Permit Application Status

B0400950


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B0400950
Building Permit - Commercial
Final Completion
DOUGLAS STATION SHOPPING CENTER LLC
NEW SHELL BUILDING
NEW SHELL BUILDING
05/25/2004
07/14/2004
01/10/2005
04/12/2005
Locations
Contacts
DAVIDSON DESIGN GROUP, Address:11301STRANG LINE ROAD  
CAPITAL CONSTRUCTION SERVICES, LLC, Address:839 NE WOODS CHAPEL RD  
DOUGLAS STATION SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/21/2004 10/29/2010
Correction

CA - The design of the retaining wall was not provided. Retaining wall over 4 feet in height measured from the bottom of the footing shall be designed by an engineer.
Correction

CA - Sheet A2.4 was not included with the application.
Correction

CA - The Sheet Index on the cover sheet does not include all sheets provided in the set.
Correction

P & D - The lengthened island on Sycamore Street shall be constructed per City standards prior to the issuance of any type of occupancy permit for Lot 1.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department; New and existing buildings shall have approved address numbers, building numbers, placed in a position to be plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background.
Correction

Fire Department: Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the code official is authorized to require a key box to be installed in an accessible location. The key box shall be of an approved type and shall contain keys to gain access as required by the code official.
Correction

Fire Department; Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - 2000 IPC 708.3.2 - Building sewers shall be provided with cleanouts located not more than 100 feet apart measured fron the upstream entrance of the cleanout. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 feet of developed length of the drainage piping.
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of akey or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

CA - 1999 NEC 250-104(a) - Metal water piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The points of attachment of the bonding jumper(s) shall be accessible.
Correction

CA - 1999 NEC 250-104(b) - Metal gas piping. Each aboveground portion of a gas piping system upstream from the equipment shutoff valve shall be electrically continuous and bonded to the grounding electrode system.
Correction

CA - The initial building permit issued for this property in Douglas Station Commercial Park will receive a water tap fee credit of $2,734.00. This credit will only be given on the domestic water tap for a building located on this property and no other.
Correction

A double check detector check valve assembly is required on the fire service line.
Correction

All backflow prevention assemblies must be tested and reports filed with the Lee's Summit Water Utilities Backflow Division (816-969-7636) within 30 days from the date installed.
Correction

Backflow prevention assembly must be located in an accessible location, min. 12" from floor, min. 6" from wall, max. 48" from floor.
Correction

CA - The allowable area calculation on the cover sheet is incorrect. There is a 300 percent increase in area allowed in fully sprinkled buildings. This makes the total allowable area 36,000 square feet without any setback requirements.
Correction

CA - The size of the buidling sewer is not indicated on the plans.
Correction

CA - 2000 IBC 1704.1.1 - The permit applicant shall submit a statement of special inspections prepared by the registered design professional in responsible charge in accordance with Section 106.1 as a condition for permit issuance. This statement shall include a complete list of materials and work requiring special inspections by this section, the inspections to be performed and a list of the individuals, approved agencies or firms intended to be retained for conducting such inspections.
Correction

CA - 2000 IBC 1704.1.2 - Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was done in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and the registered design professional in responsible charge prior to the completion of that phase of the work. A final report of inspections documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted periodically at a frequency agreed upon by the permit applicant and the building official prior to the start of work.
Correction

CA - 2000 IBC 1003.3.1.4 - Floor Elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal.
Correction

CA - 2000 IBC 1003.2.12 - Guards. Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 30 inches above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with Section 1607.7. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 30 inches above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in Section 1607.7. In addition, guards are required at retaining walls over 30 inches above grade when walking surfaces are within 10 feet of the high side of the retaining wall. (As amended in the Lee's Summit Code of Ordinances, Chapter 7, Section 7-216.)
Correction

CA - 2000 IBC 1202.2 - Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceiling are applied directly to the underside of roof framing member shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch of air space shall be provided between the insulation and the roof sheathing. The net free ventilating area shll not be less than 1/150 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet above the eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents.
Correction

Fire Department. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. The plans and specifications shall bear a State of Missouri licensed engineers seal. This includes fire sprinkler systems, grease hood and duct suppression systems as well as other fire suppression system.
Correction

