:3693 W 129TH PLACE  
MEDICAL PLAZA INC, Address:2 NE SYCAMORE ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/12/2004 10/29/2010
Correction

CA - ANSI A117.1-1998 404.2.7 - Door Hardware. Handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. Such hardware shall be 34 inches minimum and 48 inches maximum above the floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.
Correction

CA - ANSI A117.1-1998 406.4 - Sides of Curb Ramps. Where pedestrians must walk across a curb ramp, the ramp shall have flared sides. Slope of flares shall not be steeper than 1:10. Where the width of the walking surface at the top of the ramp and parrellel to the run of the ramp is less than 48 inches (1220 mm) wide, the flared sides shall have a slope not steeper than 1:12. Curb ramps and returned curbs shall be permitted where pedestrians would not normally walk across the ramp.
Correction

Fire Department- A fire hydrant is required within 100 feet of the fire department connection (FDC) as the truck drives.
Correction

Fire Department- The fire department connection FDC shall be a 4" Storz and not a 2 1/2" siamese. The electric bell above the FDC to indicate water flow shall be replaced by a horn/strobe.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

Fire Department- Doors 108 and 116 need to swing in the direction of travel. IFC Sec. 1008.1.2.
Correction

CA - A one-hour fire-resistive wall is shown along the west side of the corridor. This wall is not required to be rated as there is no code requirement separating tenant spaces. If this wall is to remain rated than a damper is required on the supply air duct.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - 2000 IBC 1109.1 - Required accessible elements shall be identified by the International Symbol of Accessiblity at the locations listed in Section 1109.1. 1. Not applicable as the zoning ordinance is more restrictive. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1103.2.13.5. 4. Accessible rooms where multi single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting, and locker rooms where not all such rooms are accessible.
Correction

CA - 2000 IBC 1209.2 - Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Correction

CA - 2000 IBC 1209.1 - In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.3.1.6 - Thresholds. Thresholds at doorways shall not exceed 0.75 inch in height for sliding doors serving dwelling units or 0.5 inch for other doors. Raised thresholds and floor level changes greater then 0.25 inch at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50-percent slope).
Correction

CA - 2000 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as devined in Section 2406.2 shall pass the test requirements of CPSC 16 CFR 1201, listed in Chapter 35. Glazing shall comply with the CSPC 16 CFR, Part 1201 criteria for Category I or Category II as indicated in Table 2406.1.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - 2000 IPC 708.3.2 - Building sewers shall be provided with cleanouts located not more than 100 feet apart measured fron the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 feet of developed length of the drainage piping.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

A double check detector check valve assembly is required on the fire service line.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

CA - Placement of required exit signage and emergency lighting is subject to onsite inspection.
Correction

CA - 2000 IBC 1003.3.1.5 - Landings at doors. Landings shall have a width not less than the width of the stairway or the width of the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

CA - 2000 IMC 602.2.1 - Except as required by Section 602.2.1.1 through 602.2.1.4, materials exposed within plenumbs shall be noncombustible or shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E 84.
Correction

