Summary
B0401037
Building Permit - Commercial
Certificate of Occupancy
HSM WDC PINETREE LLC
CHANGE OF TENANT
TENANT FINISH
06/04/2004
06/16/2004
12/13/2004
06/16/2004
Locations
Contacts
GOFORTH CONSTRUCTION, Address:14004 CENTURY LN  
HSM WDC PINETREE LLC, Address:12700 HILLCREST RD STE 125  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/01/2004 10/29/2010
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - For the Health Department inspection contact Bob Thomas with the Jackson County Public Works Department at 816-881-4530. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

Fire Department; Required means of egress components shall be maintained during construction and demolition.
Correction

CA - 2000 IPC 802.1.1 - Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Correction

CA - 2000 IPC 608.16.1 - Beverage dispensers. The water supply connection to carbonated beverage dispensers shall be protected against backflow by a double check valve with an intermediate atmospheric vent conforming to ASSE 1012 or ASSE 1022. The double check valve with an intermediate atmospheric vent device and the piping downstream therefrom shall not be affected by carbon dioxide gas. Secondary protection in the form of a dual check valve conforming to ASSE 1032 shall be installed on the beverage-dispensing equipment.
Correction

CA - 2000 IPC 802.2.1 - The air gap between the indirect waste pipe and the flood level rim of the waste receptor shall be a minimum of twice the effective opening of the indirect waste pipe.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $116.00 $116.00 Paid 06/16/2004
24 BLDG Plan Check Fees $11.50 $11.50 Paid 06/16/2004
25 Electrical Permit Fee $30.00 $30.00 Paid 06/16/2004
25 Mechanical Permit Fees $21.50 $21.50 Paid 06/16/2004
25 Plumbing Permit Fees $20.00 $20.00 Paid 06/16/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 06/23/2004
Correction
Resolved
06/23/2004
UNDER-SLAB DWV PIPING
All Rough Inspection - Commercial Passed 06/28/2004
Correction
Resolved
06/28/2004
IN-WALL SYSTEMS ROUGH PIPE PROTECTION CORRECTED ON-SPOT
Above Ceiling Inspection Not Ready 07/15/2004
Correction
Corrective Action Required
07/15/2004
READINESS FOR INSPECTION PRELIMINARY OBSERVATIONS PROVIDED TO GC SUPERVISOR. CALL FOR INSPECTION AFTER PREPARATION IS COMPLETE. WORK REQUESTED FOR INSP NOT COMPLETED
Above Ceiling Inspection Failed 07/16/2004
Correction
Resolved
07/16/2004
READINESS FOR INSPECTION
Correction
Corrective Action Required
07/16/2004
SECURE MC ELECTRICAL CABLE <= 6' LONG WITHIN 12" OF BOXES EXCEPT FIXTURE WHIPS IF
Correction
Corrective Action Required
07/16/2004
REMOVE UNUSED L.G. STEEL FRAMING NEAR SE CORNER
Correction
Corrective Action Required
07/16/2004
ELECTRICAL WIRING FOR EXTERIOR SIGNS SUBJECT TO APPROVAL SAME FOR SIGN LIGHTS
Above Ceiling Inspection Passed 07/27/2004
Correction
Resolved
07/27/2004
SECURE MC ELECTRICAL CABLE
Correction
Resolved
07/27/2004
REMOVE UNUSED L.G. STEEL FRAMING
Correction
Resolved
07/27/2004
ELECTRICAL WIRING FOR EXTERIOR SIGNS SEE FINAL INSPECTION
Occupancy Inspection - Codes Commercial Failed 07/27/2004
Correction
Corrective Action Required
07/27/2004
Receive Fire Department approval
Correction
Corrective Action Required
07/27/2004
Receive Water Utilities Approval
Correction
Corrective Action Required
07/27/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS NEC 110-22; 384-13: SOME BREAKERS NOT LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. SOME SCHEDULE NUMBERS DO NOT CORRESPOND WITH POSITION NUMBERS IN PANELS. INCOMPLETE/IMPROPER SERVICE PANELS
Correction
Corrective Action Required
07/27/2004
UNUSED OPENINGS AT ELECTRICAL PANELS NOT PLUGGED NEC 110-12
Correction
Corrective Action Required
07/27/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGN NOT IN PLACE
Occupancy Inspection - Codes Commercial Failed 07/29/2004
Correction
Resolved
07/29/2004
Receive Fire Department approval PER J EDEN 7/29/04 POST MAX OCCUPANT LOAD
Correction
Resolved
07/29/2004
LABELING OF ELECTRICAL CIRCUIT BREAKERS
Correction
Resolved
07/29/2004
UNUSED OPENINGS AT ELECTRICAL PANELS
Correction
Resolved
07/29/2004
HANDICAPPED ACCESSIBLE RESTROOM SIGN
Occupancy Inspection - Codes Commercial Passed 10/06/2004
Correction
Resolved
10/06/2004
Receive Fire Department approval
Correction
Resolved
10/06/2004
Receive Water Utilities Approval NO ISSUES BROUGHT FORTH
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home