Fire Department: Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurteances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. The code official shall be notified before any required acceptance testing. NOTE: Acceptance testing shall be scheduled at least 48 hours in advance by calling (816) 969-7343.
Correction

Fire Department; Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Documents shall bear a State of Missouri architect/engineers seal..Construction documents shall include, but not be limited to, all of the following: 1. A floor plan. 2. Locations of alarm-initiating and notification appli- ances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing informa- tion for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. 3. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Correction

CA - 2000 IMC 306.5 - Where equipment and appliances requireing access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shll be from grade or floor level to the equipment and appliances' level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - Sign permits must be obtained for all signs prior to installation. All signs shall comply with the sign requirements outlined in the UDO, Article 13.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - Erosion control devices shall be installed and maintained throughout the construction process in accordance with the City of Lee's Summit Design and Construction Manual. Failure to install or maintain erosion control devices may result in inspections not being performed, stop work orders being issued or court charges/action may be taken.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $1,463.00 $1,463.00 Paid 07/14/2004
24 BLDG Plan Check Fees $44.35 $44.35 Paid 07/14/2004
25 Electrical Permit Fee $329.00 $329.00 Paid 07/14/2004
25 Mechanical Permit Fees $176.50 $176.50 Paid 07/14/2004
25 Plumbing Permit Fees $29.00 $29.00 Paid 07/14/2004
84 Water Meters $600.00 $600.00 Paid 07/14/2004
85 Water Taps $4,101.00 $4,101.00 Paid 07/14/2004
Right of Way Permit $35.00 $35.00 Paid 07/14/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 08/03/2004
Correction
Partial Correction
08/03/2004
PERIMETER WALL GRADE BEAM WEST WALL; ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 08/06/2004
Correction
Partial Correction
08/06/2004
PERIMETER WALL GRADE BEAM WEST WALL; N WALL EXCEPT W 40` & E 15`; N-S GB COMPLETE @ (7); ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 08/09/2004
Correction
Partial Correction
08/09/2004
PERIMETER WALL GRADE BEAM WEST WALL; N WALL EXCEPT W 40` & E 15`; N-S GB COMPLETE @ (7); E 15` OF N WALL + E WALL S TO (B.8); ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 08/10/2004
Correction
Partial Correction
08/10/2004
PERIMETER WALL GRADE BEAM WEST WALL; N WALL EXCEPT W 40` & E 15`; N-S GB COMPLETE @ (7); E 15` OF N WALL + E WALL S TO (B.8); E WALL S TO (D) + W ON (D) & (C) TO (5.2); ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Electrical Service Inspection Partial 08/10/2004
Correction
Partial Correction
08/10/2004
TEMPORARY ELECTRICAL SERVICE INSTALLATION 200 AMP RELEASE SERVICE
Footing Inspection - Commercial Partial 08/12/2004
Correction
Partial Correction
08/12/2004
PERIMETER WALL GRADE BEAM WEST WALL; N WALL EXCEPT W 40` & E 15`; N-S GB COMPLETE @ (7); E 15` OF N WALL + E WALL S TO (B.8); E WALL S TO (D) + W ON (D) & (C) TO (5.2); SW CORNER + NW CORNER TO COMPLETE PERIMETER ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Partial 08/13/2004