CA - 2000 IPC 403.2 - Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $2,087.00 $2,087.00 Paid 08/12/2004
24 BLDG Plan Check Fees $54.75 $54.75 Paid 08/12/2004
25 Electrical Permit Fee $243.50 $243.50 Paid 08/12/2004
25 Mechanical Permit Fees $115.00 $115.00 Paid 08/12/2004
25 Plumbing Permit Fees $135.00 $135.00 Paid 08/12/2004
84 Water Meters $600.00 $600.00 Paid 08/12/2004
85 Water Taps $6,835.00 $6,835.00 Paid 08/12/2004
89 Sewer Tap Fees $660.00 $660.00 Paid 08/12/2004
Right of Way Permit $35.00 $35.00 Paid 08/12/2004
84 Water Meters ($400.00) ($400.00) $0.00 N/A
85 Water Taps ($1,367.00) ($1,367.00) $0.00 N/A
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 09/13/2004
Correction
Partial Correction
09/13/2004
None BALANCE OF F LINE 2 THRU 7 PREVIOUS INSPECTION DATED 9/10 A LINE 1-9 9 LINE A-F F LINE 7-9 APPROVED
Piers/Caissons Inspection - Commercial Passed 09/13/2004
Correction
Resolved
09/13/2004
None INT COL PIERS APPROVED
Sewer Service Inspection Not Ready 09/13/2004
Correction
Corrective Action Required
09/13/2004
READY NOT READY
Footing Inspection - Commercial Passed 09/14/2004
Correction
Resolved
09/14/2004
EAST END (BALANCE OF) EXTERIOR WALL GRADE BEAM OK TO POUR WHEN READY INCL INTEGRAL COLUMN FTGS ENSURE 3" RE-BAR COVERAGE
Correction
Resolved
09/14/2004
None
Footing Inspection - Commercial Passed 09/15/2004
Correction
Resolved
09/15/2004
EAST END (BALANCE OF) EXTERIOR WALL GRADE BEAM INCL INTEGRAL COLUMN FTGS ENSURE 3" RE-BAR COVERAGE
Correction
Resolved
09/15/2004
None 9/10/04 INITIAL PARTIAL GRADE BEAM/FOOTING INSP
Underslab Plumbing Inspection - Commercial Passed 09/17/2004
Correction
Resolved
09/17/2004
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY EXCAVATED; LAID; JOINED PER PERMIT DRAWINGS
Sewer Service Inspection Passed 09/17/2004
Correction
Resolved
09/17/2004
SEWER SERVICE INSTALLATION OK TO COVER WHEN READY FROM BUILDING ENTRY TO EXSTG WYE
Correction
Resolved
09/17/2004
READY
Sewer Service Inspection - Commercial Request Complete 9/17/2004 9/17/2004 09/17/2004
Underslab Electrical Inspection - Commercial Passed 09/21/2004
Correction
Resolved
09/21/2004
UNDER-FLOOR ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP OK TO COVER WHEN READY
Water Service Inspection Partial 09/21/2004
Correction
Partial Correction
09/21/2004
WATER SERVICE INSTALLATION OK TO COVER WHEN READY FROM BUILDING ENTRY TO NEAR METER LOCATION
Water Service Inspection - Commercial Request Complete 9/20/2004 9/21/2004 09/21/2004
Water Service Inspection - Commercial Request Complete 9/23/2004 9/23/2004 09/23/2004
Electrical Service Inspection Partial 11/24/2004
Correction
Partial Correction
11/24/2004
TEMPORARY ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
Occupancy Inspection - Codes Commercial Not Ready 12/07/2004
Correction
Corrective Action Required
12/07/2004
DAMAGE TO ADJACENT PROPERTY TO NORTH RUTTED SOD + POTENTIALLY DAMAGE TO LAWN SPRINKLERS
All Rough Inspection - Commercial Not Ready 01/11/2005
Correction
Corrective Action Required
01/11/2005
RECEPTACLE/SWITCH BOX STAND-OFFS NOT IN PLACE @ ALL BOXES CANTILEVERED FROM STUDS
Correction
Corrective Action Required
01/11/2005
PROTECTION OF COPPER PIPING INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL AT PENETRATION OF STEEL FRAMING TOP TRACKS
Gas Service Inspection - Commercial Failed 01/11/2005
Correction
Corrective Action Required
01/11/2005
Gas Test Pressure (IRC) DECREASED DURING MONITORING PERIOD
Gas Service Inspection - Commercial Passed 01/26/2005
Correction
Resolved
01/26/2005
Gas Test Pressure (IRC) DECREASED DURING MONITORING PERIOD
Gas Piping Inspection - Commercial Failed 01/26/2005
Correction
Corrective Action Required
01/26/2005
Gas Piping --Protection From Damage (IRC) RAISE DRIP LEGS TO 6" ABOVE ROOF Roof
Electrical Service Inspection Passed 01/26/2005
Correction
Resolved
01/26/2005
None INSTALLED PER APPROVED PLANS
Correction
Resolved
01/26/2005
TEMPORARY ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE
Driveway Inspection Passed 03/07/2005
Sidewalk Inspection Partial 03/07/2005
Underground Electrical Inspection - Commercial Passed 03/08/2005
Correction
Resolved
03/08/2005
L.P. BASES + BURIED CONDUIT OK TO POUR AND BACKFILL WHEN READY. CONDUIT < 18" BELOW GRADE MUST BE CONCRETE ENCASED. GROUND NOT TO DRIVEN ROD PER APPROVED DRAWINGS; A/E VERIFIES DIRECT G.E.C. CONNECTION TO RE-BAR IN BASES ALREADY POURED. BASED ON A/E VERIFICATION OF DETAILS CONCEALED
