Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/17/2004 10/29/2010
Correction

Fire Department- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devises shall be of an approved type. IFC 1003.3.1.8
Correction

1003.2.10.1 Fire Department- Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign.
Correction

Fire Department- Notification devices for the existing alarm system shall be extended into the remodeled spaces.
Correction

CA - 2000 IBC 716.2 - Fireblocking. In combustible construction, fireblocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fireblocking shall be installed in the locations specified in Sections 716.2.2 through 716.2.7.
Correction

CA - The disposal of demolition waste is regulated by the Department of Natural Resources under Chapter 260 RSMO. Such waste, in types and quantities established by the department, shall be taken to a demolition landfill or a sanitary landfill for disposal.
Correction

CA - No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

CA - Each structure shall have the address of that structure visibly posted on the jobsite throughtout the construction process.
Correction

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The occupancy and or final inspection shall be scheduled with the Codes Administration Department and requires a minimum of two (2) working days notice. Codes Administration will contact the appropriate city departments and will notify the applicant of the date and time the inspection will be performed.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

Fire Department; The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance rated assemblies shall be protected by self-closing or automatic- closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department; Portable fire extinguishers shall be installed in occupancies and locations as set forth in the IFC Sec. 906 and as required by the Code Offical. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

CA - LSCO Chapter7, Section 117 - Materials, equipment, and devices approved by the building official shall be constructed and installed in accordance with such approval.
Correction

CA - LSCO 7-134 - Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Permits for exterior work, i.e., walls, fences, decks, patios, patio covers and similar type work requiring permits, as well as permits for residential room additions and remodels shall be limited to 180 days duration. Permits for other new construction shall be limited to one-year duration. The building official official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each.
Correction

CA - LSCO 7-162 - It shall be the duty of the holder of the permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspection of such work for any inspections that are required by this code. Inspection requests shall be made in advance and in accordance with the most current written policies of the Codes Administration Department.
Correction

CA - LSCO7-168 - The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The building official shall set a time period during which the temporary certificate of occupancy is valid.
Correction

P & D - All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $272.00 $272.00 Paid 06/18/2004
24 BLDG Plan Check Fees $19.00 $19.00 Paid 06/18/2004
25 Electrical Permit Fee $39.55 $39.55 Paid 06/18/2004
25 Mechanical Permit Fees $30.50 $30.50 Paid 06/18/2004
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 07/23/2004
Correction
Partial Correction
07/23/2004
FRAMING + IN-WALL & ABOVE-CEILING SYSTEMS MECH B02 OK TO COVER AFTER LIGHT SWITCH WIRING IS IN PLACE; PHASE 1 1ST FLR OK TO COVER AFTER OLD ELECTRICAL WIRING & EQUIPMENT IS REMOVED - EXCEPT 6 OVERBORED STUDS MARKED @ S WALL REQUIRE REINSPECTION; OK TO COVER WHEN READY IN AREAS INDICATED:
All Rough Inspection - Commercial Passed 07/27/2004
Correction
Resolved
07/27/2004
FRAMING + IN-WALL & ABOVE-CEILING SYSTEMS
Above Ceiling Inspection Failed 08/26/2004
Correction
Corrective Action Required
08/26/2004
PHASE 1 ONLY - INTEGRITY OF 1-HR HARD LID HOLES & PENETRATIONS NOT FIRE-CAULKED OR MUDDED; COMBUSTIBLE MATERIALS PROTRUDING THROUGH GWB. NOT FIRE BLOCKED FOR 1-HR RATING
Correction
Corrective Action Required
08/26/2004
BARE ELECTRICAL CONDUCTORS @ RM104 SE PROTRUDING THRU HARD LID
Above Ceiling Inspection Passed 08/27/2004
Correction
Resolved
08/27/2004
BARE ELECTRICAL CONDUCTORS @ RM104 SE
Correction
Resolved
08/27/2004
PHASE 1 ONLY - INTEGRITY OF 1-HR HARD LID
Occupancy Inspection - Codes Commercial Failed 10/27/2004
Correction
Corrective Action Required
10/27/2004
PERMANENT LABELING OF CIRCUIT BREAKERS ELECTRICAL SERVICE PANEL INCOMPLETE
Correction
Corrective Action Required
10/27/2004
HANDRAILS @ BASEMENT STAIRWAY NOT INSTALLED
Correction
Corrective Action Required
10/27/2004
BASEMENT MECHANICAL ROOM COMPLETE &OBTAIN APPROVAL
Correction
Corrective Action Required
10/27/2004
MEANS OF EGRESS AT EXISTING CORRIDOR PROVIDE COMPLIANT PATH SOUTH TO EXTERIOR
Occupancy Inspection - Codes Commercial Failed 10/29/2004
Correction
Corrective Action Required
10/29/2004
PERMANENT LABELING OF CIRCUIT BREAKERS ELECTRICAL SERVICE PANEL INCOMPLETE
Correction
Corrective Action Required
10/29/2004
HANDRAILS @ BASEMENT STAIRWAY INSTALLED BUT ENDS NOT RETURNED TO WALL
Correction
Resolved
10/29/2004
BASEMENT MECHANICAL ROOM
Correction
Corrective Action Required
10/29/2004
MEANS OF EGRESS AT EXISTING CORRIDOR OBTAIN FD APPROVAL INSTALL LIGHTING + EMERGENCY SYSTEMS PROVIDE COMPLIANT PATH SOUTH TO EXTERIOR
Occupancy Inspection - Codes Commercial Failed 12/02/2004
Correction
Corrective Action Required
12/02/2004
Receive Fire Department approval
Correction
Resolved
12/02/2004
Receive Water Utilities Approval NO ISSUES PRESENTED
Correction
Resolved
12/02/2004
PERMANENT LABELING OF CIRCUIT BREAKERS
Correction
Resolved
12/02/2004
HANDRAILS @ BASEMENT STAIRWAY
Correction
Resolved
12/02/2004
MEANS OF EGRESS AT EXISTING CORRIDOR
Occupancy Inspection - Codes Commercial Passed 12/07/2004
Correction
Resolved
12/07/2004
Receive Fire Department approval PER N ULLERY 12/3/04
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home