Correction
Partial Correction
08/13/2004
ISOLATED COLUMN FOOTINGS 6 ALONG (B); ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Correction
Resolved
08/13/2004
PERIMETER WALL GRADE BEAM
Water Service Inspection Passed 09/03/2004
Water Service Inspection - Commercial Request Complete 9/3/2004 9/3/2004 09/03/2004
Sewer Service Inspection Passed 09/13/2004
Sewer Service Inspection - Commercial Request Complete 9/13/2004 9/13/2004 09/13/2004
Underslab Plumbing Inspection - Commercial Not Ready 09/17/2004
Correction
Corrective Action Required
09/17/2004
READINESS FOR INSPECTION REQUESTED FOR INSP 9/20
Underslab Plumbing Inspection - Commercial Passed 09/21/2004
Correction
Resolved
09/21/2004
UNDER-SLAB DWV PIPING OK TO COVER WHEN READY EXCAVATED; LAID; JOINED SLOPED TO DRAIN
Correction
Resolved
09/21/2004
READINESS FOR INSPECTION
Footing Inspection - Commercial Partial 09/29/2004
Correction
Partial Correction
09/29/2004
ISOLATED COLUMN FOOTINGS 6 ALONG (B); (2) THRU (11) ON (E) & (F); ENSURE 3" RE-BAR COVERAGE OK TO POUR WHEN READY
Footing Inspection - Commercial Passed 10/06/2004
Correction
Resolved
10/06/2004
FOOTING FOR RETAINING WALL @ SW BLDG CORNER OK TO POUR WHEN READY
Correction
Resolved
10/06/2004
ISOLATED COLUMN FOOTINGS
Underground Electrical Inspection - Commercial Passed 11/17/2004
Correction
Resolved
11/17/2004
PRIMARY SERVICE CONDUIT INCLUDING DRIVEN GROUND ROD @ METER BANK. ALL OK TO COVER WHEN READY FROM XFRMR POLE TO METER BANK
Electrical Service Inspection Partial 11/23/2004
Correction
Resolved
11/23/2004
TEMPORARY ELECTRICAL SERVICE INSTALLATION
Correction
Partial Correction
11/23/2004
HOUSE METER ONLY 100 AMP RELEASE ONE METER
Rough Framing Inspection - Commercial Passed 12/09/2004
Correction
Resolved
12/09/2004
ROOF TRUSS FRAMING @ HIGH CENTER ROOF OK TO COVER WHEN READY
Above Ceiling Inspection Partial 12/16/2004
Correction
Partial Correction
12/16/2004
FRONT ENTRANCE CANOPY COVER AT RISK; FIXTURE LISTING TO BE ESTABLISHED. CAN LIGHT FIXTURES UL LABELS NOT FOUND
Underground Electrical Inspection - Commercial Partial 12/22/2004
Correction
Partial Correction
12/22/2004
SITE LIGHTING CONDUIT TO 5 0F 6 LIGHT POLES OK TO COVER; NOT READY: CONDUIT TO FAR NE POLE; POLE BASE FORMING, REINFORCING, GROUNDING NOT READY OK TO COVER WHEN READY ITEMS AS INDICATED BELOW:
Piers/Caissons Inspection - Commercial Failed 12/29/2004
Correction
Corrective Action Required
12/29/2004
STEEL REBAR IS NOT AS SHOWN ON APPROVED PLANS.
Rough Electrical Inspection - Commercial Partial 12/29/2004
Correction
Partial Correction
12/29/2004
None ELECT. CONDUIT AND GROUND FOR 4 LIGH POLE APPROVED. 3 SOUTH LIGHT AND 1 WEST LIGHT BASE.
Gas Service Inspection - Commercial Partial 02/21/2005
Correction
Partial Correction
02/21/2005
TEMPORARY SERVICE TO SUITES IN RANGE 32-56 PIPING PRESSURE TEST TO BE REPEATED WHEN EQUIPMENT IS INSTALLED AND PIPING IS COMPLETED. RELEASE SERVICE TO SUITES: 32; 36; 40; 44; 48; 56 TO BE RE-TESTED - DO NOT RELEASE: 52 FOR CONSTRUCTION USE ONLY RELEASE SERVICE
Correction
Partial Correction
02/21/2005
TEMPORARY SERVICE TO RESTAURANT @ SUITE 20-28 PIPING PRESSURE TEST TO BE REPEATED WHEN EQUIPMENT IS INSTALLED AND PIPING IS COMPLETED FOR CONSTRUCTION USE RELEASE SERVICE
Gas Service Inspection - Commercial Partial 02/22/2005
Correction
Resolved
02/22/2005
TEMPORARY SERVICE TO SUITES IN RANGE 32-56 PIPING PRESSURE TEST TO BE REPEATED WHEN EQUIPMENT IS INSTALLED AND PIPING IS COMPLETED. RELEASE SERVICE TO SUITES: 32; 36; 40; 44; 48; 52; 56 RELEASE SERVICE