Underground Electrical Inspection - Commercial Request Complete 3/8/2005 3/8/2005 03/08/2005
Above Ceiling Inspection Not Ready 03/09/2005
Correction
Corrective Action Required
03/09/2005
READINESS FOR INSPECTION IBC 109.1: REMOVE TILE FROM AREAS TO BE INSPECTED. CALL TO SCHEDULE WHEN READY WORK REQUESTED FOR INSP ALREADY COVERED
Above Ceiling Inspection Not Ready 03/10/2005
Correction
Corrective Action Required
03/10/2005
READINESS FOR INSPECTION IBC 109.1: REMOVE TILE FROM AREAS TO BE INSPECTED. CALL TO SCHEDULE WHEN READY 3/10/05 4:40 PM BUILDING LOCKED; NO ACCESS; NOT READY WORK REQUESTED FOR INSP ALREADY COVERED
Above Ceiling Inspection Not Ready 03/11/2005
Correction
Corrective Action Required
03/11/2005
FLEXIBLE DUCT INSTALLATION NOT PER ADC GUIDELINES SEE ATTACHED INSTAL INSTR
Correction
Corrective Action Required
03/11/2005
SHEET METAL DUCT SUPPORT & INSULATION INCOMPLETE JOINTS SOME NOT SUPPORTED INSULATION DAMAGED +
Correction
Corrective Action Required
03/11/2005
STATUS OF IN-WALL INSPECTION NO RECORD OF APPROVAL
Correction
Corrective Action Required
03/11/2005
READINESS FOR INSPECTION IBC 109.1: REMOVE TILE FROM AREAS TO BE INSPECTED. EXAMPLE: RMS 102; 104; 126; 131 WORK REQUESTED FOR INSP ALREADY COVERED
Above Ceiling Inspection Partial 03/14/2005
Correction
Resolved
03/14/2005
READINESS FOR INSPECTION
Correction
Resolved
03/14/2005
FLEXIBLE DUCT INSTALLATION
Correction
Resolved
03/14/2005
SHEET METAL DUCT SUPPORT & INSULATION
Correction
Resolved
03/14/2005
STATUS OF IN-WALL INSPECTION
Correction
Partial Correction
03/14/2005
ABOVE-CEILING SYSTEMS EXCEPT LEASE SPACE 145 OK TO COVER WHEN READY
Sidewalk Inspection Passed 03/14/2005
All Rough Inspection - Commercial Passed 03/15/2005
Correction
Resolved
03/15/2005
PROTECTION OF COPPER PIPING
Correction
Resolved
03/15/2005
RECEPTACLE/SWITCH BOX STAND-OFFS
Gas Piping Inspection - Commercial Passed 04/04/2005
Correction
Resolved
04/04/2005
Gas Piping --Protection From Damage (IRC) SEE FINAL INSPECTION
Water Service Inspection Passed 04/04/2005
Correction
Resolved
04/04/2005
WATER SERVICE INSTALLATION
Above Ceiling Inspection Passed 04/04/2005
Correction
Resolved
04/04/2005
ABOVE-CEILING SYSTEMS EXCEPT LEASE SPACE 145
Occupancy Inspection - Codes Commercial Not Ready 04/04/2005
Correction
Partial Correction
04/04/2005
OCCUPANCY APPROVAL STATUS OK FOR STAFF & EQUIPMENT SET-UP. NO PUBLIC UNTIL APPROVED. REQUEST FULL FINAL INSPECTION WHEN READY. REQUESTED PRELIMINARY INSPECTION 4/4/05
Occupancy Inspection - Codes Commercial Failed 04/07/2005
Correction
Resolved
04/07/2005
Receive Fire Department approval PER NEIL ULLERY 4/7/05
Correction
Corrective Action Required
04/07/2005
Receive Planning & Development Approval PHONE 969-7796 CONTACT TOM SCANNELL WHEN READY FOR INSPECTION
Correction
Corrective Action Required
04/07/2005
Receive Public Works Approval PER DISCUSSION WITH BILL LYON 4/7/05. PHONE 969-7324 INSTALL BARS AT OPENING OF STORM INLET
Correction
Resolved
04/07/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Corrective Action Required
04/07/2005
EXTERIOR BUILDING SIGNS PER NEC 600.3 REQUIRE SIGN PERMIT IF LIGHTED MUST BE LISTED
Correction
Corrective Action Required
04/07/2005
SPRINKLER FIRE PROTECTION DRAIN LINE TO SUPPLY RISER NOT PROTECTED FROM DAMAGE SECURE TO STRUCTURE OR
Correction
Partial Correction
04/07/2005
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Occupancy Inspection - Codes Commercial Passed 04/18/2005
Correction
Resolved
04/18/2005
DAMAGE TO ADJACENT PROPERTY TO NORTH ASSURED BY PERMIT HOLDER WILL BE DONE IMMENENTLY
Correction
Resolved
04/18/2005
Receive Planning & Development Approval PER TOM SCANNELL 4/18/05
Correction
Resolved
04/18/2005
Receive Public Works Approval PER B LYON 4/18/05
Correction
Resolved
04/18/2005
EXTERIOR BUILDING SIGNS PER NEC 600.3. NOTICE TO PERMIT HOLDER + PROPERTY OWNER. REQUIRE SIGN PERMIT IF LIGHTED MUST BE LISTED
Correction
Resolved
04/18/2005
SPRINKLER FIRE PROTECTION DRAIN LINE
Correction
Resolved
04/18/2005
OCCUPANCY APPROVAL STATUS
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Lee's Summit Medical Plaza
07/31/2017 Lee's Summit Medical Plaza Re-Inspection
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home