Correction
Partial Correction
02/22/2005
TEMPORARY SERVICE TO RESTAURANT @ SUITE 20-28
Gas Piping Inspection - Commercial Passed 02/22/2005
Underground Electrical Inspection - Commercial Partial 02/24/2005
Correction
Partial Correction
02/24/2005
SITE LIGHTING OK TO POUR WHEN READY: 4 BASES ALONG SOUTH SIDE OF LOT NOT READY: 2 BASES ALONG EAST END OF LOT OK TO COVER WHEN READY ITEMS AS INDICATED BELOW:
Underground Electrical Inspection - Commercial Request Complete 2/24/2005 2/24/2005 02/24/2005
Footing Inspection - Commercial Passed 03/01/2005
Correction
Resolved
03/01/2005
None THE 2 EAST LIGHT POLE BASES APPROVED PER PLANS.
Underground Electrical Inspection - Commercial Partial 03/01/2005
Correction
Partial Correction
03/01/2005
None 2 - EAST LIGHT POLE BASES - APPROVED
Underground Electrical Inspection - Commercial Request Complete 2/28/2005 3/1/2005 03/01/2005
Piers/Caissons Inspection - Commercial Passed 03/23/2005
Correction
Resolved
03/23/2005
STEEL
Above Ceiling Inspection Passed 03/23/2005
Correction
Resolved
03/23/2005
FRONT ENTRANCE CANOPY
Underground Electrical Inspection - Commercial Passed 03/23/2005
Correction
Resolved
03/23/2005
PRIMARY SERVICE CONDUIT
Correction
Resolved
03/23/2005
SITE LIGHTING
Correction
Resolved
03/23/2005
None
Rough Electrical Inspection - Commercial Passed 03/23/2005
Correction
Resolved
03/23/2005
None
Electrical Service Inspection Passed 03/23/2005
Correction
Resolved
03/23/2005
HOUSE METER ONLY 100 AMP RELEASE ONE METER
Final Inspection - Commercial Not Ready 03/23/2005
Correction
Corrective Action Required
03/23/2005
Receive Planning & Development Approval
Correction
Corrective Action Required
03/23/2005
Receive Public Works Approval
Correction
Corrective Action Required
03/23/2005
Receive Water Utilities Approval
Correction
Corrective Action Required
03/23/2005
Receive Fire Department approval
Gas Service Inspection - Commercial Passed 03/23/2005
Correction
Resolved
03/23/2005
TEMPORARY SERVICE TO RESTAURANT @ SUITE 20-28
Correction
Resolved
03/23/2005
TEMPORARY SERVICE TO SUITES IN RANGE 32-56
Final Inspection - Commercial Failed 03/25/2005
Correction
Corrective Action Required
03/25/2005
Receive Fire Department approval CONTACT NEIL ULLERY PHONE 969-7427
Correction
Corrective Action Required
03/25/2005
Receive Planning & Development Approval CONTACT TOM SCANNELL PHONE 969-7796
Correction
Corrective Action Required
03/25/2005
Receive Public Works Approval CONTACT BILL LYON PHONE 969-7324
Correction
Corrective Action Required
03/25/2005
Receive Water Utilities Approval CONTACT BRENT BOICE PHONE 969-7611
Correction
Resolved
03/25/2005
TEMPORARY USE APPROVAL STATUS OUTSTANDING ISSUES OK THROUGH 4/21/05 PENDING RESOLUTION OF
Final Inspection - Commercial Failed 04/07/2005
Correction
Resolved
04/07/2005
Receive Fire Department approval PER NEIL ULLERY 4/7/05
Correction
Resolved
04/07/2005
Receive Public Works Approval PER BILL LYON 4/7/05
Correction
Resolved
04/07/2005
Receive Water Utilities Approval NO ISSUES PRESENTED
Final Inspection - Commercial Passed 04/11/2005
Correction
Resolved
04/11/2005
Receive Planning & Development Approval PER TOM SCANNELL
Correction
Resolved
04/11/2005
TEMPORARY USE APPROVAL STATUS N/A
Documents & Images
Date Uploaded File Type Document Name
07/31/2017 Douglas Station Retail Building-LaFuente
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home